background image

 

Two-way wireless system ABAX 

ACU-100 

12 

 

Prior to connecting the cable, remove preliminarily the electrostatic charge, e.g. by 
touching a grounded piece of equipment (faucet, heater, etc.) with top of your palm. 

 

It is recommended that the cable be first connected to the controller port. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 5. Connection of computer to the controller serial port. 

 
If the D

LOAD

10 program fails to communicate with the computer after connection of the RS-

232 port, you should: 

  check that the option of programming by means of RS-232 port has been selected on the 

controller DIP-switches; 

  check that the port through which the computer communicates with the controller has been 

properly selected in the D

LOAD

10 program; 

 check that the cables connecting the computer with controller have been properly 

connected. 

4.4 C

ONNECTING THE 

ACX-100

 INPUT 

&

 OUTPUT EXPANSION MODULES

 

The ACU-100 controller communication bus can accept up to five ACX-100 input & output 
expansion modules. 

The modules can only be connected when the controller is 

configured as a wireless device module interfacing with any alarm control panel. 

The ACX-100 expansion modules should be connected to the controller bus in parallel. The 
connection can be made with a typical unscreened cable, as used in the security systems 
(e.g. DY8x0,5). When connecting the modules, remember to set the correct number of ACX-
100 modules connected to the controller on the controller DIP-switches. Lack of 
communication with the module will be signaled on the TPR output as tamper. 
Each module connected to the bus must have a different address set from the range 0 to 4. 
These addresses must correspond to the number of a next module, as shown in Table 4. If 
one ACX-100 module is connected to the controller, it must have address 0 set, if two, one of 
them must have address 0 set, and the other address 1, etc. 
The numeration of control inputs and outputs of the expansion module in the system depends 
on the address set in it, i.e. on the module number. The numbers of control inputs and 
outputs in consecutive expansion modules are shown in Table 4. 

 

TO CONTROLLER 

(view of connector  
on controller board) 

2

4

5

RS-232 serial port 

DTR comp.
CTS comp.
TXD comp.
RXD comp.

GND 

DSR contr. 

RTS contr. 

RXD contr. 

TXD contr. 

COM 

20

7

 

3

 

DB-9 

DB-25 

TO COMPUTER 

5

2

3

8

(female connectors as 
seen from soldering 
points side) 

Содержание Abax ACU-100

Страница 1: ...WIRELESS SYSTEM CONTROLLER ACU 100 Program version 1 05 User Manual acu100_e 11 06 two way wireless system...

Страница 2: ...from a 12V DC source The controller is intended to be used in burglary and panic alarm systems and can be connected to any type of the alarm control panel This product conforms to the following EU Di...

Страница 3: ...nnected to the controller 14 4 5 3 LCD keypad of INTEGRA alarm system 14 4 6 Removal of wireless devices 15 4 6 1 DLOAD10 and DLOADX programs 15 4 6 2 LCD keypad 15 4 7 Hardwired zone output expander...

Страница 4: ...adX program 32 6 3 LCD keypad connected to controller 34 6 3 1 Service mode of keypad connected to the controller 34 6 4 Dload10 program 35 6 5 Description of functions options and commands 38 7 Resto...

Страница 5: ...es place within the frequency band of 868 0MHz 868 6MHz 2 DESCRIPTION OF ACU 100 WIRELESS SYSTEM CONTROLLER The ACU 100 controller supervises and coordinates operation of up to 48 wireless devices The...

Страница 6: ...control panels green steady light no communication with the control panel green blinking light correct communication with the control panel interaction with other alarm control panels green steady lig...

Страница 7: ...to 5 input output expansion modules hence if a higher value is set on the DIP switches it will be also recognized as 5 A B C D DIP switches for setting the controller address in the same way as with t...

Страница 8: ...activation of the detectors is delayed in relation to arming disarming see WIRELESS DETECTORS IN ABAX SYSTEM By having programmed the exit time in the control panel you can avoid delay in activating t...

Страница 9: ...e ACX 100 modules connected to it are being programmed at the same time Depending on how the outputs have been programmed activation of the output is indicated as follows LED assigned to the output co...

Страница 10: ...not be connected In this configuration all problem related information is sent to the control panel through the communication bus 3 WIRELESS DEVICES INTERFACING WITH THE CONTROLLER 3 1 ACX 100 INPUT...

Страница 11: ...electric transducer optical signaling LED indicators remote configuration of 2 signaling modes acoustic signaling duration switching acoustic signaling ON OFF selecting one of 3 sound signals switchin...

Страница 12: ...communication has been designed so as to enable several ACU 100 controllers to work within each other s range Synchronization with the wireless systems already in use is always performed when the con...

Страница 13: ...have been properly connected check that address 0 has been set in the LCD keypad In order to check the keypad address and if necessary to change it 1 Disconnect the KPD keypad power supply and the dat...

Страница 14: ...any alarm control panel The ACX 100 expansion modules should be connected to the controller bus in parallel The connection can be made with a typical unscreened cable as used in the security systems...

Страница 15: ...the system do the following 1 Press the NEW DEVICE button in the program 2 A window will appear in which you should enter the 7 digit serial number of the device being added The serial number can be f...

Страница 16: ...ester has the serial number 0000500 3 Depending on which device is to be added to the system turn on power supply of the ACX 200 expander immediately after start up power up the expander will send a s...

Страница 17: ...automatically assigned to it subsequent in order to the indicated one The zone s will be given a name consisting of the device name and serial number If the device takes up outputs in the system they...

Страница 18: ...e the ACX 200 expander is to be installed and attach it there temporarily It is recommended that the expander be installed as high as possible Thus a better radio communication range can be obtained a...

Страница 19: ...programmed the control panel zones to which the ACU 100 controller outputs will be connected are to be configured as NO type see also section INTERACTION WITH ALARM CONTROL PANELS In the LCD keypad an...

Страница 20: ...control panels select the corresponding option for wireless detector Otherwise the controller input for detector control should be programmed as always active The batteries ensure operation of the det...

Страница 21: ...detector with an extra independent input occupies 2 positions on the list of devices supported by the controller i e reed switch and the extra input to which an outdoor detector of NC type can be conn...

Страница 22: ...le 7 The optical signaling is on for the period of activity of the control panel output controller operating with the INTEGRA series panels or for the time when the control signal is fed onto the cont...

Страница 23: ...es LCD keypad connected to the controller and press the or X key The W and X keys enable movement between the parameters being programmed The type of sound is programmed in the top line of the display...

Страница 24: ...l inputs for each position taken up by the siren and then connect these inputs to suitably programmed outputs of the control panel If the ACU 100 controller works together with another control panel t...

Страница 25: ...r button mode 0 or on the electric circuit status mode 1 and mode 2 Information on the button status is sent in real time Information on the electric circuit status is sent during response time see RE...

Страница 26: ...5 Find the optimum location to install the new wireless device 6 Having completed the test switch off the tester and remove it from the ABAX wireless system Note If not used the tester will switch off...

Страница 27: ...mple if 9 wireless devices were initially registered in the controller but item 7 was later deleted from the list the control panel will assign 2x8 zones to the controller although just 8 devices will...

Страница 28: ...ces No Device No Device 1 ASP 105 siren 17 ASP 105 siren 17 ASP 105 siren 2 18 ASP 105 siren 18 ASP 105 siren 3 APD 100 detector 19 APD 100 detector 19 unused unavailable 4 APD 100 detector 20 APD 100...

Страница 29: ...es are assigned because these devices will function in reversed mode the inactive output will arm and the active output will disarm 5 2 ADDRESSABLE ZONE EXPANDER FOR CA 64 CONTROL PANEL Using the DIP...

Страница 30: ...nciple zone number 16 number of the wireless device on the list In order to simultaneously control the status of detectors and tampers the control panel zones assigned to wireless devices must be prog...

Страница 31: ...1 CLK1 CLK2 output 11 in controller output 12 in controller output 13 in controller output 14 in controller output 15 in controller output 16 in controller 2 CLK1 CLK2 CLK3 zone in 2nd keypad zone in...

Страница 32: ...eration of wireless devices 5 4 WIRELESS DEVICE MODULE INTERFACING WITH ANY ALARM CONTROL PANEL Using the DIP switches set the suitable operating mode of the ACU 100 controller number of ACX 100 modul...

Страница 33: ...interacting with INTEGRA control panels LCD keypad of INTEGRA security system in service mode computer with DLOADX program connected to INTEGRA control panel computer with DLOAD10 program connected to...

Страница 34: ...e period New device Active mode Filter Configuration Remove device Synchronization Test mode on Test mode off Diagnostics of the controller and the wireless devices registered in it is facilitated by...

Страница 35: ...red in the controller as recommended earlier in this manual the devices which occupy both zones and outputs in the system were added first while the devices taking up zones only were added after them...

Страница 36: ...ect the keypad to the controller see CONNECTING KEYPAD TO CONTROLLER 3 Enter the service code and confirm by pressing the key to get access to the menu of controller service functions 4 Program the co...

Страница 37: ...he wireless devices by means of the DLOAD10 program do as follows 1 Set the option of programming through the RS 232 port on the DIP switches on the controller electronics board this is not required w...

Страница 38: ...a real time diagram It illustrates both the noise level and all registered at a particular moment signals from other radio devices operating on the same frequency band Presented in red color are signa...

Страница 39: ...ACU 100 SATEL 37 Fig 18 ACU 100 controller operating window in the DLOAD10 program Fig 19 DLOAD10 program window with a diagram of the level of radio signal received by the controller...

Страница 40: ...ss devices included in the system The serial number in DLOADX and DLOAD10 programs is displayed in on line mode at each device registered in the controller Inputs you should select a control input for...

Страница 41: ...was temporarily lost In the DLOAD10 program all the communication related information is shown in real time with no need for calling any function In the INTEGRA system LCD keypad the information on p...

Страница 42: ...s the Communication quality in percentage form Synchronization the ACU 100 controller checks whether other wireless systems are operating within its range and if so it adjusts the response time accord...

Страница 43: ...K and DAT terminals 4 Reconnect the power supply A short while after power up the operating mode LED indicator will light in red When default settings are restored the LED color will change to green 5...

Страница 44: ...d to section on controller outputs p 7 Information added regarding new wireless devices of ABAX system ACX 200 zone output expander p 8 and 16 ASP 205 wireless indoor siren p 9 and 20 ASW 100 E and AS...

Отзывы: