Satec PM130EH SERIES Скачать руководство пользователя страница 23

23 

Parameter 

16-bit Register

32-bit 

Point 

R/W

Unit 

Range/Scale 

1

 

 

Reg. 

Cnv.

Register 

ID 

 

 

Low 

High 

Fundamental's (H01) real-time total values 

Total fundamental kW 

8336 

LIN3  17152-17153 

0x2A00  R 

kW 

-Pmax 

Pmax 

Total fundamental kvar 

8337 

LIN3  17154-17155 

0x2A01  R 

kvar 

-Pmax 

Pmax 

Total fundamental kVA 

8338 

LIN3  17156-17157 

0x2A02  R 

kVA 

Pmax 

Total fundamental PF 

8339 

LIN3 17158-17159  0x2A03 R 

0.001 

-1.000  1.000 

Minimum real-time values per phase (M) 

Voltage L1/L12 

5

 8416 

LIN3 

17408-17409 

0x2C00 

Vmax 

Voltage L2/L23 

5

 8417 

LIN3 

17410-17411 

0x2C01 

Vmax 

Voltage L3/L31 

5

 8418 

LIN3 

17412-17413 

0x2C02 

Vmax 

Current L1  

8419 

LIN3  17414-17415 

0x2C03  R 

Imax 

Current L2  

8420 

LIN3  17416-17417 

0x2C04  R 

Imax 

Current L3  

8421 

LIN3  17418-17419 

0x2C05  R 

Imax 

Minimum real-time total values (M)  

Total kW 

8456 

LIN3  17536-17537 

0x2D00  R 

kW 

-Pmax 

Pmax 

Total kvar 

8457 

LIN3  17538-17539 

0x2D01  R 

kvar 

-Pmax 

Pmax 

Total kVA 

8458 

LIN3  17540-17541 

0x2D02  R 

kVA 

Pmax 

Total PF 

3

 8459 

LIN3 

17542-17543 

0x2D03 

0.001 

1.000 

Minimum real-time auxiliary values (M) 

Reserved 8496 

 

17664-17665 

0x2E00 

 

Neutral current  

8497 

LIN3  17666-17667 

0x2E01  R 

Imax 

Frequency   

8498 

LIN3  17668-17669 

0x2E02  R 

0.01Hz 

100.00 

2

Maximum real-time values per phase (M) 

Voltage L1/L12 

5

 8736 

LIN3 

18432-18433 

0x3400 

Vmax 

Voltage L2/L23 

5

 8737 

LIN3 

18434-18435 

0x3401 

Vmax 

Voltage L3/L31 

5

 8738 

LIN3 

18436-18437 

0x3402 

Vmax 

Current L1  

8739 

LIN3  18438-18439 

0x3403  R 

Imax 

Current L2  

8740 

LIN3  18440-18441 

0x3404  R 

Imax 

Current L3  

8741 

LIN3  18442-18443 

0x3405  R 

Imax 

Maximum real-time total values (M)  

Total kW 

8776 

LIN3  18560-18561 

0x3500  R 

kW 

-Pmax 

Pmax 

Total kvar 

8777 

LIN3  18562-18563 

0x3501  R 

kvar 

-Pmax 

Pmax 

Total kVA 

8778 

LIN3  18564-18565 

0x3502  R 

kVA 

Pmax 

Total PF 

3

 8779 

LIN3 

18566-18567 

0x3503 

0.001 

1.000 

Maximum real-time auxiliary values (M) 

Reserved 8816 

 

18688-18689 

0x3600 

 

 

Neutral current  

8817 

LIN3  18680-18681 

0x3601  R 

Imax 

Frequency 8818 

LIN3 

18682-18683 

0x3602 

0.01Hz 

100.00 

2

Maximum demands (M) 

Max. volt demand L1/L12 

5

 8856 LIN3 

18816-18817 

0x3700 

R V 

0  Vmax 

Max. volt demand L2/L23 

5

 8857 LIN3 

18818-18819 

0x3701 

R V 

0  Vmax 

Max. volt demand L3/L31 

5

 8858 LIN3 

18820-18821 

0x3702 

R V 

0  Vmax 

Max. ampere demand L1 

8859 

LIN3  18822-18823 

0x3703  R 

Imax 

Max. ampere demand L2 

8860 

LIN3  18824-18825 

0x3704  R 

Imax 

Max. ampere demand L3  

8861 

LIN3  18826-18827 

0x3705  R 

Imax 

Reserved 8862 

 

18828-18829 

0x3706 

 

Reserved 8863 

 

18830-18831 

0x3707 

 

Reserved 8864 

 

18832-18833 

0x3708 

 

Max. sliding window kW demand   8865 

LIN3  18834-18835 

0x3709  R 

kW 

Pmax 

Reserved 8866 

 

18836-18837 

0x370A 

 

Max. sliding  window kVA 

demand  

8867 LIN3 

18838-18839 

0x370B 

R kVA 

0  Pmax 

1

  For the parameter limits, see Note

1

  to Table 5-1 

2

  The actual frequency range is 45.00 - 65.00 Hz 

3

  Absolute min/max value (lag or lead) 

4

  The exported energy registers are read as positive unsigned long (32-bit) integers 

5

  When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, 

they will be line-to-line voltages. 

6

  In the 4LN3, 4LL3, 3LN3, 3LL3 and 3DIR2 wiring modes, the harmonic voltages will represent line-to-neutral 

voltages; in the 3OP2 and 3OP3 wiring modes, they will comprise L12 and L23 line-to-line voltages.  

Содержание PM130EH SERIES

Страница 1: ...SERIES PM130EH POWERMETERS COMMUNICATIONS Modbus Communications Protocol REFERENCE GUIDE ...

Страница 2: ...g a particular installation operation or maintenance of equipment contact the manufacturer or your local representative or distributor This book is copyrighted No part of this book may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopying recording or otherwise without the prior written permission of the manufacturer This revision ...

Страница 3: ... 8 3 6 Exception Responses 9 4 PROTOCOL IMPLEMENTATION 10 4 1 Modbus Register Addresses 10 4 2 Data Formats 10 4 2 1 16 bit Integer Format 10 4 2 2 32 bit Modulo 10000 Format 12 4 2 3 32 bit Long Integer Format 12 4 3 User Assignable Registers 12 5 POWERMETER REGISTERS DESCRIPTION 14 5 1 Basic Data Registers Set 14 5 2 Basic Setup 15 5 3 User Selectable Options Setup 16 5 4 Communications Setup 16...

Страница 4: ...ommunications connections is found in Series PM130EH Powermeters Installation and Operation Manual IMPORTANT In 3 wire connection schemes the unbalanced current and phase readings for power factor active power and reactive power will be zeros because they have no meaning Only the total three phase power values can be used Most of the instrument advanced features are configured using multiple setup...

Страница 5: ...Format T1 T2 T3 Address Function Data CRC Check T1 T2 T3 8 bits 8 bits N 8 bits 16 bits 2 3 Address Field The address field contains a user assigned address 1 247 of the instrument that is to receive a message Address 0 is used in broadcast mode to transmit to all instruments broadcast mode is available only for functions 06 and 16 In this case all instruments receive the message and take action o...

Страница 6: ...nventional LSB or right most bit of each character first In generating the CRC the first bit transmitted is defined as the MSB of the dividend For convenience and since there are no carries used in the arithmetic let s assume while computing the CRC that the MSB is on the right To be consistent the bit order of the generating polynomial must be reversed The MSB of the polynomial is dropped since i...

Страница 7: ...p to 125 contiguous registers from a single data table It can be used instead of function 03 Request Instrument Address Function 04 Starting Address Word Count Error Check 1 byte 1 byte 2 bytes 2 bytes 2 bytes Starting Address Address of the first register to be read Word Count The number of contiguous words to be read Response Instrument Address Function 04 Byte Count Data Word 1 Data Word N Erro...

Страница 8: ...ing Address Word Count Error Check 1 byte 1 byte 2 bytes 1 word 2 bytes 3 5 Function 08 Loop back Communications Test The purpose of this request is to check the communications link between the specified instrument and PC Request Instrument Address Function 08 Diagnostic Code 0 Data Error Check 1 byte 1 byte 2 bytes 2 bytes 2 bytes Diagnostic Code Designates action to be taken in Loop back test Th...

Страница 9: ...o 1 Exception Code Error Check 1 byte 1 byte 1 byte 2 byte Exception response codes 01 Illegal function 02 Illegal data address 03 Illegal data value 06 Busy rejected message The message was received without errors but the instrument is being programmed from the keypad only for requests accessing setup registers NOTE When the character framing parity or redundancy check detects a communication err...

Страница 10: ...sing either the LIN3 linear conversion or decimal pre scaling to pass fractional numbers in integer format Non scaled data The data will be presented exactly as retrieved by the communications program from the instrument The value range for unsigned data is 0 to 65535 for signed data the range is 32768 to 32767 LIN3 Linear Scaling This conversion maps the raw data received by the communications pr...

Страница 11: ...Imax 2 144 120 200 00 1 5 2 1000 10368kW LO Pmax 10368kW If the raw data reading is 5500 then the power reading in engineering units will be as follows Watts reading 5500 10368 10368 9999 10368 1037 9kW If the raw data reading is 500 then the power reading in engineering units will be as follows Watts reading 500 10368 10368 9999 10368 9331 1kW 4 Power Factor readings Power factor engineering scal...

Страница 12: ...13953 1 The 32 bit value is 1 x 65536 3464 69000V 2 Signed 32 bit Values If you read signed kW of 789kW from registers 14336 14337 then the register readings will be 14336 64747 unsigned 14337 65535 unsigned or 1 signed value To take the high order register as a signed value compare it with 32767 If the value is less or equal to 32767 use it as is If it is greater than 32767 then this is a negativ...

Страница 13: ...ress Register contents Type 0 Assigned register 0 INT16 1 Assigned register 1 INT16 2 Assigned register 2 INT16 119 Assigned register 119 INT16 Table 4 2 User Assignable Register Map Address Register contents Type R W Range 120 Mapped address for register 0 UINT16 R W 256 to 65535 121 Mapped address for register 1 UINT16 R W 256 to 65535 122 Mapped address for register 2 UINT16 R W 256 to 65535 23...

Страница 14: ...Accumulated kW demand UINT16 R W kW Pmax Pmax LIN3 282 Maximum sliding window kVA demand 4 UINT16 R W kVA Pmax Pmax LIN3 283 Accumulated kVA demand UINT16 R W kVA Pmax Pmax LIN3 284 Max ampere demand L1 UINT16 R W A 0 Imax LIN3 285 Max ampere demand L2 UINT16 R W A 0 Imax LIN3 286 Max ampere demand L3 UINT16 R W A 0 Imax LIN3 287 kWh import low UINT16 R W kWh 0 9999 NONE 288 kWh import high UINT16...

Страница 15: ...ameter Address Type R W Range Wiring mode 1 2304 UINT16 R W 0 3OP2 1 4LN3 2 3DIR2 3 4LL3 4 3OP3 5 3LN3 6 3LL3 PT ratio 2305 UINT16 R W 10 to 65000 0 1 CT primary current 2306 UINT16 R W 1 to 10000 A Power demand period 2307 UINT16 R W 1 2 5 10 15 20 30 60 min 255 external synchronization 2 Volt ampere demand period 2308 UINT16 R W 0 to 1800 sec Averaging buffer size 2309 UINT16 R W 8 16 32 Reset e...

Страница 16: ...e master s request 5 5 Reset Synchronization Registers Table 5 5 Reset Synchronization Registers Register function Address Type R W Reset value Clear total energy registers 3404 UINT16 W 0 Clear total maximum demand registers 3405 UINT16 W 0 all maximum demands 1 power demands 2 volt ampere demands Reserved 3406 3407 UINT16 Clear event time counters 3408 UINT16 W 0 all counters 1 4 counter 1 4 Cle...

Страница 17: ... Not used permanently set to 0 Bit meaning 0 relay operated 1 relay released Table 5 8 Instrument Options Options register Bit Description Options1 0 120V option 1 690V option 2 4 Reserved 5 150 current over range 6 8 Reserved 9 Relays option 10 15 Reserved Options 2 0 2 Number of relays 1 3 15 Reserved 5 7 Extended Status Table 5 9 Extended Status Registers Register description Address Type R W V...

Страница 18: ...new log flag is reset when the user reads the first log record after the flag has been set Table 5 13 Setpoint Alarm Status Bit Description 0 Alarm 1 1 Alarm 2 2 Alarm 3 3 Alarm 4 4 Alarm 5 5 Alarm 6 6 Alarm 7 7 Alarm 8 8 Alarm 9 9 Alarm 10 10 Alarm 11 11 Alarm 12 12 Alarm 13 13 Alarm 14 14 Alarm 15 15 Alarm 16 Bit meaning 1 setpoint has been operated The setpoint alarm register stores the status ...

Страница 19: ...ese registers into adjacent addresses to access multiple data from different data groups by using a single request Refer to Section 2 9 for information on the user assignable registers Along with the register address the table shows for each data item its point identifier ID This is a one word containing a data group ID in the high byte and the parameter offset in a group in the low byte Point IDs...

Страница 20: ...13699 0x0F01 R kvar Pmax Pmax Total kVA 7258 LIN3 13700 13701 0x0F02 R kVA 0 Pmax Total PF 7259 LIN3 13702 13703 0x0F03 R 0 001 1 000 1 000 Real time auxiliary values Reserved 7296 13824 13825 0x1000 R 0 0 Neutral current 7297 LIN3 13826 13827 0x1001 R A 0 Imax Frequency 7298 LIN3 13828 13829 0x1002 R 0 01Hz 0 100 00 2 Voltage unbalance 7299 LIN3 13830 13831 0x1003 R 1 0 300 Current unbalance 7300...

Страница 21: ...R V 0 Vmax Voltage L31 7368 LIN3 14016 14017 0x1120 R V 0 Vmax Average total values Total kW 7456 LIN3 14336 14337 0x1400 R kW Pmax Pmax Total kvar 7457 LIN3 14338 14339 0x1401 R kvar Pmax Pmax Total kVA 7458 LIN3 14340 14341 0x1402 R kVA 0 Pmax Total PF 7459 LIN3 14342 14343 0x1403 R 0 001 1 000 1 000 Average auxiliary values Reserved 7496 14464 14465 0x1500 R 0 0 Neutral current 7497 LIN3 14466 ...

Страница 22: ...h import L3 7626 7627 14858 14859 0x1805 R kvarh 0 108 1 kVAh total L1 7628 7629 14860 14861 0x1806 R kVAh 0 108 1 kVAh total L2 7630 7631 14862 14863 0x1807 R kVAh 0 108 1 kVAh total L3 7632 7633 14864 14865 0x1808 R kVAh 0 108 1 Fundamental s H01 real time values per phase Voltage L1 L12 6 8296 LIN3 17024 17025 0x2900 R V 0 Vmax Voltage L2 L23 6 8297 LIN3 17026 17027 0x2901 R V 0 Vmax Voltage L3...

Страница 23: ... LIN3 18442 18443 0x3405 R A 0 Imax Maximum real time total values M Total kW 8776 LIN3 18560 18561 0x3500 R kW Pmax Pmax Total kvar 8777 LIN3 18562 18563 0x3501 R kvar Pmax Pmax Total kVA 8778 LIN3 18564 18565 0x3502 R kVA 0 Pmax Total PF 3 8779 LIN3 18566 18567 0x3503 R 0 001 0 1 000 Maximum real time auxiliary values M Reserved 8816 18688 18689 0x3600 R 0 Neutral current 8817 LIN3 18680 18681 0...

Страница 24: ...disable the setpoint write zero into this register When writing the setpoint registers except the event when the setpoint is to be disabled it is recommended to write all the setpoint registers using a single request or disable the setpoint before writing into separate registers Each value being written is checked for compatibility with the other setpoint parameters if the new value does not confo...

Страница 25: ...W Pmax Pmax LIN3 High total kW export 0x1407 UINT16 kW Pmax Pmax LIN3 High total kvar import 0x1408 UINT16 kvar Pmax Pmax LIN3 High total kvar export 0x1409 UINT16 kvar Pmax Pmax LIN3 High total kVA 0x1402 UINT16 kVA 0 Pmax LIN3 Low total PF Lag 0x9404 UINT16 0 001 0 1 000 LIN3 Low total PF Lead 0x9405 UINT16 0 001 0 1 000 LIN3 High low average auxiliary values High neutral current 0x1501 UINT16 A...

Страница 26: ... 0 1 hour resolution while the setpoint is in the operated state Each time counter has a non volatile shadow counter which counts time at 1 second resolution before the corresponding time counter is incremented 5 10 Pulsing Setpoints Table 5 20 Pulsing Registers Setup registers see Table 5 21 2892 2893 Table 5 21 Pulsing Setup Registers Parameter Offset Type R W Range Output parameter ID 0 UINT16 ...

Страница 27: ...able 5 26 Min Max Log Window Registers Parameter Offset Type R W Range Second 0 UINT16 R 0 Minute 1 UINT16 R 0 Hour 2 UINT16 R 0 Day 3 UINT16 R 0 Month 4 UINT16 R 0 Year 5 UINT16 R 0 Parameter value 1 6 UINT16 R See Table 5 15 Reserved 7 UINT16 R 0 1 The Min Max parameter value is read as a 16 bit scaled value using LIN3 conversion For the conversion scales refer to Table 5 15 The time stamp is no...

Отзывы: