19
.
Time scale option
Parameter options:(12,24)
12: 12 hours display for time clock 24: 24 hours display for time clock
Factory default:24
20
.
Remote sensor option
Parameter options:(0,1,2,3)
0: No remote sensor
1: Outdoor sensor . If an optional outdoor sensor is installed, “INFO” will display in home screen
press “INFO” for inquiry for the outside temperature
2: Outdoor control sensor (See Menu item 21 Heat pump temperature lockout)
3: Indoor sensor. if the thermostat is installed with an indoor remote sensor, display will show the
read temperature from the indoor sensor.
18
.
UV lamp replacement run time option
Parameter options:(UO,UF)
UO: It means starts to counting for 0 day to 400 day UF: It means cancel the function
Factory default:UF
The thermostat will display the “
Chg UV
” when UV time(400 days) has expired.
21
.
Heat pump compressor lockout option
Parameter options:(0
℉
,15
℉
,
20
℉,
25
℉
,
30℉,35℉,40℉
)
0
:
No heat pump compressor lockout
15
℉
,
20
℉,
25
℉
,
30℉,35℉,40℉:heat pump compressor lockout temperature
Factory default:0
This option apply only to HP1, HP2 setting in system type option and only works when
remote sensor option (menu item 20) is set 2.
22
.
Heat pump auxiliary heating temperature lockout option
Parameter options:(0
℉
,40
℉
,
45
℉,
50
℉
,
55℉,60℉
)
0
:
No auxiliary heating temperature lockout
15
℉
,
20
℉,
25
℉
,
30℉,35℉,40℉:heat pump auxiliary heating temperature lockout
Factory default:0
This option apply only to HP1, HP2 setting in system type option and only works when
remote sensor option (menu item 20) is set 2.
37
38
If the option is 1,2,or 3,please choose SAS104NTC-REM
sensor.
Factory default:0