Diagram 38

Locking fitting end

Diagram 39

Installation of flue assembly

Fit the PVC pipe (

A

) into the wall with locking

fitting end to outside.

Fit the rubber sealing collar (

C

) into the groove

at the outer end of the PVC pipe.

Pull the PVC pipe inwards to bring the rubber

sealing collar hard against the external wall, see

diagram 40

.

Spot drill two holes using a 2.5 mm drill through

the flange and PVC pipe.

Fasten the flange to the PVC pipe using the two

self tapping screws provided.

From inside, fully insert the aluminium pipe (

B

),

locking end first, into the PVC pipe. Turn aluminium
pipe anticlockwise, viewed from inside, as far as
possible.

Fit the rubber connecting sleeve (

D

), plain end

first, onto the end of the PVC pipe. Push it on as
far as possible.

Lift the boiler and engage both fixing jig hooks

in the two support brackets on the back of the
boiler.

Lower the boiler until it rests on the outward

facing lip at the centre of the connecting plate.

Make the connections between the boiler and

connecting plate using the sealing washers, flow
regulator and filters provided, see 

diagram 41

.

Important : 

the gas connection must be made first

as there is no flexibility in this connection. Do not
forget the sealing washer.

Connect the aluminium pipe onto the central

outlet of either the straight flue connector or the
flue elbow. To do this, the aluminium pipe must be
held and turned clockwise, as viewed from inside.
The aluminium pipe will move out from the PVC
pipe and can be twisted onto the centre of the
flue connector or elbow.

Make sure that aluminium pipe is firmly fixed

either to the flue connector or elbow and is
correctly locked into the PVC outer pipe.

Note. 

The aluminium pipe is correctly fitted and

locked only when the concentric spacer is FLUSH
with the outermost end of the PVC pipe, see

diagram 42

.

After checking that the aluminium pipe is

correctly fitted, pull the rubber sleeve towards the
boiler and fit the flanged end fully over the spigot
of the boiler flue connector or elbow, to make a
seal.

Diagram 40

Diagram 41

Diagram 42

Cutting lenght

PVC pipe

Extension PVC pipe

Aluminium pipe

Extension aluminium pipe

Cutting lenght

1

2

3

5

6

7

4

55

55

57,5

57,5

r

p

q

34

25

23

11

3

s

33

A

B

C

D

F

E

m

REAR OUTLET FLUE ASSEMBLY

Extension PVC pipe

Extension aluminium pipe

This dimension must 
be 30 mm or greater

V

en 086

V

en 087

Pho 087

Pla 105a

V

en 088a

Содержание THELIA 23

Страница 1: ...1 THELIA THIS IS A CAT II2H3 APPLIANCE 01773 828100 IN WARRANTY TECHNICAL HELPLINE 01773 828400...

Страница 2: ...marked on the label attached to the inside of the door Refer to the Introduction section page 3 for a description of the basic functions of the boiler The Users section describes how to safely operate...

Страница 3: ...2H3 Gas Category for use with natural gas G20 as distributed in the United Kingdom or with butane or propane gas G30 31 These instructions should be carefully followed for the safe and economical use...

Страница 4: ...043a Hab 130 Note On pressing the ON button the fan will be heard to run at full speed after which the ignition sequence will start and the pilot will light Should the pilot fail to remain alight or g...

Страница 5: ...33 Diag 7 HEATING HOT WATER Place the selector lever diagram 4 to position winter In this position the domestic hot water will have PRIORITY HEATING ONLY Turn the selector switch diagram 8 to position...

Страница 6: ...four hour format for example 1300 for 1pm see diagram 12 Helpful Hint The and buttons are used to change times Press and release for small changes If you press and hold down the time will run To Set...

Страница 7: ...ton again The display will now show the first Off time you have just entered Repeattheabovefortheremaining On and Off times When you have set the On and Off times you require place the slide switch to...

Страница 8: ...during a holiday After the programmed time has gone by the boiler returns to its normal programmes To set the Hold or Holiday feature carry on as follows Place the slide switch to Timer the letter h w...

Страница 9: ...boiler The valve MUST NOT BE TOUCHED except by a competent person If the valve discharges at any time switch the boiler off and isolate it from the electrical supply Contact your installation servic i...

Страница 10: ...e in sanitary hot water mode l min 3 3 Specific flow rate for 30 C temperature rise l min 11 11 Mini supply pressure bar 0 3 0 3 Max supply pressure bar 10 10 Electrical supply V 230 230 230 Amperage...

Страница 11: ...pen open 1 turn open 3 turns open 2 turns Pressure loss between flow and return boiler connections metres head Heat output kW 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 3 Btu h 30387 34142 37557 40...

Страница 12: ...ver 8 Expansion vessel 9 Pump 10 Automatic air vent 11 Burner 12 Heat exchanger air vent 13 Heat exchanger 14 Multi functional control 15 Safety electrovalve THELIA 23 E only 16 Hight limit thermostat...

Страница 13: ...23 Airflow switch A Heating return C Heating flow F Gas inlet 1 ON push button 2 OFF push button 3 Spark generator 4 Central heating water temperature adjustment 5 Temperature gauge 6 Pressure gauge 8...

Страница 14: ...5a A Heating return with isolating valve m B Cold water inlet with isolating valve p C Heating flow with isolating valve q drain screw r and safety valve s D Domestic hot water out E Electrical connec...

Страница 15: ...e with any type of installation Heating surfaces may consist of radiators convectors or fan assisted convectors Caution if the materials used are of different types corrosion phenomena may develop In...

Страница 16: ...emplate on wall in required position mak ing allowance for the necessary clearances etc Mark the position of the holes for the hook and the connecting plate Drill plug and fix the connecting plate and...

Страница 17: ...t window 400 F from an adjacent air vent 600 G from vertical or horizontal air pipes 600 H from an external corner of the building 300 I from an internal corner of the building 1000 L from the ground...

Страница 18: ...e installation of this boiler must be carried out by a competent person in accordance with the relevant requirements of the current issue of The Gas Safety Installation and Use Regulations The Buildin...

Страница 19: ...29 E F D C B A 234 50 mini 29 60 255 mini Diagram 30 Cutting the flue hole Making allowance for the slope of the flue cut the hole in the external wall preferably using a 115 mm diameter core drill I...

Страница 20: ...redu ced in this way it will be necessary to drill two fixing holes in these pipes to match the fixing holes in the aluminium connector The PVC connector is used to connect the PVC extension pipe to...

Страница 21: ...m 41 Important the gas connection must be made first as there is no flexibility in this connection Do not forget the sealing washer Connect the aluminium pipe onto the central outlet of either the str...

Страница 22: ...plate to leave fan outlet pointing upward Using the alternative set of three holes in the mounting plate fasten the fan to the mounting plate see diagram 45 Disconnect air pressure switch tube from re...

Страница 23: ...d see diagram 41 Important The gas connection must be made first as there is no flexibility in this connection Do not forget the sealing washer Fit the internal plastic flange Q Push it along the pipe...

Страница 24: ...any of the terminals of this plug All models In case of difficulty obtaining a suitable timeclock room thermostat a programmable room thermo stat is available as an accessory Saunier Duval part number...

Страница 25: ...plug Voltage free room thermostat Do not connect Voltage free room thermostat Do not connect Voltage free cylinder thermostat External controls plug Time clock External controls plug Timeclock room th...

Страница 26: ...Filling the system With the selector diagram 51 or 52 in the winter position or open the shut off valves q m and p diagram 53 the slot of the screw corres ponds to flow direction the bleed plug situat...

Страница 27: ...he left hand position Gas pressures The main burner pressure should be checked dur ing commissioning to make sure the correct in put is obtained Proceed as follows Shut down boiler Remove screw from t...

Страница 28: ...ure shown on the pressure gauge diag 58 is less than 1 bar the system must be filled up immediately Call the nearest after sales service department Air in the heating system Persistent air in the heat...

Страница 29: ...run when the burner is lit and will continue to run after burner extinction This can be useful on certain installa tions that requireconstant heating water circula tion To change the pump operation t...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...32 Le Technipole 8 av Pablo Picasso 94132 Fontenay sous Bois cedex T l phone 1 49 74 11 11 T lex 262 958 T l copie 1 49 74 11 01 102740 D 08 96...

Отзывы: