![Satec PM130EH SERIES Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/satec/pm130eh-series/pm130eh-series_reference-manual_1200371017.webp)
17
5.6 Instrument Status
Table 5-6 Instrument Status Registers
Parameter
Address
Type
R/W
Range
Instrument reset register
1
2560
UINT16
R/W
0 (when read)
65535 (when written) = reset the
instrument
Reserved
2561
UINT16
R
Read as 0
Relay status
2562
UINT16
R
see Table 5-7
Reserved
2563
UINT16
R
Read as 0
Reserved 2564
UINT16
R
Firmware version number
2565
UINT16
R
0-65535
Instrument options 1
2566
UINT16
R
See Table 5-8
Instrument options 2
2567
UINT16
R
See Table 5-8
1
Writing a value of 65535 into register 2560 will cause the instrument to perform a warm restart.
Table 5-7 Relay Status
Bit number
Description
0-6
Not used (permanently set to 1)
7 Relay
status
8-15
Not used (permanently set to 0)
Bit meaning: 0 = relay operated, 1 = relay released
Table 5-8 Instrument Options
Options register
Bit
Description
Options1 0
120V
option
1
690V
option
2-4
Reserved
5
150% current over-range
6-8
Reserved
9
Relays
option
10-15
Reserved
Options 2
0-2
Number of relays - 1
3-15
Reserved
5.7 Extended Status
Table 5-9 Extended Status Registers
Register description
Address
Type
R/W Value range
Relay status
3452
UINT16
R
See Table 5-10
Reserved
3453-
UINT16
R
Read as 0
3454
UINT16
Setpoints status
3455
UINT16
R
See Table 5-11
Log status
3456
UINT16
R
See Table 5-12
Reserved
3457-3473
UINT16
R
Read as 0
Setpoint alarm status
3474
UINT16
R/W
See Table 5-13
Self-check alarm status
3475
UINT16
R/W
See Table 5-14
Table 5-10 Relay Status
Bit
Description
0 Relay
status
1-15
Not used (permanently set to 0)
Bit meaning: 0 = relay released, 1 = relay operated