59
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
55712-55721
Calendar entry #1
55722-55731
Calendar entry #2
55732-55741
Calendar entry #3
…
56022-56031
Calendar entry #32
56032-56191 Reserved
Summary Energy/TOU Registers Setup
E
56672-56703
+0 Not
used
UINT16
R/W
+1
Units of measurement
0=none, 1=kWh, 2=kvarh, 3=kVAh,
4=m
3
, 5=CF (cubic feet), 6=CCF
(hundred cubic feet)
UINT16
R/W
+2
Flags (bitmap)
Bit 0=1 - TOU enabled
UINT16
R/W
+3 Not
used
0
UINT16
R/W
56672-56675
Register #1 Setup
56676-56679
Register #2 Setup
56680-56683
Register #3 Setup
56684-56687
Register #4 Setup
Summary Energy/TOU Registers Source Setup
E
56928-57183
+0
Energy source ID
F11
UINT16
R/W
+1
Target summary register number
0-7 = register #1-#8
UINT16
R/W
+2,3 Multiplier
0-1000000
×
0.001
INT32 R/W
56928-56931
Energy Source #1
56932-56935
Energy Source #2
56936-56939
Energy Source #3
56940-56943
Energy Source #4
Digital Inputs Setup
61728-61775
+0
Pulse mode
0 = pulse, 1 = KYZ
UINT16
R/W
+1
Polarity
Bit 0 – pulse polarity: 0=normal,
1=inverting
Bit 1 – input polarity: 0=normal,
1=inverting
UINT16
R/W
+2
De-bounce time, ms
1-100
UINT16
R/W
The same debounce time is set in
groups of 4 inputs
+3 Reserved
UINT16
R/W
61728-61731
DI1 Setup
61732-61735
DI2 Setup
…
61772-61775
DI12 Setup
Relay Outputs Setup
61984-62007
Provided
by
Northeast
Power
Systems,
Inc.