50
3.7 Device Setup Registers
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
Device Identification
46080-46111
+0,1
Device serial number
0-999999
UINT32
R
+2,3
Device model ID
13010=PM130P,
13011=PM130A,
13020=PM130E,
13030-13032=PM130EH
UINT32
R
+4-11
Device model name
“PM130P”, “PM130E”,“PM130EH”
CHAR16
R
Null-terminated string
+12-13
Device options (bitmap)
0
UINT32
R
+14-19 Reserved
UINT16
R
+20
Device firmware version number
1101-1199
UINT16
R
Two higher decimal digits = major
version number, two lower decimal
digits = minor version number
+21
Device firmware build number
1-99
UINT16
R
+22,23 Reserved
UINT16
R
+24
Boot loader version number
0101-0199
UINT16
R
Two higher decimal digits = major
version number, two lower decimal
digits = minor version number
+25
Boot loader build number
1-99
UINT16
R
+26-31 Reserved
UINT16
R
Factory Device Settings
46112-46178
+0
V1-V3 input range
690, 120 (option U)
V
UINT16
R
Does not limit the 690V input range
+1
V1-V3 input overload
120
%
UINT16
R
+2,3 Reserved
UINT16
R
+4
I1-I3 input range
1, 5
A
UINT16
R
+5
I1-I3 input overload
200
%
UINT16
R
+6-13 Reserved
UINT16
R
+14-63 Unused
UINT16
+64
Ethernet MAC address 0-1
0x0500
UINT16
R
+65
Ethernet MAC address 2-3
0x00F0
UINT16
R
+66
Ethernet MAC address 4-5
0x0000-0xFFFF
UINT16
R
Basic Setup
2304-2324
+0 Wiring
mode
F26
UINT16
R/W
+1
PT ratio
10 to 65000
×
0.1
UINT16 R/W
+2
CT primary current
1 to 50,000
A
UINT16
R/W
+3
Power block demand period
E
1,2,3,5,10,15,20,30,60 min,
255 = external synchronization
min
UINT16
R/W
If the external synchronization is
selected, the DI1 input is
considered a pulse or KYZ input.
Provided
by
Northeast
Power
Systems,
Inc.
www.nepsi.com