3.  Remove the discharged battery. 
4.  Install a new CR123A 3 V lithium battery. 
5.  Close the detector enclosure. 
6.  Press and hold down the test/reset button (designated with the letter A in Figure 2). Alarm should be 

triggered. 

6.  Specifications 

Operating frequency band ...................................................................................................... 433.05 ÷ 434.79 MHz 
Radio communication range (in open area) ...........................................................................................up to 200 m 
Battery....................................................................................................................................................CR123A 3 V 
Battery life expectancy..........................................................................................................................up to 3 years 
Standby current consumption .......................................................................................................................... 85 µA 
Maximum current consumption..................................................................................................................... 120 mA 
Operating temperature range .................................................................................................................. 0°C...55°C 
Dimensions .........................................................................................................................................ø108 x 54 mm 
Weight...............................................................................................................................................................170 g

 

 
The MSD-350 wireless smoke detector conforms to the essential requirements of the EU Regulations and 
Directives: 

CPR

 305/2011 Regulation of the European Parliament and of the Council of 9 March 2011 laying down 

harmonized conditions for the marketing of construction products and repealing the Council Directive 
89/106/EEC on construction products; 

EMC

 2014/30/EU Electromagnetic Compatibility Directive; 

RED

 Directive 2014/53/EU of the European Parliament and of the Council of 16 April 2014 on the harmonization 

of the laws of the Member States relating to the making available on the market of radio equipment and 
repealing Directive 1999/5/WE. 
The CNBOP-PIB Certification Body in Józefów issued the Certificate of Constancy of Performance 1438-CPR-
0623 for the construction product MSD-350 Wireless Smoke Detector, confirming its compliance with the 
requirements of EN 14604:2006. 
The CNBOP-PIB Certification Body in Józefów has tested the MSD-350 Wireless Smoke Detector confirming its 
compliance with the EN 14604 Standard, within the scope of Appendix L (approved for the use in caravans and 
camper vans). 
The Certificate and the Declaration of Performance can be downloaded from the 

www.satel.eu

. website 

 
 
 

 

18

 

SATEL Sp. z o.o. • ul. Budowlanych 66 • 80-298 Gda

ń

sk • POLAND 

1438 

1438-CPR-0623 

MSD-350 

EN 14604 

Fire safety. MSD-350 Wireless Smoke Detector, stand-alone, capable of interacting over the air with the 

intruder alarm system, based on scattered light principle, designed for indoor use. 

Declaration of Performance 1438-CPR-0623 

Application – fire safety. 
Technical specifications – please refer to this manual. 

 
 
 

SATEL sp. z o.o. • ul. Budowlanych 66 • 80-298 Gda

ń

sk • POLAND 

tel. +48 58 320 94 00 

www.satel.eu 

 

Содержание MSD-350

Страница 1: ...ed Fire alarm signaling The alarm is indicated visually LED steady light and acoustically intermittent sound for 5 minutes Pressing the test reset button designated with the letter A in Figure 2 during the alarm will clear the alarm condition and will block the smoke detection function in the detector for 5 minutes Operating modes You can set the operating mode using the jumper Fig 4 jumper remove...

Страница 2: ...ll plugs delivered with the detector are intended for brick concrete and similar mounting surfaces For other surfaces e g drywall wood styrofoam use other wall plugs as required 9 Replace the detector cover and lock it with the screw 10 Press and hold down the test reset button designated with the letter A in Figure 2 Alarm should be triggered 11 If in the premises where the detector is installed ...

Страница 3: ...ed 5 Battery replacement The used batteries must not be discarded but should be disposed of in accordance with the existing rules for environment protection When the battery needs to be replaced the battery voltage drops below 2 75 V the detector informs you about it by means of LED and sounds 3 short flashes of the LED and 3 short beeps every 30 seconds 1 Remove the screw fastening the cover Fig ...

Страница 4: ...ncil of 16 April 2014 on the harmonization of the laws of the Member States relating to the making available on the market of radio equipment and repealing Directive 1999 5 WE The CNBOP PIB Certification Body in Józefów issued the Certificate of Constancy of Performance 1438 CPR 0623 for the construction product MSD 350 Wireless Smoke Detector confirming its compliance with the requirements of EN ...

Отзывы: