Satec RPT091 Скачать руководство пользователя страница 3

 

9.  

DO NOT attempt to open the instrument under any 
circumstances. 

10.  

Although designed to operate in an electrically noisy 
environment, 

the instrument should not be placed near very high 

electric fields. In the event that the instrument is mounted in a 
harsh, noisy environment with high potential for electromagnetic 
impulses from heavy switch gears, motors or lightning, it is 
recommended to install appropriate protective devices such as 
lightening and over-voltage arresters to all incoming voltage inputs. 

 

LIMITED WARRANTY

 

The manufacturer offers the customer a 24-month functional warranty on 
the instrument for faulty workmanship or parts from date of dispatch from 
the distributor. In all cases, this warranty is valid for 36 months from the 
date of production. This warranty is on a return to factory basis. 
The manufacturer does not accept liability for any damage caused by 
instrument malfunction. The manufacturer accepts no responsibility for 
the suitability of the instrument to the application for which it was 
purchased. 
Failure to install, setup or operate the instrument according to the 
instructions herein will void the warranty. 
Your instrument may be opened only by a duly authorized representative 
of the manufacturer. The unit should only be opened in a fully anti-static 
environment. Failure to do so may damage the electronic components 
and will void the warranty. 

NOTE 

The greatest care has been taken to manufacture and calibrate your 
instrument. However, these instructions do not cover all possible 
contingencies that may arise during installation, operation or 
maintenance, and not all details and variations of this equipment are 
covered by these instructions.   
For additional information regarding installation, operation or 
maintenance of this instrument, contact the manufacturer or your local 
representative or distributor. 

 

 

 

BG0227  Rev. A2

 

Содержание RPT091

Страница 1: ...RPT091 Remote Power Transducer QUICK GUIDE BG0227 Rev A2...

Страница 2: ...r supply voltage input voltages currents analog output and communication protocol for your application Also check the correctness of other ordering options 3 Under no circumstances should the instrume...

Страница 3: ...does not accept liability for any damage caused by instrument malfunction The manufacturer accepts no responsibility for the suitability of the instrument to the application for which it was purchased...

Страница 4: ...________________8 3 5 Relays ______________________________________12 3 6 Status Inputs_________________________________13 3 7 Analog Output _______________________________13 4 RDM Display ___________...

Страница 5: ...Frequency Demand Ampere Demand per phase Max Amp Demand per phase Accumulated kW Demand Accumulated kVA Demand kW Demand KVA Demand kW Sliding Demand KVA Sliding Demand kW Maximum Sliding Demand KVA M...

Страница 6: ...nt for physical damage incurred in transit If the instrument is damaged inform your local distributor immediately Figure 2 1 RDM Cut out Dimensions Figure 2 2 RDM Panel Mounting STEP 1 Insert RDM into...

Страница 7: ...RPT to brackets tighten nuts STEP 7 Connect RDM to RPT via the 15 pin connectors using cable supplied STEP 1 Insert RDM into cutout STEP 2 Mount brackets on studs STEP 3 Fasten brackets do not tighte...

Страница 8: ...minal 12 negative to terminal 10 Figure 3 1 Locations of Terminals Front View NOTE Power source connection requires use of the suppression core provided with the instrument IMPORTANT It is recommended...

Страница 9: ...5 5 8 8 2 2 11 5 11 and 8 11 should not exceed 144V AC RMS and 225V amplitude 120V input usually implies use of a potential transformer PT The PT requires use of any of the four wiring configurations...

Страница 10: ...ages LOAD Figure 3 2 Three Wire Direct Connection Using 2 CTs 2 element Wiring Mode 3dir2 LINE LINE LINE I I I K K K L L L 1 A 2 B 3 C Shorting Switches 11 9 7 6 4 3 1 12 10 8 5 2 V1 V2 VN V3 1 2 3 Cu...

Страница 11: ...witches 10 8 5 2 V V V I I I V Currents Voltages LOAD Figure 3 4 Four Wire Wye Connection Using 3 PTs 3 CTs 3 element Wiring Mode 4LL3 or 4Ln3 LINE LINE K I I I K L L c98 10011 1 A 2 B 3 C Shorting Sw...

Страница 12: ...ur Wire Wye Connection Using 2 PTs 3 CTs 2 element Wiring Mode 3LL3 or 3Ln3 Note Use this configuration only if voltages are balanced LINE LINE K K K L L L 1 A 2 B 3 C Shorting Switches 11 9 7 6 4 3 1...

Страница 13: ...2 L L1 A 2 L B 1 L K K K L L LOAD L c98 10008 1 A 2 B 3 C Shorting Switches 11 9 7 6 4 3 1 12 10 8 5 2 V 1 V 2 V I I I N V3 1 2 3 Currents Voltages Figure 3 8 Four Wire Delta Direct Connection Using 3...

Страница 14: ...g output after an input change takes up to 250 ms for real time data and 1 to 6 sec for average data depending on how the buffer is defined in the setup see Section 5 1 Basic Setup One or two AX 7 ana...

Страница 15: ...lit up this means that the RDM is displaying the common measurements parameters Maximum demands press MAX DEMAND key Harmonic press THD TDD key RPT091H only Energy press ENERGY key Only the RPT091H p...

Страница 16: ...Hz Frequency 4 Hz 4 3 kvar Total kvar 4 kvar Mvar 5 1 Ph L1 Label 5 2 PF Power factor L1 4 5 3 kW kW L1 4 kW MW 6 1 kVA kVA L1 4 kVA MVA 6 2 Ph L1 Label 6 3 kvar kvar L1 4 kvar Mvar 7 1 Ph L2 Label 7...

Страница 17: ...Current THD L2 4 2 3 A3 Current THD L3 4 TDD 3 1 A1 Current TDD L1 4 3 2 A2 Current TDD L2 4 3 3 A3 Current TDD L3 4 Total Energies 1 1 MWh Ac En Label 1 2 IP Label 1 3 MWh import 6 MWh 2 1 Mvarh rE E...

Страница 18: ...L3 6 Mvarh 14 1 MVAh AP En Label 14 2 L3 Label 14 3 MVAh L3 6 MVAh c Display readings for all electrical quantities are sliding average values d Voltage and current readings with a decimal point are d...

Страница 19: ...iting setup 3 Press ENTER If a password is required use to input the first digit and press SELECT to advance to next digit After all 4 digits are input press ENTER 4 Press SELECT to choose the menu pr...

Страница 20: ...parameters see the complete RPT091 Installation and Operation Manual 5 1 Basic Setup Parameters Options Code Parameter Value Range Description ConF Wiring Mode 3OP2 3 wire open delta using 2 CTs 2 ele...

Страница 21: ...fault 900 sec buF Averaging Buffer Size 8 16 32 The number of measurements for RMS sliding averaging Default 8 rSt RESET enable disabl e diS En Protects all reset functions either via the RDM or commu...

Страница 22: ...owermeter address 1 99 ASCII 1 247 Modbus 255 DNP 3 0 SPA Default 1 bAud Baud Rate 110 300 110 baud 300 baud 600 1200 600 baud 1200 baud 2400 4800 2400 baud 4800 baud 9600 19 2 9600 baud Default 19200...

Страница 23: ...ndicator flashes when the instrument sends out data The RXD indicator flashes when the instrument receives data Figures 6 3 through 6 6 illustrate all RS 422 and RS 485 cable configurations and wiring...

Страница 24: ...Tx Tx Tx Rx Rx Rx Rx Rx Rx 2 2 15 16 17 14 4 5 3 Shield c98 10007 21 Shield Shield POWERMETERS IBM PC COMPATIBLE RS 422 RS 485 R1 R2 R1 R2 200 500 Ohm RxD RTS RxD RTS TxD CTS TxD CTS OR RS 232 RS 422...

Страница 25: ...e voltages not connected Check voltage inputs connections One or more phase currents not displayed Incorrect current inputs connections Check current inputs connections Phase active powers or power fa...

Страница 26: ...a relay output with zero number of unit hours per pulse 2 You selected an output parameter already assigned to another relay output 1 Check that no unit hours is within allowed range 1 9999 2 Check t...

Страница 27: ...ud rate Protocol name ASCII or non ASCII PC COMPORT RXD LED does not flash Communication cable not connected properly Check cable Instrument does not respond more than 1 of sessions in the ASCII or no...

Страница 28: ...ge and Current Input terminals UL recognized Maximum wire section 4 mm2 10 AWG Optically Isolated Communication Port EIA RS 422 and RS 485 standards Maximum wire section 2 5 mm2 12 AWG 2 Relay Outputs...

Страница 29: ...mm 4 5x4 5x 787 Mounting wall mount Display weight 0 2 kg 0 44 lb Standards Compliance Standards UL File E129258 CE EMC 89 336 EEC as amended by 92 31 EEC and 93 68 EEC CE SAFETY 72 23 EEC as amended...

Страница 30: ...ive power 0 36 PT CT 120V input 1 2 PT CT 690V input 0 5 PF 0 5 c 2 000 000 to 2 000 000 kW 1 kW 1kW to 9 999 kW 0 1 10 MW to 2 000 MW Reactive power 0 36 PT CT 120V input 1 2 PT CT 690V input 0 5 PF...

Страница 31: ...0 to 999 9 0 1 via communication Total harmonic distortion THD U I U1 I1 100 1 5 1 FS U I 10 FSU FSI 0 to 100 0 1 Total Demand harmonic distortion TDD I 100 1 5 1 FS I 10 FSI 0 to 100 0 1 Active energ...

Страница 32: ...ntal I1 current fundamental c 10 to 120 of voltage FS and 2 to 120 of current FS d Higher resolution is achievable via communications e Where the current is 10 FS the energy accuracy is better than 1...

Отзывы: