Measurement Specifications
Accuracy, %
Range
Display Resolution (%Rdg)
d
Parameter
Full Scale
Rdg FS Conditions
@
range
Voltage
120V
×
PT
@ 120V
380V
×
PT
@ 660V
208V
×
PT
@ 120V
660V
×
PT
@ 660V
0.25 10% to 120% FS 0 to 999,000 V
1 V @ 1V to 9,999 V
≤
0.1% @ 10,000 V to 999,000 V
Starting voltage 1.5% FS
Line current
CT PRIMARY CURRENT
0.25 2% to 120% FS
0 to 60,000 A
1 A @ 1A to 9,999 A
≤
0.1% @ 10,000 A to 60,000 A
Starting current 0.5% FS
Active power
0.36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
0.5
|PF|
≥
0.5
c
-2,000,000 to
+2,000,000 kW
1 kW @ 1kW to 9,999 kW
≤
0.1% @ 10 MW to 2,000 MW
Reactive power
0.36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
0.5
|PF|
≤
0.9
c
-2,000,000 to
+2,000,000 kvar
1 kvar @ 1kvar to 9,999 kvar
≤
0.1% @ 10 Mvar to 2,000 Mvar
Apparent power
0.36
×
PT
×
CT @ 120V input
1.2
×
PT
×
CT @ 690V input
0.5
|PF|
≥
0.5
c
0 to
2,000,000 kVA
1 kVA @ 1kVA to 9,999 kVA
≤
0.1% @ 10 MVA to 2,000 MVA
Power factor
1
1
|PF|
≥
0.5
-0.999 to +1.000
0.001
Frequency
0.1
45.00 to 65.00 Hz
0.01 Hz
For Ln reading
and for
3OP2/3OP3
wiring
modes
For LL reading
except
3OP2/3OP3
wiring modes
or
or