19
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
+0
Exchange number
0-249
UINT16
R/W
Write an exchange number before
reading the setup registers
+1 Reserved
+2,3
Start device register address
0-65535
UINT32
R/W
+4,5
Exchange block size, registers
1-114
UINT32
R/W
+6 Device
ID
1-247
UINT16
R/W
+7
Polling enabled
1=enabled, 0=disabled
UINT16
R/W
+8
RTC update enabled (optional)
1=enabled, 0=disabled
UINT16
R/W
+9-15 Reserved
46944-46959
Status Event Exchange Setup
+0
Exchange number
0-249
UINT16
R/W
Write an exchange number before
reading the setup registers
+1 Reserved
UINT16
+2,3
Device status register address
0-65535
UINT32
R/W
+4,5 Event
mask
0x00000000–0x0000FFFF
UINT32
R/W
Lower 16 bits are used
+6 Device
ID
1-247
UINT16
R/W
+7
Polling enabled
1=enabled, 0=disabled
UINT16
R/W
+8
Options flags (bitmap)
Bit 0 – auto reset:
0=disabled
1=enabled
Bit 1 – register type:
0=holding register (request 3)
1=coils (request 1)
UINT16
R/W
+9-15 Reserved
46960-46975
Write Data Exchange Setup
+0
Exchange number
0-249
UINT16
R/W
Write an exchange number before
reading the setup registers
+1 Reserved
UINT16
+2,3
Start device register address
0-65535
UINT32
R/W
+4,5
Exchange block size, registers
1-12
UINT32
R/W
+6 Device
ID
1-247
UINT16
R/W
+7
Write enabled
1=enabled, 0=disabled
UINT16
R/W
+8-15 Reserved
46976-46991
Data Server Options
+0 Polling
interval
1-1000
min
UINT16
R/W
1 min default
+1
Logging interval, polls
0-1000, 0=logging disabled
UINT16
R/W
1 - default
+2
Data Server Enabled
1=enabled, 0=disabled
UINT16
R/W
0- default
+3
Continuous polling
1=enabled, 0=disabled
UINT16
R/W
0- default
+4-15 Reserved
Gateway Setup
46992-46999
+0
ETC2002 device address
1-247
UINT16
R/W
99 default
+1
Gateway device address range start
1-247
UINT16
R/W
1 default
+2
Gateway device address range end
1-247
UINT16
R/W
247- default