background image

SATEL 

VERSA Plus LTE 

31 

device list, the same name will be given to the other zones. If the device is to be 
assigned to outputs, the outputs will be given the same name. 

6.3.  In the “Zone” field, select the number of the zone to which you want to assign the 

device (if you have not done this before or if you want to change the previously 
selected number). 

6.4.  For some devices you can select if the device is to occupy one or two positions on 

the list of devices. 

7.  Click on the “OK” button (you can click on the “Quit” button to cancel adding a new device 

or on the “Next” button to proceed to adding a next wireless device). The “New wireless 
dev.” window will close. 

8.  Click on the “Write”  button  to write the new wireless device data to the controller (these 

data will not be written after clicking on the 

 button in the main menu). 

LCD keypad 

You can add ABAX 2 / ABAX wireless devices  in the service mode by means of the N

EW 

DEVICE

  function (S

ERVICE MODE

 

2. H

ARDWARE

 

1. K

PDS

.

 

&

  EXPS

3. W

IRELESS  DEV

1. N

EW DEVICE

). 

1.  Start the N

EW DEVICE

 function. 

2.  When the “Serial number” is displayed, enter the serial number of the device being added. 

3.  Press 

4.  When the “Open device tamper” command is displayed, power on the device (insert the 

battery into the device, turn on the device power, etc.). 

5.  Type and serial number of the device will be displayed (if nothing happens, you might 

have entered a wrong serial number – press 

 to quit the function).  

6.  Depending on the device: 

–  if the device takes up only 1 zone or you cannot select how many positions the device 

is to occupy on the device list – press 

–  if you can select whether the device will take up one or two positions (channels) on the 

list of devices, a special message will inform you about it – press 

 (the device will 

occupy 1 position) or 

 (the device will occupy 2 positions). 

7.  Use the 

 and 

 keys to select the zone to which you want to assign the device. 

8.  Press 

9.  The new name of the zone / output to which the device has been assigned will be 

displayed. You can change that name. 

10. Press 

11. If the device occupies two or more zones / outputs, the name giving procedure is 

repeated for them. 

12. In the next steps, you can configure the device settings (see the P

ROGRAMMING

 manual). 

5.17.2  Removing ABAX 2 / ABAX wireless devices 

DLOADX program 

You can remove ABAX 2 / ABAX wireless devices in the “VERSA  –  Structure” window, 
“Hardware” tab, after clicking on the ABAX 2 / ABAX controller name in the list of devices. 

1.  In the “Zones/Outputs” tab, click on the “Read” button to read the data related to wireless 

devices from the controller. 

Содержание VERSA Plus LTE

Страница 1: ...INSTALLER MANUAL EN versa_plus_lte_i_en 09 21 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu Alarm Control Panel VERSA Plus LTE Firmware Version 1 10...

Страница 2: ...under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and software Current information about the changes being...

Страница 3: ...Connecting the INT AVT terminal 23 5 11 1 Mounting the INT AVT terminal 23 5 12 Connecting the power supply and starting the control panel 25 5 12 1 Main power supply 25 5 12 2 Backup power supply 25...

Страница 4: ...4 6 1 1 Hardwired zones 34 6 1 2 Wireless zones 34 6 2 Numeration of outputs 35 6 2 1 Hardwired outputs 35 6 2 2 Wireless outputs 35 7 Specifications 35 7 1 Control panel 35 7 2 VERSA LCD keypad 36 7...

Страница 5: ...e EOL configuration Electrical protection of the zones Maximum number of programmable zones 30 20 zone types NC type tamper input on the control panel mainboard Outputs 5 programmable hardwired output...

Страница 6: ...e numbers using SMS messages with automatically generated content Informing users of the VERSA CONTROL application about events using push notifications Built in voice module Nearly 13 minutes for mes...

Страница 7: ...control panel USB port configuring the built in voice module Remote programming using a computer with DLOADX program installed via PSTN telephone network modem cellular network modem LTE HSPA EDGE GPR...

Страница 8: ...able with different color options for display and backlight of keys The color variant is indicated by the additional designation in the keypad name e g VERSA LCD GR green display and keys backlight VE...

Страница 9: ...NT CR INT IT 2 INT IT Proximity card arm disarm device Enables arming disarming and alarm clearing in partitions by means of proximity cards proximity tags and other passive transponders 5 System inst...

Страница 10: ...es are greater several wires connected in parallel may have to be used for each signal in order to reduce conductor resistance This however may lead in consequence to an increase in conductor capacita...

Страница 11: ...controller DIALER LED Indicates the status of control panel telephone communicator pins for emergency starting the control panel see Emergency procedure of the control panel start up p 26 USB MINI B...

Страница 12: ...put output 5 OUT1 OUT2 programmable high current outputs 12 VDC voltage is always present at the terminal The terminal is either shorted to or disconnected from the common ground depending on the outp...

Страница 13: ...Grade 2 the VERSA LCD VERSA LED keypads must have the firmware version 1 01 or newer at least one LCD keypad must be connected to the control panel This will allow the users to be informed about the...

Страница 14: ...X S expansion module is connected to the control panel installation of the VERSA MCU controller in the system is impossible Fig 4 Connecting the INT RX S expander to the control panel Fig 5 Setting ad...

Страница 15: ...ol panel can support up to 30 wireless zones and 12 wireless outputs If the wireless zone number coincides with that of the wired zone on mainboard or in expander the wireless zone is supported If the...

Страница 16: ...el Fig 9 Setting the DIP switches in the ABAX 2 ABAX controllers 5 5 5 Connecting the hardwired zone expanders Up to three INT E CA 64 E CA 64 EPS expanders can be connected to the control panel This...

Страница 17: ...identification please refer to the manual delivered with the expander Fig 10 Connecting the INT E expander to the control panel Fig 11 Setting the DIP switches in expanders to be identified as CA 64...

Страница 18: ...o be identified for detailed information please refer to the manual delivered with the expander The INT O expander is identified as CA 64 O the dedicated power supply not connected to the expander or...

Страница 19: ...es with the NO normally open alarm output Closing the circuit will trigger an alarm EOL this wiring type may be used to connect devices having the NC or NO alarm output Closing or opening the circuit...

Страница 20: ...ATEL Fig 16 The ways to connect detectors to zones The detector outputs are designated with letters A alarm T tamper R R1 R2 VERSA Plus LTE Fig 17 Example of connecting an NC detector NO detector conn...

Страница 21: ...SATEL VERSA Plus LTE 19 VERSA Plus LTE Fig 18 Example of connecting an NC detector in Single EOL configuration VERSA Plus LTE Fig 19 Example of connecting an NO detector in Single EOL configuration...

Страница 22: ...ual If the resistor value in the expander is not programmable in Single EOL configuration the 2 2 k resistor is required and in Double EOL 2EOL configuration two 1 1 k resistors 5 7 Connecting the sir...

Страница 23: ...ting to the VERSA Plus LTE control panel Contact number Description Connection method 2 alternating voltage check connect to control panel AC terminal 12 power supply connect directly to battery throu...

Страница 24: ...ls marked T 1 R 1 Hence the telephone line should be connected to the control panel using a four wire cable When connected in this manner the control panel will be able to completely capture the line...

Страница 25: ...to the terminal the system users will be able after establishing telephone connection with the control panel to use the listen in feature and talk with the people staying inside the protected premises...

Страница 26: ...for wall plugs screw anchors 5 Run wires through the opening in the enclosure base 6 Using wall plugs screw anchors and screws fasten the enclosure base to the wall 7 Connect the INT AVT terminals to...

Страница 27: ...f the battery voltage drops below 11 V for longer than 12 minutes 3 battery tests the control panel will indicate battery failure When the voltage goes down to approx 10 5 V the battery will be discon...

Страница 28: ...t LCD the and of the second partition LEDs will be lit and the message Restore factory settings 1 Yes will come up on the display LED the and of the second partition LEDs will be lit and the LED will...

Страница 29: ...he keypad in which a new address is to be set press the key number corresponding to the new address The address change will be confirmed by four short beeps followed by a long one 5 Press the key to f...

Страница 30: ...art Three short beeps will indicate that identification has been completed and information on the identified devices will be presented on the display in the LCD keypad and by means of LEDs in the LED...

Страница 31: ...ler is connected to the control panel you can proceed to installation of ABAX 2 ABAX wireless devices after control panel start up and controller identification by the control panel Before installing...

Страница 32: ...o which no wireless device is still assigned If the device takes up more than one position on the list of devices additional zones will be assigned to the device automatically these will be zones imme...

Страница 33: ...displayed power on the device insert the battery into the device turn on the device power etc 5 Type and serial number of the device will be displayed if nothing happens you might have entered a wron...

Страница 34: ...ce can reach the controller To send a transmission you can e g open the detector tamper switch If transmissions from the detector planned installation place do not reach the controller select another...

Страница 35: ...adding a new detector or on the Next button to proceed to adding a next wireless detector The New wireless dev window will close 8 Click on the Write button to write the new wireless detector data to...

Страница 36: ...ove is assigned 3 Press 4 When a prompt will be displayed asking you whether to remove the detector type and serial number of the detector will be displayed press 6 Numeration of zones and outputs in...

Страница 37: ...ns 7 1 Control panel Supply voltage 18 VAC 15 50 60 Hz Recommended transformer 40 VA Standby current consumption 150 mA Maximum current consumption 300 mA Standby current consumption from battery 130...

Страница 38: ...class according to EN50130 5 II Operating temperature range 10 55 C Maximum humidity 93 3 Enclosure dimensions 114 5 x 95 x 22 5 mm Weight 123 g 7 3 VERSA LCDM keypad Supply voltage 12 VDC 15 Standby...

Страница 39: ...current consumption VERSA LED GR 110 mA VERSA LED BL 120 mA Environmental class according to EN50130 5 II Operating temperature range 10 55 C Maximum humidity 93 3 Enclosure dimensions 114 5 x 95 x 2...

Страница 40: ......

Отзывы: