background image

SATEL 

DMP-100 

● DRP-100 ● DCP-100 

The  DCP-100  heat  detector  conforms  to  the  essential  requirements  of  the  EU  Regulations  and 
Directives: 

CPR

  305/2011  Regulation  of  the  European  Parliament  and  of  the  Council  of  9  March  2011  laying 

down  harmonized  conditions  for  the  marketing  of  construction  products  and  repealing  the  Council 
Directive 89/106/EEC on construction products; 

EMC

 2014/30/UE Electromagnetic Compatibility Directive; 

LVD

 2014/35/EU Low Voltage Directive. 

The  CNBOP-

PIB  Certification  Body  in  Józefów  issued  the  Certificate  of  Constancy  of  Performance 

1438-CPR-0316  for  the  construction  product  DCP-100  detector,  confirming  its  compliance  with  the 
requirements of EN 54-5:2017+A1:2018. 

The  Certificate  and  the  Declaration  of  Constancy  of  Performance  can  be  downloaded  from  the 

www.satel.pl

 website. 

 

 

13 

SATEL Sp. z o.o. • ul. Budowlanych 66 • 80-298 Gdańsk • POLAND 

1438 

1438-CPR-0316 

Declaration of Performance DOP/CPR/0316 

EN 54-5:2017+A1:2018 

Fire safety in construction works. 

DCP-100 conventional, detachable, spot type heat detector 

for fire alarm systems used in buildings. 

Declaration of Performance DOP/CPR/0316. 

Use 

– fire safety 

Technical specifications 

– please refer to this manual. 

 

The  DRP-100  smoke  detector  conforms  to  the  essential  requirements  of  the  EU  Regulations  and 
Directives: 

CPR

  305/2011  Regulation  of  the  European  Parliament  and  of  the  Council  of  9  March  2011  laying 

down  harmonized  conditions  for  the  marketing  of  construction  products  and  repealing  the  Council 
Directive 89/106/EEC on construction products; 

EMC

 2014/30/UE Electromagnetic Compatibility Directive; 

LVD

 2014/35/EU Low Voltage Directive. 

The  CNBOP-

PIB  Certification  Body  in  Józefów  issued  the  Certificate  of  Constancy  of  Performance 

1438-CPR-0340  for  the  construction  product  DRP-100  detector,  confirming  its  compliance  with  the 
requirements of EN 54-7:2018. 

The  Certificate  and  the  Declaration  of  Constancy  of  Performance  can  be  downloaded  from  the 

www.satel.pl

 website. 

Содержание CSP DMP-100

Страница 1: ...are version 2 00 Optical smoke detector DRP 100 Firmware version 2 00 Fixed temperature rate of rise heat detector DCP 100 Firmware version 2 00 dmp 100_en 11 22 SATEL sp z o o ul Budowlanych 66 80 298 Gdańsk POLAND tel 48 58 320 94 00 www satel pl EN ...

Страница 2: ...l in order to avoid mistakes that can lead to malfunction or even damage to the equipment Disconnect power before making any electrical connections Changes modifications or repairs not authorized by the manufacturer shall void your rights under the warranty The following symbols may be used in this manual note caution ...

Страница 3: ...Detection of optical chamber fouling DMP 100 and DRP 100 Red LED indicator Installation in DB 100 base Optional connection of remote alarm indicator 3 Functional description 3 1 Smoke detection DMP 100 and DRP 100 An optical method is used for the detection of visible smoke When the concentration of smoke in the optical chamber exceeds a given threshold an alarm is triggered The detector automatic...

Страница 4: ... cookers The detector is designed for installation in the DB 100 base to which cables are connected Having installed the detector into its base protect it temporarily with the plastic dust cover included in the detector delivery set if any work which might cause fouling of the detector is being carried out in the building It is advisable to keep the dust cover in case repair work is conducted in t...

Страница 5: ...ver Fig 10 6 Using a soft brush or compressed air clean the labyrinth in the cover as well as the base of the optical chamber paying attention to the recesses where LEDs are installed 7 Replace the optical chamber cover 8 Replace the plastic element with the thermistor on the optical chamber 9 Secure the electronics module with the optical chamber in the cover and turn it clockwise 10 Insert the d...

Страница 6: ... current DMP 100 23 mA DRP 100 23 mA DCP 100 23 mA Class according to EN 54 5 heat sensor A1R Minimum static response temperature 54 C Maximum static response temperature 65 C Operating temperature range 25 50 C Maximum humidity 93 3 Enclosure dimensions DMP 100 DCP 100 ø108 x 49 mm DRP 100 ø108 x 42 mm Weight DMP 100 94 g DRP 100 94 g DCP 100 94 g ...

Страница 7: ...PR 0316 Declaration of Performance DOP CPR 0316 EN 54 5 2017 A1 2018 Fire safety in construction works DCP 100 conventional detachable spot type heat detector for fire alarm systems used in buildings Declaration of Performance DOP CPR 0316 Use fire safety Technical specifications please refer to this manual The DRP 100 smoke detector conforms to the essential requirements of the EU Regulations and...

Страница 8: ...6 EEC on construction products EMC 2014 30 UE Electromagnetic Compatibility Directive LVD 2014 35 EU Low Voltage Directive The CNBOP PIB Certification Body in Józefów issued the Certificate of Constancy of Performance 1438 CPR 0341 for the construction product DMP 100 detector confirming its compliance with the requirements of EN 54 7 2018 and EN 54 5 2017 A1 2018 The Certificate and the Declarati...

Отзывы: