14 

 

8

 

Device Clusters and Attributes 

The following Clusters are supported in the Std HA release of the SS9005 Mini Three Phase Meter: 

 

Basic 

 

On/Off 

 

Simple Metering 

This section lists the available attributes in each supported cluster. 

A maximum of 11 attributes can be configured for reporting at once. There is only one timer for 
attribute reports, and attributes will be reported at the interval specified in the most recent report 
configuration message. Because ZigBee attributes have a variable size however, it may not be 
possible for a device to send 11 attributes in a single report. If the total size of the report exceeds 
the maximum payload size (60 bytes), some attributes will be excluded from the report. The device 
will not automatically follow up with the remaining attributes if this is the case, and any missing 
attributes must be requested separately. 

8.1

 

Basic Cluster 

Cluster ID: 0x0000 (0) 
Manufacturer ID: 0x0000 (0) 

Attr ID 

Attr ID 
(Hex) 

Attribute Name 

Writeable 

ZigBee Cluster Library Version 

Application Version 

Stack Version 

Hardware Version 

Manufacturer Name 

Model Identifier 

Date Code 

Power Source 

16 

10 

Location Description 

18 

12 

Device Enabled 

 

 

Содержание SS9005

Страница 1: ...D501 2 4 29 Oct 2015 SS9005 Mini Three Phase Meter User Manual Version 1 3 Std HA Release build V003...

Страница 2: ...Specifications 6 5 Commissioning and Installation Instructions 7 5 1 Before Installation 7 5 2 Installation 7 5 3 Commissioning 11 6 Switching 12 7 Metering 13 8 Device Clusters and Attributes 14 8 1...

Страница 3: ...ent failure This product is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience or knowledge unless they have been given super...

Страница 4: ...join any ZigBee HA network with Permit Joining mode enabled When the button is pressed the button colour will change to yellow and then begin to rapidly blink green once is has been held long enough t...

Страница 5: ...005 an ideal choice for monitoring renewable generation sources and energy storage devices Three phase consumption is tracked independently to provide instantaneous three phase power and accurate thre...

Страница 6: ...Range 25 C to 80 C Relative Humidity 10 95 non condensing Average Power Consumption 2W Mass 0 103kg Dimensions 60 5 x 90 x 35 5mm Wire gauge 0 1mm2 min 2 5mm2 stranded or 2 5mm2 solid core max IP Rati...

Страница 7: ...ini Three Phase Meter is designed to be straightforward to install into a standard domestic or commercial switchboard The following steps should be followed to install the device 1 Identify the circui...

Страница 8: ...y an approved circuit breaker The maximum voltage permitted between the Neutral N terminal and any of the phase input terminals A B or C is 240VAC Exceeding this limit may cause permanent damage to th...

Страница 9: ...sources and voltages share the same phase Figure 1 Mini Three Phase Meter monitoring a Three Phase load Cable of minimum cross section 0 1mm2 and maximum cross section 1 5mm2 stranded or 2 5mm2 solid...

Страница 10: ...ay contactor or control system Refer to the relevant documentation when connecting this Mini Three Phase Meter to a third party control device See Section 6 Switching for more information 6 Apply powe...

Страница 11: ...before activating the first device using the Factory Reset LLLSS button sequence 2 Instruct the new Mini Three Phase Meter to join the network by pressing and holding the front panel button for 5 sec...

Страница 12: ...l IO on a control device such as a PLC The example below shows a SS9005 Mini Three Phase Meter being used to control an external contactor with a 240V coil by switching the active input to the contact...

Страница 13: ...ith the supplied CTs IMPORTANT Attaching a third party CT to the device can damage the device and will void the product warranty SS9005 Mini Three Phase Meter devices have a variant label on the front...

Страница 14: ...ver it may not be possible for a device to send 11 attributes in a single report If the total size of the report exceeds the maximum payload size 60 bytes some attributes will be excluded from the rep...

Страница 15: ...which can trigger a safe state reversion 1 Loss of ZigBee communications between the meter and the coordinator e g ESBox 2 Receipt of a start revert command from the ZigBee coordinator regularly sent...

Страница 16: ...ed by receipt of a stop revert message from the ZigBee coordinator Since stop revert messages will only be received by the device if the ZigBee network is working and the ESBox is able to communicate...

Страница 17: ...00 N 57664 e140 Accumulated Energy 1 Active Import Wh 1 N 57665 e141 Accumulated Energy 1 Reactive Import varh 1 N 57721 e179 Accumulated Energy 1 Active Export Wh 1 N 57722 e17a Accumulated Energy 1...

Страница 18: ...Current attribute cannot be configured for reporting All SS9005 phases are calibrated for the same CT type The Maximum Current attribute specifies the rating of the supplied current transformers The f...

Страница 19: ...ining mode Try to join the device again Saturn South metering devices will initially scan a reduced subset of the full range of available ZigBee channels If the network is on a channel that is not in...

Отзывы: