Turn the knob (

dia-

gram. 56

) to switch the

boiler ON and OFF: cloc-
kwise to increase the
temperature, anti-cloc-
kwise to decrease. The
burner will automatically
turn ON at full rating, at
reduced rating, or will
turn OFF.

COMMISSIONING

Reg 012

Diagram. 56

Allow the temperature to rise to the maximum

value, with all radiator valves open. The tempera-
ture rise will cause release of the gases contained
in the water of the central heating system :
- Gases driven toward the boiler will be automati-
cally exhausted through the automatic air vent.
-  The gases trapped at the highest point of the
system must be released by bleeding the radia-
tors.
On reaching maximum temperature, the boiler
should be turned off and the system drained  off
as rapidly as possible whilst still hot.

Refill the system to a pressure of 1 bar and vent

as before.

Restart the boiler and operate until maximum

temperature is reached. Shut down the boiler and
vent the heating system. If necessary, top up the
heating system and make sure that a pressure of
1 bar is indicated on the pressure gauge when
the system is COLD.

Starting the boiler

Before starting the boiler check that:
- The gas meter tap is open. If using butane or
propane, check that valve on storage cylinder
or tank is open.
- The boiler gas service cock is open.
- The boiler is connected to the electrical supply
and switched on.
- The selector lever is in the left hand position.

Gas pressures

The main burner pressure should be checked dur-
ing commissioning to make sure the correct in-
put is obtained. Proceed as follows :

Shut down boiler.

Remove screw from test point on main burner,

below sealed chamber of boiler (

see diag. 57

).

Connect a suitable pressure gauge.

Set selector lever to right hand, heating and hot

water position.

Start boiler as described in ‘Instructions for Use’

Set control thermostat to maximum, fully

clockwise, and check that any external controls
are calling for heat.

Check that the reading on the gauge matches

that given in ‘Technical Data’ for the type of gas
being used.

Move the selector lever to the left hand position,

remove the pressure gauge, replace test point
screw and check for gas soundness.

If measured burner pressure differs greatly from

the given figure, check the gas inlet pressure as
follows:

Shut down boiler.

Remove screw from inlet test point at rear of

multi-functional control.

Connect a suitable pressure gauge.

Start boiler as described in ‘Instructions for Use’

Check that the inlet pressure reading on the

gauge matches that given in ‘Technical Data’ for
the type of gas being used.

Shut down boiler.

Remove the pressure gauge, replace test point

screw and check for gas soundness.

If the gas pressure is incorrect, refer to the Fault

Finding section in servicing instructions.

If inlet pressure is below that given, the gas sup-

ply pipework/meter must be checked and any
fault corrected.

In the case of an LPG installation, check the stor-

age tank or cylinder, regulator and pipework.

Des 044

Diagram. 57

Содержание THELIA 23

Страница 1: ...1 THELIA THIS IS A CAT II2H3 APPLIANCE 01773 828100 IN WARRANTY TECHNICAL HELPLINE 01773 828400...

Страница 2: ...marked on the label attached to the inside of the door Refer to the Introduction section page 3 for a description of the basic functions of the boiler The Users section describes how to safely operate...

Страница 3: ...2H3 Gas Category for use with natural gas G20 as distributed in the United Kingdom or with butane or propane gas G30 31 These instructions should be carefully followed for the safe and economical use...

Страница 4: ...043a Hab 130 Note On pressing the ON button the fan will be heard to run at full speed after which the ignition sequence will start and the pilot will light Should the pilot fail to remain alight or g...

Страница 5: ...33 Diag 7 HEATING HOT WATER Place the selector lever diagram 4 to position winter In this position the domestic hot water will have PRIORITY HEATING ONLY Turn the selector switch diagram 8 to position...

Страница 6: ...four hour format for example 1300 for 1pm see diagram 12 Helpful Hint The and buttons are used to change times Press and release for small changes If you press and hold down the time will run To Set...

Страница 7: ...ton again The display will now show the first Off time you have just entered Repeattheabovefortheremaining On and Off times When you have set the On and Off times you require place the slide switch to...

Страница 8: ...during a holiday After the programmed time has gone by the boiler returns to its normal programmes To set the Hold or Holiday feature carry on as follows Place the slide switch to Timer the letter h w...

Страница 9: ...boiler The valve MUST NOT BE TOUCHED except by a competent person If the valve discharges at any time switch the boiler off and isolate it from the electrical supply Contact your installation servic i...

Страница 10: ...e in sanitary hot water mode l min 3 3 Specific flow rate for 30 C temperature rise l min 11 11 Mini supply pressure bar 0 3 0 3 Max supply pressure bar 10 10 Electrical supply V 230 230 230 Amperage...

Страница 11: ...pen open 1 turn open 3 turns open 2 turns Pressure loss between flow and return boiler connections metres head Heat output kW 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 3 Btu h 30387 34142 37557 40...

Страница 12: ...ver 8 Expansion vessel 9 Pump 10 Automatic air vent 11 Burner 12 Heat exchanger air vent 13 Heat exchanger 14 Multi functional control 15 Safety electrovalve THELIA 23 E only 16 Hight limit thermostat...

Страница 13: ...23 Airflow switch A Heating return C Heating flow F Gas inlet 1 ON push button 2 OFF push button 3 Spark generator 4 Central heating water temperature adjustment 5 Temperature gauge 6 Pressure gauge 8...

Страница 14: ...5a A Heating return with isolating valve m B Cold water inlet with isolating valve p C Heating flow with isolating valve q drain screw r and safety valve s D Domestic hot water out E Electrical connec...

Страница 15: ...e with any type of installation Heating surfaces may consist of radiators convectors or fan assisted convectors Caution if the materials used are of different types corrosion phenomena may develop In...

Страница 16: ...emplate on wall in required position mak ing allowance for the necessary clearances etc Mark the position of the holes for the hook and the connecting plate Drill plug and fix the connecting plate and...

Страница 17: ...t window 400 F from an adjacent air vent 600 G from vertical or horizontal air pipes 600 H from an external corner of the building 300 I from an internal corner of the building 1000 L from the ground...

Страница 18: ...e installation of this boiler must be carried out by a competent person in accordance with the relevant requirements of the current issue of The Gas Safety Installation and Use Regulations The Buildin...

Страница 19: ...29 E F D C B A 234 50 mini 29 60 255 mini Diagram 30 Cutting the flue hole Making allowance for the slope of the flue cut the hole in the external wall preferably using a 115 mm diameter core drill I...

Страница 20: ...redu ced in this way it will be necessary to drill two fixing holes in these pipes to match the fixing holes in the aluminium connector The PVC connector is used to connect the PVC extension pipe to...

Страница 21: ...m 41 Important the gas connection must be made first as there is no flexibility in this connection Do not forget the sealing washer Connect the aluminium pipe onto the central outlet of either the str...

Страница 22: ...plate to leave fan outlet pointing upward Using the alternative set of three holes in the mounting plate fasten the fan to the mounting plate see diagram 45 Disconnect air pressure switch tube from re...

Страница 23: ...d see diagram 41 Important The gas connection must be made first as there is no flexibility in this connection Do not forget the sealing washer Fit the internal plastic flange Q Push it along the pipe...

Страница 24: ...any of the terminals of this plug All models In case of difficulty obtaining a suitable timeclock room thermostat a programmable room thermo stat is available as an accessory Saunier Duval part number...

Страница 25: ...plug Voltage free room thermostat Do not connect Voltage free room thermostat Do not connect Voltage free cylinder thermostat External controls plug Time clock External controls plug Timeclock room th...

Страница 26: ...Filling the system With the selector diagram 51 or 52 in the winter position or open the shut off valves q m and p diagram 53 the slot of the screw corres ponds to flow direction the bleed plug situat...

Страница 27: ...he left hand position Gas pressures The main burner pressure should be checked dur ing commissioning to make sure the correct in put is obtained Proceed as follows Shut down boiler Remove screw from t...

Страница 28: ...ure shown on the pressure gauge diag 58 is less than 1 bar the system must be filled up immediately Call the nearest after sales service department Air in the heating system Persistent air in the heat...

Страница 29: ...run when the burner is lit and will continue to run after burner extinction This can be useful on certain installa tions that requireconstant heating water circula tion To change the pump operation t...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...32 Le Technipole 8 av Pablo Picasso 94132 Fontenay sous Bois cedex T l phone 1 49 74 11 11 T lex 262 958 T l copie 1 49 74 11 01 102740 D 08 96...

Отзывы: