Saturn South SS9005 Скачать руководство пользователя страница 16

16 

 

ZigBee coordinators that properly implement safe state functionality will send regular ‘stop revert’ 
commands to all connected meters whenever they are communicating successfully with the ESCo, 
and will send regular ‘start revert’ commands during ESCo communications outages. 

 

Safe State Manual Override 

In normal operation, the state of the relay can be set remotely by the ESCo or manually using the 
front panel button on the device. When communications are interrupted – due either to a loss of 
ESCo communications from the ESBox, or a loss of ZigBee communications between the meter and 
the ESBox – the safe state mechanism can guarantee that the switch state will revert to a pre-
defined safe state. However, the designated safe state may not always be the state desired by the 
consumer, meaning that there must be a mechanism to manually override the switch state during 
times when the normal ESCo controls are not available. 

Safe State Manual Override enables consumers to manually set the switch state of their device 
during communications outages. When the switch state is manually set 

following the start of a safe 

state reversion countdown

, the switch will ignore safe state reversion triggers until manual override 

is disabled by receipt of a ‘stop revert’ message from the ZigBee coordinator. Since ‘stop revert’ 
messages will only be received by the device if the ZigBee network is working 

and

 the ESBox is able 

to communicate with the ESCo, the device will be under the control of the ESCo meaning that 
manual control can be cancelled. 

 

Safe State Reversion Reports

 

The safe state mechanism includes a 

report

 capability to enable the ESCo to determine if a switch 

state transition occurred autonomously.

 

If safe state reversion reporting is enabled, bit 1 of the 

Switch State attribute will be set to 1 if a reversion to safe state was the cause of the most recent 
switch state transition.

 

Safe state reporting example: The Switch Safe State attribute is set to 3, and the relay is currently 
OFF (Switch State = 0). The SS9005 loses contact with the ZigBee network, causing the switch state 
to revert to the selected safe state (ON). The Switch State attribute (attribute 0) will be set to 3, 
indicating that the switch is on (bit 0 ==1) and a reversion has occurred (bit 1 = 1). 

The reversion to safe state report bit in the Switch State attribute will be cleared the next time the 
switch state is changed, either remotely or using the front panel button on the SS9005. 

 

Effect of Factory Reset on Safe State Settings 

Performing a factory reset on the device will reset the ‘Switch Safe State’ attribute to 4 (disabled), 
and the ‘Switch Safe State Reversion Delay’ attribute to zero. 

 

 

Содержание SS9005

Страница 1: ...D501 2 4 29 Oct 2015 SS9005 Mini Three Phase Meter User Manual Version 1 3 Std HA Release build V003...

Страница 2: ...Specifications 6 5 Commissioning and Installation Instructions 7 5 1 Before Installation 7 5 2 Installation 7 5 3 Commissioning 11 6 Switching 12 7 Metering 13 8 Device Clusters and Attributes 14 8 1...

Страница 3: ...ent failure This product is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience or knowledge unless they have been given super...

Страница 4: ...join any ZigBee HA network with Permit Joining mode enabled When the button is pressed the button colour will change to yellow and then begin to rapidly blink green once is has been held long enough t...

Страница 5: ...005 an ideal choice for monitoring renewable generation sources and energy storage devices Three phase consumption is tracked independently to provide instantaneous three phase power and accurate thre...

Страница 6: ...Range 25 C to 80 C Relative Humidity 10 95 non condensing Average Power Consumption 2W Mass 0 103kg Dimensions 60 5 x 90 x 35 5mm Wire gauge 0 1mm2 min 2 5mm2 stranded or 2 5mm2 solid core max IP Rati...

Страница 7: ...ini Three Phase Meter is designed to be straightforward to install into a standard domestic or commercial switchboard The following steps should be followed to install the device 1 Identify the circui...

Страница 8: ...y an approved circuit breaker The maximum voltage permitted between the Neutral N terminal and any of the phase input terminals A B or C is 240VAC Exceeding this limit may cause permanent damage to th...

Страница 9: ...sources and voltages share the same phase Figure 1 Mini Three Phase Meter monitoring a Three Phase load Cable of minimum cross section 0 1mm2 and maximum cross section 1 5mm2 stranded or 2 5mm2 solid...

Страница 10: ...ay contactor or control system Refer to the relevant documentation when connecting this Mini Three Phase Meter to a third party control device See Section 6 Switching for more information 6 Apply powe...

Страница 11: ...before activating the first device using the Factory Reset LLLSS button sequence 2 Instruct the new Mini Three Phase Meter to join the network by pressing and holding the front panel button for 5 sec...

Страница 12: ...l IO on a control device such as a PLC The example below shows a SS9005 Mini Three Phase Meter being used to control an external contactor with a 240V coil by switching the active input to the contact...

Страница 13: ...ith the supplied CTs IMPORTANT Attaching a third party CT to the device can damage the device and will void the product warranty SS9005 Mini Three Phase Meter devices have a variant label on the front...

Страница 14: ...ver it may not be possible for a device to send 11 attributes in a single report If the total size of the report exceeds the maximum payload size 60 bytes some attributes will be excluded from the rep...

Страница 15: ...which can trigger a safe state reversion 1 Loss of ZigBee communications between the meter and the coordinator e g ESBox 2 Receipt of a start revert command from the ZigBee coordinator regularly sent...

Страница 16: ...ed by receipt of a stop revert message from the ZigBee coordinator Since stop revert messages will only be received by the device if the ZigBee network is working and the ESBox is able to communicate...

Страница 17: ...00 N 57664 e140 Accumulated Energy 1 Active Import Wh 1 N 57665 e141 Accumulated Energy 1 Reactive Import varh 1 N 57721 e179 Accumulated Energy 1 Active Export Wh 1 N 57722 e17a Accumulated Energy 1...

Страница 18: ...Current attribute cannot be configured for reporting All SS9005 phases are calibrated for the same CT type The Maximum Current attribute specifies the rating of the supplied current transformers The f...

Страница 19: ...ining mode Try to join the device again Saturn South metering devices will initially scan a reduced subset of the full range of available ZigBee channels If the network is on a channel that is not in...

Отзывы: