background image

3

ENGLISH

 

1.- TECHNICAL SPECIFICATIONS

 

NOTE:

Las capacidades se basan en la temperatura del aire de 
entrada de: 27 ºC Bulbo Seco / 19,5 ºC Bulbo Húmedo.

El caudal de agua y la presión se basan en la temperatura 
del agua de entrada 7ºC.

SPECIFICATIONS DATASHEET

MODEL 

 

035 AK 

075 AK

Nominal Capacity

 

kW

 

3,68 

 

3,47 

6,38 

 

6,55 

Nominal Air Flow 

 

l/s

 

189 

378

Noise Level

 

dB(A) (L/H) 

30 / 38 

42 / 48

Power Supply

 

V / Ph / Hz

 

 

 

  220 - 240 / 1 / 50

Fan

 

Type

 

 

 

 

1 Air Inlet

 

Qty.

 

 

 

 

1

Fan Motor

 

W

 

67 

89

 

A

 

0,3 

0,45

 

Speed

 

3

Coil

 

Type

 

 

 

 

--- 

 

Drain Connection

 

mm (‘‘)

 

22,22 (7/8’’)

Air Filter

 

Material

 

Washable / Honey Bee / Sintetic

Water Flow Rate

 

l/h

 

  501 

 

1.097

Water Pressure Drop

 

m

 

  1,9 

 

1,94

Connections

 

In (mm / ’’)

 

 19,05 - 1/2” 

 

19,05 - 3/4”

 

Out (mm / ’’)

 

 19,05 - 1/2” 

 

19,05 - 3/4”

Case Dimension 

(mm)

 

Height

 

  213 

 

268

 

Width

 

  584 

 

866

 

Depth

 

  584 

 

866

Panel Dimension  

(mm)

 

Height

 

  23 

 

110 ()

 

Width

 

  700 

 

950

 

Depth

 

  700 

 

950

Carton Case

 

(HxWxD) (mm)

  

392 x 807 x 789 

       422 x 1.057 x 1.039

Carton Panel

 

(HxWxD) (mm) 

 

187 x 807 x 789 

    187 x 1.057 x 1.039

Case Weight

 

Kg

 

22,5 

40 

Panel Weight

 

Kg

 

 

 

12 

 

Width x Depth

Panel Dimensions

Case Dimensions

Width x Depth

Содержание 035 AK

Страница 1: ...g 4 Select location 4 Indoor unit location 5 Installation method 5 7 Drain pipework 7 Water connections 7 Electrical wiring 7 Interconnecting wiring 8 Mounting front panel assembly 8 9 Fresh air renew...

Страница 2: ...ioner please read the Important Safety Information Chapter first to avoid the air conditioner damage or any other accident caused by your mishandling 3 All pictures are only sketches If there is any d...

Страница 3: ...e 1 Air Inlet Qty 1 Fan Motor W 67 89 A 0 3 0 45 Speed 3 3 Coil Type Drain Connection mm 22 22 7 8 Air Filter Material Washable Honey Bee Sintetic Water Flow Rate l h 501 1 097 Water Pressure Drop m 1...

Страница 4: ...ammable gas or alkaline acid substances are present Aluminum copper coils and or internal plastic components can be damaged irreparably Do not install in workshops or kitchens oil vapors drawn in by t...

Страница 5: ...run to the outdoor unit From where condensate can be easily run to drain Check the distance between the upper slab and false ceiling to ensure the unit will suit the distance Fig 4 MODEL A mm 035 AK...

Страница 6: ...unit by the condensate drain discharge pipe or by the piping connections Incline unit and insert it into the false ceiling Insert the rods into the brackets slot With false ceilings minimum height se...

Страница 7: ...d slope On completion the drain line should be insulated WATER CONNECTIONS Water connections are fixed to the unit body to avoid breaks when pipes are connected to valve assemblies it is advisable to...

Страница 8: ...adiated at the infra red receiver on the unit Install the unit and components as far as practical at least five metres away from the electromagnetic wave source Install a noise filter if any harmful n...

Страница 9: ...lled for outside air intake and branch ducting See Fig 23 Cut and remove anti condensate insulating material Install your flanges and conduits to casing Conduits can be flexible polyester with spring...

Страница 10: ...121203 www saunier duval co uk Saunier Duvalreserves the right to introduce modifications without previous warning...