Satel KNX-BSA12H Скачать руководство пользователя страница 27

SATEL 

KNX-BSA12L 

• KNX-BSA12H 

25 

Scene 1…8: initial value

 

– you can select how the initial value will be set for scenes after 

starting/restarting the module. 

The parameter is available, if the “yes” option is selected for 

the “Learning scenes from bus” parameter. 

default

 

–  value  defined  in  the  program. If the  object  receives  a  telegram  with  the  scene 

numbe

r (“Scene 1...8: number” field), the blind and slats (if the blind has slats) are set to 

the  positions  corresponding  to  the  values  defined  for  the  scene  with  this  number  in 
fields “Scene 1...8: position” and “Scene 1...8: position of slats”. 

last set from bus

 

– the value learned via the last telegram from the bus. If the value of the 

“Scene” object has not been changed by the learning function, the default value will be 
set. 

Weather alarms 

You  can  define  reaction  of  the  blind/shutter  to  a  change  of  state  of  the  safety-related 
communication  objects  “Wind  alarm”,  “Rain  alarm”  and  “Frost  alarm”.  For  each  the  object, 
you can define a different reaction (no reaction / fully opened / fully closed / stop). Regardless 
of the selected blind/shutter type, reaction to weather alarms is defined in the same way. 

Description of parameters 

 

Alarm  priority

 

–  you  can  define  priorities  of  each  alarm,  i.e.  their  hierarchy  (where:  1 – 

highest priority, 3 

– lowest priority): 

1: Frost; 2: Rain; 3: Wind 

1: Frost; 2: Wind; 3: Rain 

1: Rain; 2: Frost; 3: Wind 

1: Rain; 2: Wind; 3: Frost 

1: Wind; 2: Frost; 3: Rain 

1: Wind; 2: Rain; 3: Frost 

A weather alarm with higher priority can change the blind/shutter position set previously in 
response  to  a  lower  priority  alarm.  On the  other  hand,  weather  alarms  with  lower  priority 
trigger  no  reaction  in  the  channel  as  long  as  the  channel  is  locked  by  a  higher  priority 
alarm. 
Example for the “1: Frost; 2: Rain; 3: Wind” variant. If the blind/shutter is set in response to 
the “Wind” alarm, and then the “Frost” alarm is triggered, the blind/shutter position will be 
changed  to  a  position  defined  as  response  to  the  “Frost”  alarm.  However,  if  the 
blind/shutter 

position is set in response to the “Frost” alarm, the “Wind” and “Rain” alarms 

will not change the blind/shutter 

position until the “Frost” alarm is called off. 

If you select this variant, the fields for defining the channel reaction to each weather alarm 
will arrange in the order corresponding to their priorities. 

The blind/shutter position set in response to the weather alarm can be overridden by 
the position forcing function, which has the highest priority. 

Reaction  on  frost  alarm

 

–  position  to  which  the  blind/shutter  will  be  set  in  response  to 

change of state of the “Frost alarm" communication  object (no reaction / fully opened / 

fully closed / stop). 

Содержание KNX-BSA12H

Страница 1: ...KNX BSA12L 24 VDC KNX BSA12H 230 VAC Blind shutter Actuator Firmware version 1 02 knx bsa_en 09 20 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu...

Страница 2: ...ized by the manufacturer shall void your rights under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and softw...

Страница 3: ...guring global parameters 7 4 2 1 Weather alarms 8 4 3 Configuring channels 9 4 3 1 Blind shutter operating parameters 10 Motor 17 Shutter awning window 18 Venetian blind 18 4 3 2 Functions 20 Scene 1...

Страница 4: ...s are configured in the ETS program in the same way for both modules except for defining operation of the vertical blinds as only the KNX BSA12L module supports this blinds 1 Features Communication wi...

Страница 5: ...ror is automatically cleared when the blind shutter reaches the end position in the opposite direction to that in which it was moving when the channel reported an error Continuous operation for too lo...

Страница 6: ...nsions based on the KNX BSA12L module The module takes up 4 units on the DIN rail 35 mm 2 2 Operating the module manually Manual operation allows you to control the movement of blinds shutters using t...

Страница 7: ...12H reverse the wires controlling the direction of motor rotation Check the current consumption by the blind shutter motor if it is lower than the minimum current detected by the module the blind shut...

Страница 8: ...eu ets must be imported into the program For detailed information on how to configure the module refer to section Configuring the module 3 1 Wiring diagram 4 Configuring the module Working parameters...

Страница 9: ...ition control function will not be able to change the blind shutter position until the alarm is called off 4 2 Configuring global parameters The main working parameters of the module are defined in th...

Страница 10: ...enetian blind vertical blind awning window Selecting the type of blind shutter will enable the communication objects to control its movement and display the Channel B tab The Vertical blind type of bl...

Страница 11: ...me of the Frost alarm object 0 65535 seconds With the monitoring disabled field value 0 the alarm will only be triggered by receiving the Alarm telegram As good practice indicates monitoring time of t...

Страница 12: ...lind shutter travel time may be detected by the module automatically recommended or can be determined based on a measurement taken The travel time is the time during which the blind shutter can be mov...

Страница 13: ...o the upper end position It is advisable to automatically detect the time of movement by the module for all blinds shutters that make it possible Slat adjustment time This parameter applies to the sla...

Страница 14: ...he slat position and adjustment time for a vertical blind only for the KNX BSA12L module Description of parameters Depending on the type of blind shutter selected for the channel A different parameter...

Страница 15: ...select the manual detection fields that allow you to enter the measured values will be displayed in the tab see Shutter awning window and Venetian blind If you select manual detection for a blind shu...

Страница 16: ...position at which the blind shutter can stop see Fig 10 0 100 default 10 If after stopping the distance between the blind shutter and the target position is greater the channel will report an error in...

Страница 17: ...bstacle detection by smart motor Value 0 disables the cyclic telegram sending Interval of cyclic position sending frequency of sending a telegram with information about current blind shutter position...

Страница 18: ...Move up down central communication object Changing the object value will trigger a channel response as a result of which the blind shutter will be moved up or down according to the value saved in the...

Страница 19: ...the channel Disable Enable If you select Enable the Weather alarms tab will be displayed The parameter is available when the weather alarm functions are enabled in the module Weather alarms parameter...

Страница 20: ...be taken Travel time up shutter travel time from the lower to the upper end position see Fig 4 6 and 7 0 480000 milliseconds The field is available if the yes option is selected for the Travel time in...

Страница 21: ...option is selected for the Travel time in two directions parameter Travel time down time of travel of Venetian blind from the upper to the lower end position see Fig 4 0 480000 milliseconds The field...

Страница 22: ...to control the position of blinds by defining the correct percentage values of opening for the first and second scenes from the pair percentage value of opening before calling scenes channel A 0 chann...

Страница 23: ...with value 0 from the Call scene 1 bit 1 2 communication object 0 100 0 upper end shutter position 100 lower end shutter position see Fig 4 6 and 7 Scene 2 delay time that must elapse from receiving t...

Страница 24: ...ind position 100 lower end blind position see Fig 4 and 5 Scene 1 position of slats position to which the slats will be set in response to the telegram with value 0 from the Call scene 1 bit 1 2 commu...

Страница 25: ...from the bus If the object value has not been changed by the learning function the default value will be set Initial values for the other scenes are defined in the same way as for the 1 2 pair Scene...

Страница 26: ...g scenes from bus parameter default value defined in the program If the object receives a telegram with the scene number Scene 1 8 number field the shutter is set to position corresponding to the valu...

Страница 27: ...larm i e their hierarchy where 1 highest priority 3 lowest priority 1 Frost 2 Rain 3 Wind 1 Frost 2 Wind 3 Rain 1 Rain 2 Frost 3 Wind 1 Rain 2 Wind 3 Frost 1 Wind 2 Frost 3 Rain 1 Wind 2 Rain 3 Frost...

Страница 28: ...he object assumes the value 1 the blind shutter will be set to the position defined and the channel will be locked Unlocking of the channel is only possible when the object assumes the value 0 When un...

Страница 29: ...ountdown will be started again reset The blind shutter position set by using this object can only be changed as a result of a higher priority alarm see Weather alarms or by the position forcing functi...

Страница 30: ...absolute position slats percentage 1 byte DPT 5 001 C W The object will be enabled if you select Enable for the Central absolute position parameter in the tab for configuring the settings of the chann...

Страница 31: ...in the Interval of cyclic device error alarm sending field in the Global tab Telegram 1 error in one of the channels 0 module is working correctly Flag C communication R read W write T transmit U upda...

Страница 32: ...a 1 bit object 0 step up by the value defined in the Step value field 1 step down by the value defined in the Step value field when the blind shutter or slats are moving 0 STOP 1 STOP 19 Channel A De...

Страница 33: ...shutter in the Channel A field Global tab It enables sending a telegram with information about the current position of the blind shutter The telegram is always sent after the travel is completed The p...

Страница 34: ...etian blind Telegram 1 error in the channel 0 channel is workin correctlly Flag C communication R read W write T transmit U update Functions Channel communication objects No Object name Object functio...

Страница 35: ...ject with number X Y enables the current blind shutter position percentage value of opening to be assigned to the 1 bit scene with number X and Y Telegram 0 current blind shutter position will be assi...

Страница 36: ...L 24 VDC KNX BSA 12H 230 VAC In rated current KNX BSA 12L 6 A KNX BSA 12H 6 A Connections Maximum wire cross section 2 5 mm2 Maximum tightening torque 0 5 Nm KNX parameters Maximum time of reaction to...

Отзывы: