28
Resetting the Hour Counter
To reset the hour counter (parameter d4), proceed as follows:
•
press the PRG button for 5 seconds, until the code P0 is displayed, indicating the first modifiable parameter;
using the
Ç
Ç
Ç
Ç
Ç
and
È
È
È
È
È
buttons, scroll the parameters until d4 is displayed;
•
press the SEL button to display the value of the hour counter (preceded for 1 second by the unit of measure);
•
press the
Ç
Ç
Ç
Ç
Ç
and
È
È
È
È
È
buttons together for 5 seconds until the value is set to zero, preceded by a brief flash.
Alarms
In the event of an alarm, the alarm LED (9) will flash, the alarm relay will close, and the alarm code will flash in the
display. Multiple alarms will flash in sequence, alternating with the main display. Pressing the PRG button will
reset the alarms, although still active alarms will continue to display.
Controller Action
H
Humivisor Causes
Solution
H
Reset
display
Alarm
relay
Reset
relay
EH
E102
Over-current at the
electrodes; probable
electrode malfunction
or water conductivity
temporarily too high
(especially when
starting after a short
stop)
1. Check the operation of the
drain valve
2. Check for fill valve leakage
3. Drain part of the water and
re-start
Shut-
down
N/A Active N/A
EL
E103
Power not available;
no steam production
when on
1. With the machine off and
disconnected from the main
power, check the internal
electrical connections
Shut-
down
N/A Active N/A
EC
E105
High supply water
conductivity
1. Check limit set for b6
2. Turn the machine off and
clean the water conductivity
probes
3. If the problem persists,
change the source of supply
water or install a suitable
treatment system
(demineralization, even
partial).
Note: the problem will not be
resolved by softening the
supply water.
Shut-
down
N/A Active N/A
EP
E113
Excessive reduction in
output
1. Cylinder completely spent
or water with excessive foam.
Perform maintenance on the
cylinder.
Shut-
down
Manual Active Manual