SATEL AXD-200 

Simultaneous operation of the detector by the ABAX 2 and ABAX controller / 
INTEGRA 128-WRL alarm control panel is not possible. 

4.  Close the detector enclosure. 
5.  Put the detector at the place of its future installation. 
6.  Check the level of signal received from the detector by the ABAX 2 / ABAX controller or 

the INTEGRA 128-WRL control panel. If the signal level is lower than 40%, select another 
place for installation. Sometimes, it is sufficient to shift the device ten or twenty 
centimeters to obtain a considerable improvement in the signal quality. You can also try to 
turn the enclosure to check what effect the change of antenna position will have on the 
signal strength. 

The ARF-200 tester makes it possible to check the radio signal strength at the place of 
future installation without having to put the detector there. 

For the shock detector (AVD-200), check also the detector range in the selected 
location of installation. 

7.  Open the detector enclosure (Fig. 3). 
8.  If detectors or flood probe are to be connected to the additional input terminals, make 

a hole in the enclosure base, run wires through the hole and secure them to the terminals. 

9.  Use wall plugs (anchors) and screws to secure the enclosure base to the mounting 

surface (Fig. 4). The wall plugs delivered with the device are intended for concrete, brick, 
etc. For other types of surface (drywall, styrofoam), use the appropriately selected wall 
plugs. 

10. Close the detector enclosure. 
11. In the case of the magnetic contact (AMD-200 / AMD-201 / AMD-202 / AVD-200), secure 

the magnet (Fig. 5). taking into account the maximum permissible distance from the 
magnetic sensor (Fig. 6). The distance shown applies to the magnet located at the sensor 
height. Location of the sensor in the enclosure is shown in Fig. 7. 

To make the hole for flush magnet, use the ø9 mm drill bit. 

 

12. 

Configure the detector settings (see the ABAX 2 / ABAX controller manual / the 
INTEGRA 128-WRL control panel manual). 

13. Start the test mode (see the ABAX 2 / ABAX controller manual / the INTEGRA 128-WRL 

control panel manual). 

Содержание AMD-100

Страница 1: ...AXD 200 Wireless multipurpose detector Firmware version 1 00 axd 200_en 03 19 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58 320 94 00 www satel eu...

Страница 2: ...improve the quality of its products which may result in changes in their technical specifications and software Current information about the changes being introduced is available on our website Pleas...

Страница 3: ...d in the ABAX system as AMD 100 This manual applies to the detector with firmware version 1 00 which is supported by ABAX 2 ACU 220 ACU 280 controller ARU 200 repeater ABAX ACU 120 ACU 270 controller...

Страница 4: ...BAX system the detector is identified as AMD 101 AMD 202 Magnetic contact with input for roller shutter detector Detects open door window etc Input for connecting a wired roller shutter detector Input...

Страница 5: ...ate periodical communication Additional communication may take place as a result of alarm see Operating modes Alarms Described below are circumstances in which the detector reports alarm depending on...

Страница 6: ...ht at which the probe is installed The detector reports end of flooding a few seconds after the water level drops below the height at which the probe is installed Operating modes Active information ab...

Страница 7: ...tor inside after opening the enclosure terminal block COM common ground M1 input supported in the case of the AMD 200 AMD 201 AMD 202 and AFD 200 detectors It allows connection of an NC type detector...

Страница 8: ...frame for this purpose This will reduce the probability of the detector being flooded accidentally when the window is partially or full open The following tools will be useful to mount the detector b...

Страница 9: ...location of installation 7 Open the detector enclosure Fig 3 8 If detectors or flood probe are to be connected to the additional input terminals make a hole in the enclosure base run wires through the...

Страница 10: ...8 AXD 200 SATEL...

Страница 11: ...d be determined experimentally after securing the detector to the surface ARD 200 after changing the detector position AFD 200 after submerging the flood probe in water 15 For the water flood detector...

Страница 12: ...p to 2000 m ACU 280 up to 1200 m ABAX up to 500 m Battery CR123A 3 V Battery life expectancy up to 2 years NC type input sensitivity 240 ms Temperature measurement range 10 C 55 C Temperature measurem...

Отзывы: