7. Outputs
The system supports the following outputs:
hardwired
– on the control panel PCB and in the expander.
wireless
– in the PERFECTA-T 32-WRL control panel. There are 4 outputs that support
wireless sirens.
7.1 Output functions
0. N
OT USED
1. E
XTERNAL SIREN
– output activated by triggering burglary, panic or fire alarm. In the event
of the fire alarm, the output is pulsating.
2. I
NTERNAL SIREN
– output activated by triggering burglary, panic, fire or warning alarm. In the
event of the fire alarm, the output is pulsating.
3. B
URGLARY
– output activated after alarm is triggered by the 0. E
NTRY
/E
XIT
, 1. E
NTRY
/E
XIT
FINAL
, 2. I
NTERNAL
, 3. I
NSTANT
, 4. D
OUBLE KNOCK
or 5. 24
H
B
URGLARY
zone.
4. F
IRE ALARM
– output activated by triggering fire alarm from keypad or by the 10. 24
H
F
IRE
zone.
5. DURESS
ALARM
– output activated by using a code with D
URESS
right.
6. P
ANIC ALARM
– output activated by triggering panic alarm from keypad (loud or silent), by
the 7. 24
H
P
ANIC
or 8. 24
H
P
ANIC SILENT
zone.
7. MEDICAL
ALARM
– output activated by calling medical help from keypad or by the 9. 24
M
EDICAL
zone.
8. A
LARM
–
NOT VERIFIED
– output activated by triggering unverified alarm.
9. A
LARM
-
VERIFIED
– output activated by triggering verified alarm.
10. T
AMPER ALARM
– output activated by triggering tamper alarm.
11. F
IRE DETECTORS POWER SUPPLY
– output for power supply of fire detectors with automatic
alarm verification. The output is deactivated for 16 seconds after violation of the 10. 24
H
F
IRE
zone. If, after reactivation of the output, the zone will be violated again, fire alarm will
be triggered.
12. P
OWER SUPPLY ON ARMED
– output for power supply of the detectors which should not
operate when the system is disarmed. The output is active when the system is armed (it
will be activated as soon as the exit delay countdown starts).
13. Z
ONE VIOLATION
– output activated by zone violation.
14. C
HIME
– output activated by zone violation, if the zone is disarmed.
15. C
ONTROLLED
– output activated / deactivated by using zones, timers, keypad etc.
16. READY
STATUS
– output is active, when the system is ready for arming (no zone is
violated).
17. E
XIT DELAY STATUS
– output is active, when E
XIT DELAY
countdown is running.
18. A
RMED STATUS
– output is active, when the system is armed.
19. T
ROUBLE STATUS
– output is active, when there is a trouble in the system.
20. A
RM
/
ALARM STATUS
– output is active, when the system is armed (continuous mode) or
when there is alarm (pulsating mode).
21. D
ETECTORS RESET
– output is used to reset the alarm memory in detectors. It is activated
on:
– starting the exit delay countdown (if the exit delay is 0 – on arming),
– starting the 3.O
UTPUTS RESET
user function.