6. If the partition keypad is to control an electric strike, electromagnetic lock or another door
actuator, connect this device to the NO terminals as shown in Fig. 2. It is not
recommended that the door actuator be powered from the same source as the partition
keypad.
7. If the keypad is to supervise the door status, connect the detector supervising the door
status to the IN and COM terminals. If the keypad is not to supervise the door status,
connect the IN terminal to the COM terminal or, when configuring the keypad, set value 0
for the “Max. door open time” parameter.
8. Connect the power wires to the 12V and COM terminals. The keypad may be powered
directly from the control panel, from an expander with power supply or from a power
supply.
9. Close the enclosure and then lock it with the screw.
10. Power on the alarm system.
11. Start the identification function in the control panel (see the control panel installer
manual). The keypad will be identified as "INT-S/SK".
Address setting
To set the address, use the DIP switches on the electronics board. The switches have
numbers assigned to them. The number for OFF position is 0. The numbers assigned to the
switches in ON position are presented in the table below. The sum of these numbers is the
address set.
Switch (ON position)
1
2
3
4
5
Number
1
2
4
8
16