19
5. Press
SELECT
to activate the middle window; use
▲
▼
to
choose the parameter; press
ENTER
.
6. Press
SELECT
to activate the lower window; use
▲
▼
to
choose the value; press
ENTER
(or press
ESC
to leave value
unchanged).
Menus
Code
Full Name
Code Full Name
bASc
Basic -
see Section 5.1
PulS
Pulsing Relay *
Port
Communications Port -
see Section 4.2
SetP
rtc
Alarm Setpoints *
Real time Clock*
dinP
Digital (Status) Inputs *
disp
Display*
Aout
Analog Output *
rSt
Reset enable/disable *
AEPn
Analog Expander *
AccS
Password enable/disable *
* For full setup instructions for these parameters, see the complete
RPT091 Installation and Operation Manual
.
5.1 Basic Setup Parameters
Options /
Code Parameter Value Range Description
ConF
Wiring Mode
3OP2
3-wire open delta using 2 CTs (2
element)
Default =
3OP3
4Ln3
3dir2
4LL3
3Ln3
3LL3
3-wire open delta using 3 CTs (2½
element)
4-wire Wye using 3 PTs (3 element),
line to neutral voltage readings
3-wire direct connection using 2 CTs
(2 element)
4-wire Wye using 3 PTs (3 element),
line to line voltage readings
4-wire Wye using 2 PTs (2 ½
element), line to neutral voltage
readings
4-wire Wye using 2 PTs (2 ½
element), line to line voltage readings
Pt
PT Ratio
1.0 to
6500.0
The phase potential transformer ratio.
If direct connection, set PT to 1;
otherwise, PT= primary voltage/
secondary voltage
Default = 1