25
Trigger parameter
Trigger
Type
Unit
Limit/scale
1
Con-
ID
Low
High
version
Negative phase rotation reversal
2
0x8902
UINT16
N/A N/A NONE
High/low real-time values on any phase
High voltage
4
0x0E00
UINT16 V
0
Vmax LIN3
Low voltage
4
0x8D00
UINT16 V
0
Vmax LIN3
High current
0x0E01
UINT16 A
0
Imax LIN3
Low current
0x8D01
UINT16 A
0
Imax
LIN3
High voltage THD
5
0x0E07
UINT16
0.1%
0
999.9
LIN3
High current THD
0x0E08
UINT16 0.1%
0
999.9
LIN3
High K-Factor
0x0E09
UINT16 0.1
1.0
999.9
LIN3
High current TDD
0x0E0A
UINT16 0.1%
0
100.0
LIN3
High/low real-time auxiliary values
High frequency
0x1002
UINT16 0.01Hz
0
100.00
3
LIN3
Low frequency
0x9002
UINT16 0.01Hz
0
100.00
3
LIN3
High/low average values per phase
High current L1
0x1103
UINT16 A
0
Imax LIN3
High current L2
0x1104
UINT16 A
0
Imax LIN3
High current L3
0x1105
UINT16 A
0
Imax LIN3
Low current L1
0x9103
UINT16 A
0
Imax LIN3
Low current L2
0x9104
UINT16 A
0
Imax LIN3
Low current L3
0x9105
UINT16 A
0
Imax LIN3
High/low average values on any phase
High voltage
4
0x1300
UINT16 V
0
Vmax LIN3
Low voltage
4
0x9200
UINT16 V
0
Vmax LIN3
High current
0x0301
UINT16 A
0
Vmax LIN3
Low current
0x8201
UINT16 A
0
Vmax LIN3
High/low average total values
High total kW import
0x1406
UINT16 kW
-Pmax Pmax LIN3
High total kW export
0x1407
UINT16 kW
-Pmax Pmax LIN3
High total kvar import
0x1408
UINT16 kvar
-Pmax Pmax LIN3
High total kvar export
0x1409
UINT16 kvar
-Pmax Pmax LIN3
High total kVA
0x1402
UINT16 kVA
0
Pmax LIN3
Low total PF Lag
0x9404
UINT16 0.001
0
1.000 LIN3
Low total PF Lead
0x9405
UINT16 0.001
0
1.000 LIN3
High/low average auxiliary values
High neutral current
0x1501
UINT16 A
0
Imax LIN3
High frequency
0x1502
UINT16 0.01Hz
0
100.00
3
LIN3
Low frequency
0x9502
UINT16 0.01Hz
0
100.00
3
LIN3
High present demands
High volt demand L1/L12
4
0x1600
UINT16 V
0
Vmax LIN3
High volt demand L2/L23
4
0x1601
UINT16 V
0
Vmax LIN3
High volt demand L3/L31
4
0x1602
UINT16 V
0
Vmax LIN3
High ampere demand L1
0x1603
UINT16 A
0
Imax LIN3
High ampere demand L2
0x1604
UINT16 A
0
Imax LIN3
High ampere demand L3
0x1605
UINT16 A
0
Imax LIN3
High block kW demand
0x1606
UINT16 kW
0
Pmax LIN3
High block kVA demand
0x1608
UINT16 kVA
0
Pmax LIN3
High sliding window kW
demand
0x1609
UINT16 kW
0
Pmax LIN3
High sliding window kVA
demand
0x160B
UINT16 kVA
0
Pmax LIN3
High accumulated kW demand
0x160F
UINT16 kW
0
Pmax LIN3
High accumulated kVA demand
0x1611
UINT16 kVA
0
Pmax LIN3
High predicted kW demand
0x1612
UINT16 kW
0
Pmax LIN3
High predicted kVA demand
0x1614
UINT16 kVA
0
Pmax LIN3
1
For parameter limits, see Note
1
to Table 5-1
2
The setpoint is operated when the actual phase sequence does not match the indicated phase rotation