background image

 

35

Address Point 

ID 

Description 

Options/Range

2

 Units

2, 4

 Type

2

 

R/W Notes 

+16,17 0x1408 

Total kvar import 

0-Pmax 

U3 

UINT32 

 

+18,19 0x1409 

Total kvar export 

0-Pmax 

U3 

UINT32 

 

+20,21 0x140A 

3-phase average L-N/L-L voltage 

0-Vmax 

U1 

UINT32 

 

+22,23 0x140B 

3-phase average L-L voltage 

0-Vmax 

U1 

UINT32 

 

+24,25 0x140C 

3-phase average current 

0-Imax 

U2 

UINT32 

 

14464-14473  

1-Second Auxiliary Values 

 

 

 

 

 

+0,1 0x1500 Not 

used 

 

 

UINT32  R   

+2,3 0x1501 

In (neutral) Current 

0-Imax 

U2 

UINT32 

 

+4,5 0x1502 Frequency 

0-Fmax 

×

0.01Hz 

UINT32 R  

+6,7 0x1503 Voltage 

unbalance 

0-300 

UINT32  R   

+8,9 0x1504 Current 

unbalance 

0-300 

UINT32  R   

14592-14651  

Present Volt, Ampere and Power Demands 

 

 

 

 

 

+0,1 0x1600 

V1/V12 Volt demand 

0-Vmax 

U1 

UINT32 

1

 

+2,3 0x1601 

V2/V23 Volt demand 

0-Vmax 

U1 

UINT32 

1

 

+4,5 0x1602 

V3/V31 Volt demand 

0-Vmax 

U1 

UINT32 

1

 

+6,7 0x1603 

I1 Ampere demand 

0-Imax 

U2 

UINT32 

 

+8,9 0x1604 

I2 Ampere demand 

0-Imax 

U2 

UINT32 

 

+10,11 0x1605 

I3 Ampere demand  

0-Imax 

U2 

UINT32 

 

+12,13 0x1606 

kW import block demand  

0-Pmax 

U3 

UINT32 

 

+14,15 0x1607 

kvar import block demand  

0-Pmax 

U3 

UINT32 

 

+16,17 0x1608 

kVA block demand  

0-Pmax 

U3 

UINT32 

 

+18,19 0x1609 

kW import sliding window demand  

0-Pmax 

U3 

UINT32 

 

+20,21 0x160A 

kvar import sliding window demand  

0-Pmax 

U3 

UINT32 

 

+22,23 0x160B 

kVA sliding window demand  

0-Pmax 

U3 

UINT32 

 

+24,25 0x160C Not 

used 

 

 

UINT32  R   

+26,27 0x160D Not 

used 

 

 

UINT32  R   

+28,29 0x160E Not 

used 

 

 

UINT32  R   

+30,31 0x160F 

kW import accumulated demand  

0-Pmax 

U3 

UINT32 

 

+32,33 0x1610 

kvar import accumulated demand  

0-Pmax 

U3 

UINT32 

 

+34,35 0x1611 

kVA accumulated demand  

0-Pmax 

U3 

UINT32 

 

+36,37 0x1612 

kW import predicted sliding window demand  

0-Pmax 

U3 

UINT32 

 

+38,39 0x1613 

kvar import predicted sliding window demand  

0-Pmax 

U3 

UINT32 

 

+40,41 0x1614 

kVA predicted sliding window demand  

0-Pmax 

U3 

UINT32 

 

+42,43 0x1615 

PF (import) at Max. kVA sliding window demand  

0-1000 

×

0.001 

UINT32 R  

+44,45 0x1616 

kW export block demand  

0-Pmax 

U3 

UINT32 

 

+46,47 0x1617 

kvar export block demand  

0-Pmax 

U3 

UINT32 

 

+48,49 0x1618 

kW export sliding window demand  

0-Pmax 

U3 

UINT32 

 

+50,51 0x1619 

kvar export sliding window demand  

0-Pmax 

U3 

UINT32 

 

+52,53 0x161A 

kW export accumulated demand  

0-Pmax 

U3 

UINT32 

 

+54,55 0x161B 

kvar export accumulated demand  

0-Pmax 

U3 

UINT32 

 

+56,57 0x161C 

kW export predicted sliding window demand  

0-Pmax 

U3 

UINT32 

 

+58,59 0x161D 

kvar export predicted sliding window demand  

0-Pmax 

U3 

UINT32 

 

+60,61 0x161E Not 

used 

 

 

UINT32  R   

Provided 

by 
Northeast 

Power 

Systems, 

Inc. 

www.nepsi.com

Содержание pm130e

Страница 1: ...Series PM130 PLUS Powermeters PM130P PM130E PM130EH Modbus Communications Protocol Reference Guide BG0427 Rev A4 Provided by Northeast Power Systems Inc www nepsi com ...

Страница 2: ...s 11 1 6 or higher Added DNP 16 bit and 32 bit frozen binary counter and analog input objects Added DNP Object 50 Time and Date to the Class 0 point list F W versions 11 1 11 or higher Added TCP event notification client Added GPRS setup and communication counters Added time triggers Added DI change event log F W versions 11 2 1 or higher Added 8 tariffs F W versions 11 3 1 or higher Added event a...

Страница 3: ...Multi section Data Log Files 15 Reading Real time Waveforms 16 2 11 TCP Notification Client 16 3 MODBUS REGISTER MAP 18 3 1 Modbus Setup Registers 18 Assignable Modbus Registers 18 Assignable Registers Map 18 Modbus Conversion Scales 18 Device Data Scales 18 32 bit Register Type 18 3 2 16 bit Scaled Analog Registers and Energy Counters Basic Register Set 19 3 3 16 bit Scaled Analog Registers Binar...

Страница 4: ...ister 3 E 29 TOU Maximum Demand Register 4 E 29 V1 V12 Harmonic Angles EH 30 V2 V23 Harmonic Angles EH 30 V1 V31 Harmonic Angles EH 30 I1 Harmonic Angles EH 30 I2 Harmonic Angles EH 30 I3 Harmonic Angles EH 30 Setpoint Status 30 3 4 32 bit Analog Registers Binary Registers and Counters 32 Special Inputs 32 Digital Inputs 32 Relay Outputs 32 Counters 32 1 Cycle Phase Values 32 1 Cycle Total Values ...

Страница 5: ...isters 41 Generic TOU Season Maximum Demand Registers 42 Generic Data 42 3 5 Minimum Maximum Log Registers 43 Minimum Phase Values 43 Minimum Total Values 43 Minimum Auxiliary Values 43 Maximum Phase Values 43 Maximum Total Values 44 Maximum Auxiliary Values 44 Summary Energy Maximum Demands E 44 Maximum Demands 44 TOU Maximum Demand Register 1 E 45 TOU Maximum Demand Register 2 E 45 TOU Maximum D...

Страница 6: ... Analog and Digital I O Configuration 61 I O Slots Configuration Info 61 I O Type Info 61 3 9 File Transfer Registers E 62 File Transfer Control Blocks 62 File Info Response Block Variation 0 File info 63 File Info Response Block Variation 1 Current record info 64 File Info Response Block Variation 2 Data log record structure 64 Event Log Response Block 64 Data Log Response Block 65 RT Waveform Re...

Страница 7: ...3 AO Parameters ID 73 Event Cause Point ID 73 Event Effect ID 74 Data Point ID 74 Event Type ID 74 Device Diagnostics 74 DNP Object Variations 75 DNP Class 0 Objects 75 Wiring Mode 75 Instrument Options 76 I O Slot Types 76 Provided by Northeast Power Systems Inc www nepsi com ...

Страница 8: ...o PM130A PM130P PM130E and PM130EH meters IMPORTANT In 3 wire connection schemes the unbalanced current and phase readings for power factor active power and reactive power will be zeros because they have no meaning Only the total three phase power values are provided Most of the advanced features are configured using multiple setup parameters that can be accessed in a number of contiguous register...

Страница 9: ...mal Meaning in Modbus Action 03 Read holding registers Read multiple registers 04 Read input registers Read multiple registers 06 Preset single register Write single register 16 Preset multiple registers Write multiple registers 081 Loop back test Communications test 1 The PM130 supports only diagnostic code 0 return query data 2 4 Exception Responses The instrument sends an exception response whe...

Страница 10: ...the type of 32 bit registers in your meter Analog registers 256 through 308 and 6656 through 10935 contain scaled 16 bit data 2 7 1 16 bit Scaled Integer Format 16 bit scaled analog data is transmitted in a single 16 bit Modbus register being scaled to the range of 0 to 9999 To get a true reading a reverse conversion should be done using the following formula LO 9999 LO HI X Y where Y True reading...

Страница 11: ... 1000 119 232 kW LO_ENG Pmax 119 232 kW If the raw data reading is 5500 then the power reading in engineering units will be as follows Watts reading 5500 119 232 119 232 9999 0 119 232 11 936 kW If the raw data reading is 500 then the power reading in engineering units will be as follows Watts reading 500 119 232 119 232 9999 0 119 232 107 307 kW 4 Power Factor readings Power factor engineering sc...

Страница 12: ...bit Min Max registers see Sections 3 3 3 5 can be read in IEEE single precision floating point format in two adjacent 16 bit Modbus registers the low order register first The low order register always starts at an even Modbus address 2 7 4 32 bit Modulo 10000 Format Energy counters 287 294 and 301 302 are read in two contiguous 16 bit registers in a modulo 10000 format The first low order register...

Страница 13: ... continuous chunk and thus prevents possible leakage of memory caused by fragmentation Data records in a file are arranged in the order of their recording Each record has a unique 16 bit sequence number that is incremented modulo 65536 with each new record The sequence number can be used to point to a particular record in the file or to check the sequence of records when uploading files from the d...

Страница 14: ...e New records are added to the file automatically every day at midnight You can review the list of parameters recorded to the file through the file info request response blocks using info requests with variation 2 see Section 3 9 or through the Data log 16 setup it shows the list of parameters for the first file section which represents the first configured energy usage register Real time Waveform...

Страница 15: ... file record acknowledge the record and check bit 0 in the record status word Bit 0 is set to 1 only once when you read the last record of the file The following gives a summary of steps you should do to read an ordinal log file 1 If you wish to begin reading a file from a particular record or from the first record use either the Set File Position request with the desired record sequence number or...

Страница 16: ...gisters using write function 16 The following table shows the message exchange structure Modbus Register Description Type Comment 0 1 Device serial number UINT32 2 4 Device MAC address CHAR6 5 Device address UINT16 Device port address 6 7 Device IP address UINT32 Network byte order 8 Event type UINT16 See F22 in Section 5 9 Event sequence number UINT16 Not used 10 11 Event timestamp seconds UINT32...

Страница 17: ...ogrammable setpoints To send event notifications to a server configure a setpoint to respond to a desired trigger or to periodic time events and put Notification to the setpoint action list Provided by Northeast Power Systems Inc www nepsi com ...

Страница 18: ... address 0 65535 UINT16 R W Modbus Conversion Scales 240 Low raw scale 0 UINT16 R 241 High raw scale 9999 UINT16 R Device Data Scales 242 Voltage scale secondary volts 60 828 1V UINT16 R W Default 144V 243 Current scale secondary amps 10 100 0 1A UINT16 R W Default 2 CT secondary 244 245 Reserved 0 UINT16 R 32 bit Register Type 246 Type of 32 bit registers Bits 0 1 analog values 0 32 bit integer 1...

Страница 19: ...0 001 INT16 R 18 0x1403 Total PF 1 000 1 000 0 001 INT16 R 19 0x1400 Total kW Pmax Pmax U3 INT16 R 20 0x1401 Total kvar Pmax Pmax U3 INT16 R 21 0x1402 Total kVA Pmax Pmax U3 UINT16 R 22 0x1501 In neutral Current 0 Imax U2 UINT16 R 23 0x1502 Frequency 45 00 65 00 0 01Hz UINT16 R 24 0x3709 Maximum kW import sliding window demand Pmax Pmax U3 UINT16 R 25 0x160F kW import accumulated demand Pmax Pmax ...

Страница 20: ... R 3 sec value 51 0x111C I2 Current TDD 0 100 0 0 1 UINT16 R 3 sec value 52 0x111D I3 Current TDD 0 100 0 0 1 UINT16 R 3 sec value NOTES Energy and power demand readings are only available in PM130E and PM130EH meters Total harmonics are only available in PM130EH meters 1 Voltage and Voltage Harmonics Readings When the 4LN3 3LN3 or 3BLN3 wiring mode is selected the voltages will be line to neutral...

Страница 21: ...0x0C07 kW L2 Pmax Pmax U3 INT16 R 8 0x0C08 kW L3 Pmax Pmax U3 INT16 R 9 0x0C09 kvar L1 Pmax Pmax U3 INT16 R 10 0x0C0A kvar L2 Pmax Pmax U3 INT16 R 11 0x0C0B kvar L3 Pmax Pmax U3 INT16 R 12 0x0C0C kVA L1 0 Pmax U3 UINT16 R 13 0x0C0D kVA L2 0 Pmax U3 UINT16 R 14 0x0C0E kVA L3 0 Pmax U3 UINT16 R 15 0x0C0F Power factor L1 1 000 1 000 0 001 INT16 R 16 0x0C10 Power factor L2 1 000 1 000 0 001 INT16 R 17...

Страница 22: ... 12 0x0F0C 3 phase average current 0 Imax U2 UINT32 R 7296 7300 1 Cycle Auxiliary Values 0 0x1000 Not used UINT16 R 1 0x1001 In neutral Current 0 Imax U2 UINT16 R 2 0x1002 Frequency 0 Fmax 0 01Hz UINT16 R 3 0x1003 Voltage unbalance 0 300 UINT16 R 4 0x1004 Current unbalance 0 300 UINT16 R 7316 7331 Phasor 0 0x1080 V1 V12 Voltage magnitude 0 Vmax U1 UINT16 R 1 1 0x1081 V2 V23 Voltage magnitude 0 Vma...

Страница 23: ... UINT16 R 1 3 sec value 20 0x1114 V3 V31 Voltage THD 0 999 9 0 1 UINT16 R 1 3 sec value 21 0x1115 I1 Current THD 0 999 9 0 1 UINT16 R 3 sec value 22 0x1116 I2 Current THD 0 999 9 0 1 UINT16 R 3 sec value 23 0x1117 I3 Current THD 0 999 9 0 1 UINT16 R 3 sec value 24 0x1118 I1 K Factor 1 0 999 9 0 1 UINT16 R 3 sec value 25 0x1119 I2 K Factor 1 0 999 9 0 1 UINT16 R 3 sec value 26 0x111A I3 K Factor 1 ...

Страница 24: ...ort sliding window demand 0 Pmax U3 UINT16 R 10 0x160A kvar import sliding window demand 0 Pmax U3 UINT16 R 11 0x160B kVA sliding window demand 0 Pmax U3 UINT16 R 12 0x160C Not used UINT16 R 13 0x160D Not used UINT16 R 14 0x160E Not used UINT16 R 15 0x160F kW import accumulated demand 0 Pmax U3 UINT16 R 16 0x1610 kvar import accumulated demand 0 Pmax U3 UINT16 R 17 0x1611 kVA accumulated demand 0 ...

Страница 25: ...3 0 999 999 999 kvarh UINT32 R 32 33 0x1715 kvarh Q4 0 999 999 999 kvarh UINT32 R 7616 7633 Phase Energies E 0 1 0x1800 kWh import L1 0 999 999 999 kWh UINT32 R 2 3 0x1801 kWh import L2 0 999 999 999 kWh UINT32 R 4 5 0x1802 kWh import L3 0 999 999 999 kWh UINT32 R 6 7 0x1803 kvarh import L1 0 999 999 999 kvarh UINT32 R 8 9 0x1804 kvarh import L2 0 999 999 999 kvarh UINT32 R 10 11 0x1805 kvarh impo...

Страница 26: ...1E27 H40 Harmonic distortion 0 100 00 0 01 UINT16 R 8296 8313 Fundamental Phase Values EH 2 cycle values 0 0x2900 V1 V12 Voltage 0 Vmax U1 UINT16 R 1 1 0x2901 V2 V23 Voltage 0 Vmax U1 UINT16 R 1 2 0x2902 V3 V31 Voltage 0 Vmax U1 UINT16 R 1 3 0x2903 I1 Current 0 Imax U2 UINT16 R 4 0x2904 I2 Current 0 Imax U2 UINT16 R 5 0x2905 I3 Current 0 Imax U2 UINT16 R 6 0x2906 kW L1 Pmax Pmax U3 INT16 R 7 0x290...

Страница 27: ... 0 0x3400 V1 V12 Voltage 0 Vmax U1 UINT16 R 1 1 0x3401 V2 V23 Voltage 0 Vmax U1 UINT16 R 1 2 0x3402 V3 V31 Voltage 0 Vmax U1 UINT16 R 1 3 0x3403 I1 Current 0 Imax U2 UINT16 R 4 0x3404 I2 Current 0 Imax U2 UINT16 R 5 0x3405 I3 Current 0 Imax U2 UINT16 R 8776 8779 Maximum 1 Cycle Total Values 0 0x3500 Total kW Pmax Pmax U3 INT16 R 1 0x3501 Total kvar Pmax Pmax U3 INT16 R 2 0x3502 Total kVA 0 Pmax U3...

Страница 28: ...e 1 4 4 7 Season 2 Profile 1 4 8 11 Season 3 Profile 1 4 12 15 Season 4 Profile 1 4 UINT16 R W 9076 9079 Scaled Analog Outputs 0 0x3C80 Analog output AO1 0 4095 UINT16 R W 1 0x3C81 Analog output AO2 0 4095 UINT16 R W 2 0x3C82 Analog output AO3 0 4095 UINT16 R W 3 0x3C83 Analog output AO4 0 4095 UINT16 R W 9096 9111 TOU Energy Register 1 E 0 1 0x3D00 Tariff 1 register 0 999 999 999 kWh UINT32 R 2 3...

Страница 29: ... Pmax U3 UINT16 R 2 0x4602 Summary register 3 demand 0 Pmax U3 UINT16 R 3 0x4603 Summary register 4 demand 0 Pmax U3 UINT16 R 9516 9519 Summary Energy Maximum Demands E 0 0x4780 Summary register 1 maximum demand 0 Pmax U3 UINT16 R 1 0x4781 Summary register 2 maximum demand 0 Pmax U3 UINT16 R 2 0x4782 Summary register 3 maximum demand 0 Pmax U3 UINT16 R 3 0x4783 Summary register 4 maximum demand 0 ...

Страница 30: ...0816 10855 I1 Harmonic Angles EH 3 0 0x6700 H01 Harmonic angle 180 0 180 0 0 1º INT16 R 1 0x6700 H02 Harmonic angle 180 0 180 0 0 1º INT16 R 39 0x6727 H40 Harmonic angle 180 0 180 0 0 1º INT16 R 10856 10895 I2 Harmonic Angles EH 3 0 0x6800 H01 Harmonic angle 180 0 180 0 0 1º INT16 R 1 0x6800 H02 Harmonic angle 180 0 180 0 0 1º INT16 R 39 0x6827 H40 Harmonic angle 180 0 180 0 0 1º INT16 R 10896 109...

Страница 31: ...xamples see Section 2 7 1 16 bit Scaled Integer Format 3 Harmonic angles are referenced to the fundamental voltage harmonic H01 on phase L1 4 The binary counters and energy registers can be read either as 32 bit integer or 32 bit floating point values Refer to Section 2 7 for details Provided by Northeast Power Systems Inc www nepsi com ...

Страница 32: ...R 14 15 0x0C07 kW L2 Pmax Pmax U3 INT32 R 16 17 0x0C08 kW L3 Pmax Pmax U3 INT32 R 18 19 0x0C09 kvar L1 Pmax Pmax U3 INT32 R 20 21 0x0C0A kvar L2 Pmax Pmax U3 INT32 R 22 23 0x0C0B kvar L3 Pmax Pmax U3 INT32 R 24 25 0x0C0C kVA L1 0 Pmax U3 UINT32 R 26 27 0x0C0D kVA L2 0 Pmax U3 UINT32 R 28 29 0x0C0E kVA L3 0 Pmax U3 UINT32 R 30 31 0x0C0F Power factor L1 1000 1000 0 001 INT32 R 32 33 0x0C10 Power fac...

Страница 33: ...5 0x0F0C 3 phase average current 0 Imax U2 UINT32 R 13824 13833 1 Cycle Auxiliary Values 0 1 0x1000 Not used UINT32 R 2 3 0x1001 In neutral Current 0 Imax U2 UINT32 R 4 5 0x1002 Frequency 0 Fmax 0 01Hz UINT32 R 6 7 0x1003 Voltage unbalance 0 300 UINT32 R 8 9 0x1004 Current unbalance 0 300 UINT32 R 13864 13895 Phasor 0 1 0x1080 V1 V12 Voltage magnitude 0 Vmax U1 UINT32 R 1 2 3 0x1081 V2 V23 Voltage...

Страница 34: ... 1 UINT32 R 1 3 sec value 40 41 0x1114 V3 V31 Voltage THD 0 9999 0 1 UINT32 R 1 3 sec value 42 43 0x1115 I1 Current THD 0 9999 0 1 UINT32 R 3 sec value 44 45 0x1116 I2 Current THD 0 9999 0 1 UINT32 R 3 sec value 46 47 0x1117 I3 Current THD 0 9999 0 1 UINT32 R 3 sec value 48 49 0x1118 I1 K Factor 10 9999 0 1 UINT32 R 3 sec value 50 51 0x1119 I2 K Factor 10 9999 0 1 UINT32 R 3 sec value 52 53 0x111A...

Страница 35: ...t sliding window demand 0 Pmax U3 UINT32 R 20 21 0x160A kvar import sliding window demand 0 Pmax U3 UINT32 R 22 23 0x160B kVA sliding window demand 0 Pmax U3 UINT32 R 24 25 0x160C Not used UINT32 R 26 27 0x160D Not used UINT32 R 28 29 0x160E Not used UINT32 R 30 31 0x160F kW import accumulated demand 0 Pmax U3 UINT32 R 32 33 0x1610 kvar import accumulated demand 0 Pmax U3 UINT32 R 34 35 0x1611 kVA...

Страница 36: ...2 R 32 33 0x1715 kvarh Q4 0 999 999 999 kvarh UINT32 R 14760 14767 Summary Energy Registers E 0 1 0x1780 Summary energy register 1 0 999 999 999 kWh UINT32 R 2 3 0x1781 Summary energy register 2 0 999 999 999 kWh UINT32 R 4 5 0x1782 Summary energy register 3 0 999 999 999 kWh UINT32 R 6 7 0x1783 Summary energy register 4 0 999 999 999 kWh UINT32 R 14848 14865 Phase Energies E 0 1 0x1800 kWh import...

Страница 37: ...T32 R 78 79 0x1D27 H40 Harmonic distortion 0 10000 0 01 UINT32 R 15616 15695 I3 Harmonic Distortions EH 0 1 0x1E00 H01 Harmonic distortion 0 10000 0 01 UINT32 R 2 3 0x1E01 H02 Harmonic distortion 0 10000 0 01 UINT32 R 78 79 0x1E27 H40 Harmonic distortion 0 10000 0 01 UINT32 R 17024 17059 Fundamental H01 Phase Values EH 2 cycle values 0 1 0x2900 V1 V12 Voltage 0 Vmax U1 UINT32 R 1 2 3 0x2901 V2 V23...

Страница 38: ...0 1000 0 001 UINT32 R Absolute value 17664 17669 Minimum 1 Cycle Auxiliary Values 0 1 0x2E00 Not used UINT32 R 2 3 0x2E01 In Current 0 Imax U2 UINT32 R 4 5 0x2E02 Frequency 0 Fmax 0 01Hz UINT32 R 18432 18491 Maximum 1 Cycle Phase Values 0 1 0x3400 V1 V12 Voltage 0 Vmax U1 UINT32 R 1 2 3 0x3401 V2 V23 Voltage 0 Vmax U1 UINT32 R 1 4 5 0x3402 V3 V31 Voltage 0 Vmax U1 UINT32 R 1 6 7 0x3403 I1 Current ...

Страница 39: ...40 41 0x3714 Not used UINT32 R 42 43 0x3715 In Maximum ampere demand 0 Imax U2 UINT32 R 19456 19459 TOU Parameters E 0 1 0x3C00 Active tariff 0 7 UINT32 R 2 3 0x3C01 Active profile 0 15 1 3 Season 1 Profile 1 4 4 7 Season 2 Profile 1 4 8 11 Season 3 Profile 1 4 12 15 Season 4 Profile 1 4 UINT32 R 19496 19503 Scaled Analog Outputs 0 1 0x3C80 Analog output AO1 0 4095 UINT32 R W 2 3 0x3C81 Analog out...

Страница 40: ...6 20743 Summary Energy Sliding Window Demands E 0 1 0x4600 Summary register 1 demand 0 Pmax U3 UINT32 R 2 3 0x4601 Summary register 2 demand 0 Pmax U3 UINT32 R 4 5 0x4602 Summary register 3 demand 0 Pmax U3 UINT32 R 6 7 0x4603 Summary register 4 demand 0 Pmax U3 UINT32 R 20904 20911 Summary Energy Maximum Demands E 0 1 0x4780 Summary register 1 maximum demand 0 Pmax U3 UINT32 R 2 3 0x4781 Summary ...

Страница 41: ...armonic Angles EH 1 3 0 1 0x6600 H01 Harmonic angle 1800 1800 0 1º INT32 R 2 3 0x6600 H02 Harmonic angle 1800 1800 0 1º INT32 R 78 79 0x6627 H40 Harmonic angle 1800 1800 0 1º INT32 R 25088 25167 I1 Harmonic Angles EH 3 0 1 0x6700 H01 Harmonic angle 1800 1800 0 1º INT32 R 2 3 0x6700 H02 Harmonic angle 1800 1800 0 1º INT32 R 78 79 0x6727 H40 Harmonic angle 1800 1800 0 1º INT32 R 25216 25295 I2 Harmo...

Страница 42: ... Vmax U1 UINT32 0x7407 I1 current 0 Imax U2 UINT32 0x7408 I2 current 0 Imax U2 UINT32 0x7409 I3 current 0 Imax U2 UINT32 NOTES Energy and power demand readings are only available in PM130E and PM130EH meters Harmonics are only available in PM130EH meters 1 Voltage and voltage harmonics readings When the 4LN3 3LN3 or 3BLN3 wiring mode is selected the voltages will be line to neutral for any other w...

Страница 43: ...l kvar Timestamp Pmax Pmax U3 sec INT32 UINT32 R R 8 9 10 11 0x2D02 Min Total kVA Timestamp 0 Pmax U3 sec UINT32 UINT32 R R 12 13 14 15 0x2D03 Min Total PF Timestamp 1000 1000 0 001 sec INT32 UINT32 R R 36352 36362 Minimum Auxiliary Values 0 1 2 3 0x2E00 Not used UINT32 UINT32 R R 4 5 6 7 0x2E01 Min In Current Timestamp 0 Imax U2 sec UINT32 UINT32 R R 8 9 10 11 0x2E02 Min Frequency Timestamp 0 Fma...

Страница 44: ...and Timestamp 0 Pmax U3 UINT32 R 4 5 6 7 0x4781 Summary register 2 Maximum Demand Timestamp 0 Pmax U3 UINT32 R 12 13 14 15 0x4783 Summary register 4 Maximum Demand Timestamp 0 Pmax U3 UINT32 R 37632 37695 Maximum Demands 0 1 2 3 0x3700 V1 V12 Maximum volt demand Timestamp 0 Vmax U1 sec UINT32 UINT32 R R 1 4 5 6 7 0x3701 V2 V23 Maximum volt demand Timestamp 0 Vmax U1 sec UINT32 UINT32 R R 1 8 9 10 ...

Страница 45: ...R 68 69 70 71 0x3711 Not used Timestamp UINT32 UINT32 R R 71 73 74 75 0x3712 Not used Timestamp UINT32 UINT32 R R 76 77 78 79 0x3713 Not used Timestamp UINT32 UINT32 R R 80 81 82 83 0x3714 Not used Timestamp UINT32 UINT32 R R 84 85 86 87 0x3715 In Maximum ampere demand Timestamp 0 Imax U2 sec UINT32 UINT32 R R 38144 38175 TOU Maximum Demand Register 1 E 0 1 2 3 0x4800 Tariff 1 maximum demand Times...

Страница 46: ...6 7 0x4881 Tariff 2 maximum demand Timestamp 0 Pmax U3 sec UINT32 UINT32 R R R 28 29 30 31 0x4887 Tariff 8 maximum demand Timestamp 0 Pmax U3 sec UINT32 UINT32 R R NOTES Power demand readings are only available in PM130E and PM130EH meters 1 Voltage and voltage harmonics readings When the 4LN3 3LN3 or 3BLN3 wiring mode is selected the voltages will be line to neutral for any other wiring mode they...

Страница 47: ...7 RO4 Control Device Reset Clear Registers 3404 Clear total energy registers 0 UINT16 W 3405 Clear total maximum demand registers 0 Clear all maximum demands 1 Clear power demands E 2 Clear volt ampere and harmonic demands UINT16 W 3406 Clear TOU energy registers E 0 UINT16 W 3407 Clear TOU maximum demand registers E 0 UINT16 W 3408 Clear pulse counters 0 Clear all counters 1 4 Clear counter 1 4 U...

Страница 48: ...stamp seconds since 1 1 1970 F1 sec UINT32 R 2 3 Timestamp seconds fraction µsec 0 999000 µsec UINT32 R 4 DI number 0 11 DI1 DI12 UINT16 R 5 DI status 0 open 1 closed UINT16 R 4368 4373 Event 1 oldest 4374 4379 Event 2 4380 4385 Event 3 4386 4391 Event 4 4392 4397 Event 5 most recent Memory Status Registers 44262 44263 Memory size bytes 59520 UINT32 R 44264 44265 Free memory bytes UINT32 R 44266 4...

Страница 49: ...nits Type R W Notes 44412 Successful TCP notification client connections 0 65534 UINT16 R 44413 Failed TCP notification client connections 0 65534 UINT16 R 44414 44441 Reserved UINT16 R 65535 N A Provided by Northeast Power Systems Inc www nepsi com ...

Страница 50: ...wer decimal digits minor version number 25 Boot loader build number 1 99 UINT16 R 26 31 Reserved UINT16 R Factory Device Settings 46112 46178 0 V1 V3 input range 690 120 option U V UINT16 R Does not limit the 690V input range 1 V1 V3 input overload 120 UINT16 R 2 3 Reserved UINT16 R 4 I1 I3 input range 1 5 A UINT16 R 5 I1 I3 input overload 200 UINT16 R 6 13 Reserved UINT16 R 14 63 Unused UINT16 64...

Страница 51: ...TEC ASCII 1 Modbus RTU 2 DNP3 0 5 Profibus DP UINT16 R W 1 Interface COM1 2 RS 485 COM2 0 RS 232 1 RS 422 2 RS 485 5 RF 6 Ethernet 7 Profibus UINT16 R W 2 Device address SATEC ASCII 0 99 Modbus RTU 1 247 DNP3 0 0 65532 Profibus DP 0 126 UINT16 R W 3 Baud rate 1 300 bps 2 600 bps 3 1200 bps 4 2400 bps 5 4800 bps 6 9600 bps 7 19200 bps 8 38400 bps 9 57600 bps 10 115200 bps UINT16 R W 4 Data format 0...

Страница 52: ... time only 1 DST enabled UINT16 R W 1 DST start month 1 12 UINT16 R W 2 DST start week of the month 1 4 1st 2nd 3rd and 4th week 5 the last week of the month UINT16 R W 3 DST start weekday 1 7 1 Sun 7 Sat UINT16 R W 4 DST end month 1 12 UINT16 R W 5 DST end week of the month 1 4 1st 2nd 3rd and 4th week 5 the last week of the month UINT16 R W 6 DST end weekday 1 7 1 Sun 7 Sat UINT16 R W 7 Clock sy...

Страница 53: ...etpoint 10 2656 2663 Setpoint 11 2664 2671 Setpoint 12 2672 2679 Setpoint 13 2680 2687 Setpoint 14 2688 2695 Setpoint 15 2696 2703 Setpoint 16 Pulse Counters Setup 2940 2947 0 Source digital input ID 0 not assigned 1 12 DI1 DI12 UINT16 R W 1 Multiplier 0 9999 UINT16 R W 2940 2941 Counter 1 Setup 2942 2943 Counter 2 Setup 2944 2945 Counter 3 Setup 2946 2947 Counter 4 Setup Analog Outputs Setup 3148...

Страница 54: ...wer client enabled 0 client disabled 1 client enabled UINT32 R W 6 7 Time to next session 1 99999 min UINT32 R W 8 9 Time to next session 1 99999 min UINT32 R Same as previous 10 15 Reserved Internet Service Provider ISP accounts 46784 46831 0 15 ISP telephone number CHAR32 R W 16 31 Login name CHAR32 R W 32 47 Login password CHAR32 R W GPRS Setup 46832 46879 0 15 Access Point Name APN CHAR32 R W ...

Страница 55: ...0 0xFFFFFE 0 not active UINT32 R W 14 15 Client IP address for spontaneous transmission 0 0xFFFFFE 0 not active UINT32 R W 16 17 Not used 0 UINT32 R W 18 Not used 0 UINT16 R W 19 Respond with class 1 data to class 2 requests 0 disabled 1 enabled UINT16 R W 20 Single point start mapped address 1 4095 UINT16 R W 21 Single point default static object type F30 UINT16 R W 22 Single point default event ...

Страница 56: ... W 2 3 Deadband threshold See Section 3 4 for the point range and resolution INT32 R W 49716 49719 Mapped static event point 1 49720 49723 Mapped static event point 2 49968 49971 Mapped static event point 64 DNP Options Setup 51158 51183 0 Default Binary Input Static object variation F24 default 0 UINT16 R W 1 Reserved UINT16 R W 2 Default Binary Counter object variation F24 default 3 UINT16 R W 3...

Страница 57: ...rs per section record 1 9 UINT16 R W 5 Not used 0 UINT16 R W 6 Section record size bytes for info only UINT16 R 7 File record size bytes for info only UINT16 R 8 9 Allocated file size bytes for info only UINT32 R 52598 52607 Event Log File Setup 52608 52617 Data Log 1 File Setup 52758 52767 Data Log 16 File Setup Data Log Setup E 54006 54517 0 Data log parameter 1 ID 0x0000 0xFFFF UINT16 R W 1 Dat...

Страница 58: ...e 1 55646 55653 Daily profile 10 Season 3 Day type 2 55654 55661 Daily profile 11 Season 3 Day type 3 55662 55669 Daily profile 12 Season 3 Day type 4 55670 55677 Daily profile 13 Season 4 Day type 1 55678 55685 Daily profile 14 Season 4 Day type 2 55686 55693 Daily profile 15 Season 4 Day type 3 55694 55701 Daily profile 16 Season 4 Day type 4 55702 55711 Reserved TOU Calendar Setup E 55712 56031...

Страница 59: ...ister 4 Setup Summary Energy TOU Registers Source Setup E 56928 57183 0 Energy source ID F11 UINT16 R W 1 Target summary register number 0 7 register 1 8 UINT16 R W 2 3 Multiplier 0 1000000 0 001 INT32 R W 56928 56931 Energy Source 1 56932 56935 Energy Source 2 56936 56939 Energy Source 3 56940 56943 Energy Source 4 Digital Inputs Setup 61728 61775 0 Pulse mode 0 pulse 1 KYZ UINT16 R W 1 Polarity ...

Страница 60: ...nits per pulse 1 10000 x0 1 UINT16 R W 5 Reserved UINT16 R W 61984 61989 RO1 Setup 61990 61995 RO2 Setup 61996 62001 RO3 Setup 62002 62007 RO4 Setup Analog Outputs Setup 62560 62571 0 Output parameter ID F18 UINT16 R W 1 Not used 0 UINT16 R W 2 3 Zero scale value 0 4 mA See Section 3 4 INT32 R W 4 5 Full scale value 20 1 mA See Section 3 4 INT32 R W 62560 62565 AO1 Setup 62566 62571 AO2 Setup Prov...

Страница 61: ...T16 R 63008 63011 DI Slot Configuration 63012 63015 RO Slot Configuration 63016 63019 AI AO Slot Configuration 63020 63055 Reserved I O Type Info 63056 63119 0 Number of I O slots of this type 0 1 UINT16 R 1 Total number of I O s of this type 0 4 UINT16 R 2 Number of I O s on the slot 0 4 UINT16 R 3 Not used 0 UINT16 R 63056 63059 DI Type Info 63060 63063 RO Type Info 63064 63067 AI Type Info 6306...

Страница 62: ...1 1970 F1 sec UINT32 R W Note 3 10 11 Find key Start time fractional seconds in µsec µsec UINT32 R W Note 3 12 13 Find key End time seconds since 1 1 1970 F1 sec UINT32 R W Note 3 14 15 Find key End time fractional seconds in µsec µsec UINT32 R W Note 3 16 31 Reserved UINT16 R W 63152 63799 File Response Block Data transfer area 0 647 UINT16 R 64944 64951 File Info Request Block 0 File function 9 ...

Страница 63: ...64952 64959 Block Heading 0 File function 9 UINT16 R 1 File ID 16 UINT16 R 2 Section number 0 31 UINT16 R 3 Section channel ID F6 F7 UINT16 R 4 Maximum number of records in the block 1 UINT16 R 5 Record size words 36 UINT16 R 6 Request variation 0 UINT16 R 7 Reserved 0 UINT16 R 64960 64997 File Info 0 File type 0 UINT16 R 1 File attributes F3 UINT16 R 2 File section status F4 UNT16 R 3 Number of s...

Страница 64: ... sequence number 0 65535 UINT16 R 4 5 Current record time seconds since 1 1 1970 F1 sec UINT32 R 6 7 Current record time fractional seconds µsec UINT32 R File Info Response Block Variation 2 Data log record structure 64952 64959 Block Heading 0 File function 9 UINT16 R 1 File ID 1 16 UINT16 R 2 Section number 0 7 UINT16 R 3 Section channel ID F6 F7 UINT16 R 4 Number of records in the block 1 UINT1...

Страница 65: ...ading 0 Last file function 1 3 5 11 UINT16 R 1 File ID 1 16 UINT16 R 2 Section number 0 7 UINT16 R 3 Section channel ID F6 UINT16 R 4 Maximum number of records in the block 8 for regular log 4 for profile log UINT16 R 5 Record size words 8 2 Number of parameters UINT16 R 6 Request variation 0 UINT16 R 7 Reserved 0 UINT16 R 63160 63367 Data Log Records 0 Record status F5 INT16 R 1 Record sequence n...

Страница 66: ...sec UINT16 R 17 Sampling rate samples cycle 32 64 128 UINT16 R 18 Sampling frequency 4500 6500 0 01Hz UINT16 R 19 Channel offset sampling units 0 INT16 R 20 21 Channel multiplier primary units See Generic Data in Section 3 4 UINT32 R 22 Channel divisor sampling units 4095 UINT16 R 23 Length of a sample series data points 512 UINT16 R 24 127 Not used 0 UINT16 R 128 Sample Series 128 639 Sample data...

Страница 67: ... kWh UINT32 6 TRF5 0x7004 Tariff 5 energy reading 0 999 999 999 kWh UINT32 7 TRF6 0x7005 Tariff 6 energy reading 0 999 999 999 kWh UINT32 8 TRF7 0x7006 Tariff 7 energy reading 0 999 999 999 kWh UINT32 9 TRF8 0x7007 Tariff 8 energy reading 0 999 999 999 kWh UINT32 16 4 Daily Maximum Demand Register 1 1 REG1 MD 0x4780 Summary total max demand reading 0 Pmax U3 UINT32 2 TRF1 MD 0x7100 Tariff 1 max de...

Страница 68: ...s selected in the Summary TOU Register setup and for which energy use profile is enabled A maximum demand profile section is allocated for registers for which maximum demand profile is enabled in the Summary TOU Register setup Not configured sections channels are not available for download Refer to the file channel mask in the file info for configured channels 2 The number of parameters in a secti...

Страница 69: ...io 1 1kW kvar kVA See Device Options Setup for information on selecting the device resolution option 1 CT Ratio CT primary current CT secondary current 2 The default Voltage scale is 144V 120V 20 You can change it via the Device Data Scale setup see Section 3 1 or via the Device Options setup in PAS 3 The default Current scale is 2 CT secondary current 2 0A with 1A secondaries 10 A with 5A seconda...

Страница 70: ...ord Status Word bitmap Bit 0 1 The last record of the file is being read Bit 8 1 File is empty Bit 9 1 Reading after EOF Bit 10 1 Corrupted record CRC error Bit 11 1 No file section found for the requested channel Bit 12 1 Reading after the end of a data block Bit 13 1 File is not accessible Bit 14 1 Record not found F5 Bit 15 1 Generic read error with one of the bits 8 14 TOU Profile Log Channel ...

Страница 71: ...ut 5 OFF 0x8605 Status input 6 OFF 0x8606 Status input 7 OFF 0x8607 Status input 8 OFF 0x8608 Status input 9 OFF 0x8609 Status input 10 OFF 0x860A Status input 11 OFF 0x860B Status input 12 OFF Relays 0x0800 Relay 1 ON 0x0801 Relay 2 ON 0x0802 Relay 3 ON 0x0803 Relay 4 ON 0x8800 Relay 1 OFF 0x8801 Relay 2 OFF 0x8802 Relay 3 OFF 0x8803 Relay 4 OFF Phase Reversal 2 0x8901 Positive phase rotation rev...

Страница 72: ...dow kW import demand E 0x160B High sliding window kVA demand E 0x160F High accumulated kW import demand E 0x1611 High accumulated kVA demand E 0x1612 High predicted kW import demand E 0x1614 High predicted kVA demand E Time and Date Parameters 0x0B02 Day of week 0x0B03 Year 0x0B04 Month 0x0B05 Day of month 0x0B06 Hour 0x0B07 Minutes 0x0B08 Seconds 0x0B09 Minute interval 1 2 3 4 5 10 15 20 30 60 mi...

Страница 73: ...01 In Current 0x1002 Frequency 1 Sec Phase Values 0x1100 V1 V12 Voltage 0x1101 V2 V23 Voltage 0x1102 V3 V31 Voltage 0x1103 I1 Current 0x1104 I2 Current 0x1105 I3 Current 0x111E V12 Voltage 0x111F V23 Voltage 0x1120 V31 Voltage 1 Sec Total Values 0x1400 Total kW 0x1401 Total kvar 0x1402 Total kVA 0x1403 Total PF 0x1404 Total PF Lag 0x1405 Total PF Lead 1 Sec Auxiliary Values 0x1501 In Current 0x150...

Страница 74: ...0 0xF10F Setpoint cleared low byte setpoint ID 0xF200 Setup Data cleared 0xF300 Setup reset set by default 0xF400 Setup changed F20 0xF500 RTC set Data Point ID Data Locations 0x03 Data memory 0x04 Factory setup 0x05 Access Password setup 0x06 Basic setup 0x07 Communications setup 0x08 Real time clock 4 0x09 Digital inputs setup 0x0A Pulse counters setup 0x0B AO setup 0x0E Timers setup 0x10 Event ...

Страница 75: ...t Analog Input Without Flag 2 16 bit Analog Input F24 3 16 bit Analog Input Without Flag DNP Class 0 Objects 0x1E01 Analog Input 30 01 0x1E02 Analog Input 30 02 0x1E03 Analog Input 30 03 0x1E04 Analog Input 30 04 0x1F01 Frozen Analog Input 31 01 0x1F02 Frozen Analog Input 31 02 0x1F03 Frozen Analog Input 31 03 0x1F04 Frozen Analog Input 31 04 0x1F05 Frozen Analog Input 31 05 0x1F06 Frozen Analog I...

Страница 76: ... as in the case of single ended analog output 0 1 mA For signed values such as powers and signed power factor the scale is always symmetrical with regard to 0 mA and the full scale corresponds to 1 mA output for positive readings and to 1 mA output for negative readings The zero scale 0 mA output is permanently set in the instrument to zero for all parameters except the signed power factor for whi...

Отзывы: