Parameter
16-bit Register
32-bit
Point
R/W
Unit
Range/Scale
1
Reg.
Cnv.
Register
ID
Low
High
Fundamental's (H01) real-time total values
Total fundamental kW
8336
LIN3 17152-17153
0x2A00 R
kW
-Pmax
Pmax
Total fundamental kvar
8337
LIN3 17154-17155
0x2A01 R
kvar
-Pmax
Pmax
Total fundamental kVA
8338
LIN3 17156-17157
0x2A02 R
kVA
0
Pmax
Total fundamental PF
8339
LIN3 17158-17159 0x2A03 R
0.001
-1.000 1.000
Minimum real-time values per phase (M)
Voltage L1/L12
5
8416
LIN3
17408-17409
0x2C00
R
V
0
Vmax
Voltage L2/L23
5
8417
LIN3
17410-17411
0x2C01
R
V
0
Vmax
Voltage L3/L31
5
8418
LIN3
17412-17413
0x2C02
R
V
0
Vmax
Current L1
8419
LIN3 17414-17415
0x2C03 R
A
0
Imax
Current L2
8420
LIN3 17416-17417
0x2C04 R
A
0
Imax
Current L3
8421
LIN3 17418-17419
0x2C05 R
A
0
Imax
Minimum real-time total values (M)
Total kW
8456
LIN3 17536-17537
0x2D00 R
kW
-Pmax
Pmax
Total kvar
8457
LIN3 17538-17539
0x2D01 R
kvar
-Pmax
Pmax
Total kVA
8458
LIN3 17540-17541
0x2D02 R
kVA
0
Pmax
Total PF
3
8459
LIN3
17542-17543
0x2D03
R
0.001
0
1.000
Minimum real-time auxiliary values (M)
Reserved 8496
17664-17665
0x2E00
R
0
0
Neutral current
8497
LIN3 17666-17667
0x2E01 R
A
0
Imax
Frequency
8498
LIN3 17668-17669
0x2E02 R
0.01Hz
0
100.00
2
Maximum real-time values per phase (M)
Voltage L1/L12
5
8736
LIN3
18432-18433
0x3400
R
V
0
Vmax
Voltage L2/L23
5
8737
LIN3
18434-18435
0x3401
R
V
0
Vmax
Voltage L3/L31
5
8738
LIN3
18436-18437
0x3402
R
V
0
Vmax
Current L1
8739
LIN3 18438-18439
0x3403 R
A
0
Imax
Current L2
8740
LIN3 18440-18441
0x3404 R
A
0
Imax
Current L3
8741
LIN3 18442-18443
0x3405 R
A
0
Imax
Maximum real-time total values (M)
Total kW
8776
LIN3 18560-18561
0x3500 R
kW
-Pmax
Pmax
Total kvar
8777
LIN3 18562-18563
0x3501 R
kvar
-Pmax
Pmax
Total kVA
8778
LIN3 18564-18565
0x3502 R
kVA
0
Pmax
Total PF
3
8779
LIN3
18566-18567
0x3503
R
0.001
0
1.000
Maximum real-time auxiliary values (M)
Reserved 8816
18688-18689
0x3600
R
0
Neutral current
8817
LIN3 18680-18681
0x3601 R
A
0
Imax
Frequency 8818
LIN3
18682-18683
0x3602
R
0.01Hz
0
100.00
2
Maximum demands (M)
Max. volt demand L1/L12
5
8856 LIN3
18816-18817
0x3700
R V
0 Vmax
Max. volt demand L2/L23
5
8857 LIN3
18818-18819
0x3701
R V
0 Vmax
Max. volt demand L3/L31
5
8858 LIN3
18820-18821
0x3702
R V
0 Vmax
Max. ampere demand L1
8859
LIN3 18822-18823
0x3703 R
A
0
Imax
Max. ampere demand L2
8860
LIN3 18824-18825
0x3704 R
A
0
Imax
Max. ampere demand L3
8861
LIN3 18826-18827
0x3705 R
A
0
Imax
Reserved 8862
18828-18829
0x3706
R
0
0
Reserved 8863
18830-18831
0x3707
R
0
0
Reserved 8864
18832-18833
0x3708
R
0
0
Max. sliding window kW demand 8865
LIN3 18834-18835
0x3709 R
kW
0
Pmax
Reserved 8866
18836-18837
0x370A
R
0
0
Max. sliding window kVA
demand
8867 LIN3
18838-18839
0x370B
R kVA
0 Pmax
1
For the parameter limits, see Note
1
to Table 5-1
2
The actual frequency range is 45.00 - 65.00 Hz
3
Absolute min/max value (lag or lead)
4
The exported energy registers are read as positive unsigned long (32-bit) integers
5
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode,
they will be line-to-line voltages.
6
In the 4LN3, 4LL3, 3LN3, 3LL3 and 3DIR2 wiring modes, the harmonic voltages will represent line-to-neutral
voltages; in the 3OP2 and 3OP3 wiring modes, they will comprise L12 and L23 line-to-line voltages.