User’s manual

 

 

8

 

IV.

 

How to use the controller

 

IV.1.

 

Principle of operation

 

The regulator controls the fan and the fuel feeder operation so that the pre-set temperature of the CH 
boiler and the water tank is reached. Additionally, it controls CH and DHW pump operation activating 
them once a pre-defined temperature of the CH boiler has been reached.

 

 

IV.2.

 

Stages of operation

 

 

Fire-up

 – this phase is initiated when the flue gas temperature reaches a pre-set value and does not 

drop below this value for 30seconds (default 

fire-up time

). 

 

Operation

 – when the fire-up phase has been completed, the controller enters operation mode and the 

display shows the message ‘PID: OPERATION’. It is the primary mode of controller functioning when the 
blow force and fuel feeding are regulated with PID algorithm, oscillating around the pre-set temperature 
defined by the user. When the temperature increases unexpectedly by more than 5

o

C above the pre-set 

value, the 

supervision mode

 is activated. 

 

Supervision mode

 – this mode is activated automatically when the temperature exceeds the pre-set 

value by more than 5

o

C in operation mode. In such a case, the controller disables PID control and uses 

manual settings (according to parameters defined in the fitter's menu).The display shows the following 
message: ‘

PID: SUPERVISION’

 

 

IV.3.

 

zPID control

 

ST-550zPID is a controller with continuous output signal, using z

PID algorithm

. This type of controller 

calculates the blow force on the basis of CH boiler temperature and the flue gas temperature measured 
at  the  CH  boiler  outlet.  The  fan  operates  continuously  and  the  blow  force  depends  on  the  CH  boiler 
temperature, the flue gas temperature as well as the difference between these parameters and their pre-
set values. One of the greatest advantages of zPID regulators is their ability to maintain a stable pre-set 
temperature without unnecessary overregulation and oscillations. 

 

Apart from zPID control, the controller  operation is adjusted on the basis of the the readings from 

the air flow sensor mounted on the fan. 

 

 

Using this type of regulator with a flue gas sensor helps to reduce fuel costs by up to several percent. 
Moreover, it ensures stable temperature of output water thus prolonging the life of the heat exchanger 
(of  the  CH  boiler).  Flue  gas  temperature  control  results  in  low  emission  of  dust  and  environmentally 
harmful  gases.  Flue  gas  heat  is  not  disposed  of  through  the  chimney,  but  it  is  utilised  for  heating 
purposes

.

 

 

TEST RESULTS - TECH controller with PID control: 

 

 
 

Содержание ST-550 zPID

Страница 1: ......

Страница 2: ...5 c Pre set DHW temperature 12 V 5 d DHW hysteresis 12 V 5 e Temperature of pump activation 12 V 5 f Pre set room temperature 13 V 6 Manual mode 13 V 7 Operation settings 13 V 7 a Feeding time 13 V 7...

Страница 3: ...ion 23 VI 5 b Short circuit pump 23 VI 5 c Floor pump 23 VI 5 d Circulating pump 23 VI 6 Time settings 24 VI 7 Date settings 24 VI 8 Internet module 24 VI 9 Fuel level calibration 27 VI 10 Language 28...

Страница 4: ...istance of the electric motors as well as the insulation resistance of the cables The regulator should not be operated by children WARNING The device may be damaged if struck by a lightning Make sure...

Страница 5: ...certain parameters and control certain functions via the Internet Possibility of controlling two valves via additional modules e g ST 431N Controller equipment CH temperature sensor Feeder temperature...

Страница 6: ...User s manual 6...

Страница 7: ...ST 550 zPID 7...

Страница 8: ...les PID control and uses manual settings according to parameters defined in the fitter s menu The display shows the following message PID SUPERVISION IV 3 zPID control ST 550zPID is a controller with...

Страница 9: ...roller is switched on it enters operation mode and OPERATION appears on the display It is the primary mode of controller operation in which the fan operates continuously and the fuel feeder operation...

Страница 10: ...ed if Hall sensor of the fan is active letter H is displayed feeder if burning without feeder option is active a crossed out feeder icon is displayed CH pump DHW pump additional pump 1 additional pump...

Страница 11: ...set DHW temperature DHW hysteresis Pump activation temperature Pre set room temperature Manual mode Fan Blow force Feeder CH pump DHW pump Additional pump 1 Additional pump 2 Built in valve 1 Built i...

Страница 12: ...set the hysteresis of the pre set temperature It is the difference between the temperature of entering the sustain mode and the temperature of restoring operation mode for example when the pre set te...

Страница 13: ...ion of the CH boiler i e unburnt coal left or failure to reach the pre set temperature of the CH boiler Appropriate pause time ensures efficient operation of the CH boiler V 7 c Blow force This functi...

Страница 14: ...CH boiler which heats the domestic hot water this value also serves as the pre set water tank temperature After this function has been activated the screen displays current CH temperature and two DHW...

Страница 15: ...iler is 600 C on each weekday Monday Friday from 300 AM to 600 AM the pre set temperature will drop by 100 C so it will be 500 C During the weekend from 4 00 PM to 7 00 PM the pre set temperature of t...

Страница 16: ...s the main screen Once the software update has been completed you can remove the memory stick from the USB port The software update of ST 66P module may be conducted in a similar way by inserting the...

Страница 17: ...n time Fan pause time Fan revolutions Buffer parameters Buffer DHW function Pre set bottom buffer temp Pre set top buffer temp Valve settings Additional pump 1 Operation algorithm selection Short circ...

Страница 18: ...eded by 5 C Once the process is completed the controller constantly monitors the CH boiler temperature If it drops by a pre defined vale the fire up process is initiated again NOTE Damping mode concer...

Страница 19: ...the submenus Valve 1 and Valve 2 are intended for controlling such valves In the case of valves 1 and 2 it is necessary to register in order for the valve to operate correctly To register the valve e...

Страница 20: ...g range differs depending on the valve type The pre set temperature value may be adjusted directly from the main screen view by twisting the pulser knob Valve1 Valve 2 Registration Valve status ON OFF...

Страница 21: ...ve for 4 intermediate external temperatures TEMP FOR 20 C TEMP FOR 10 C TEMP FOR 0 C TEMP FOR 10 C Heating curve it is a curve according to which the pre set controller temperature is determined on th...

Страница 22: ...om temperature see Room temperature difference This function is active only with TECH room regulator and it is closely related to the Room temperature difference parameter Room temperature difference...

Страница 23: ...pump remains active until the temperature drops below the pre set value by hysteresis value If other sensor is to serve as CH sensor it must be selected in CH sensor parameter VI 5 c Floor pump If flo...

Страница 24: ...rature values for both the pumps and the mixing valves It also enables the user to fire up the CH boiler activate CH boiler damping procedure or adjust the operating parameters online The installation...

Страница 25: ...ys the main screen with tiles illustrating the current status of particular heating system devices Tap on the tile to adjust the operation parameters The user may customize the home page by changing t...

Страница 26: ...ller parameters The following tabs include main controller parameters The menu structure is the same as the structure of the main controller menu Screenshot presenting an example tab with main menu Sc...

Страница 27: ...usually performed only once The first step involves filling the fuel tank up and selecting the option Fuel tank full by pressing the pulser knob The controller remembers the level as full 100 When th...

Страница 28: ...ype of regulator is selected in CH pump control or CH boiler control submenu the communication is activated automatically VI 12 External temperature correction External sensor correction should be per...

Страница 29: ...Fuel granulation parameter is no longer available in the main menu and Fuel level calibration option is not available in the fitter s menu In the case of pellet boilers it is possible to remotely init...

Страница 30: ...User s manual 30...

Страница 31: ...a pre defined time from the heater deactivation another fire up attempt follows After two unsuccessful attempts the display informs about the fire up failure When the fire up fails the controller sho...

Страница 32: ...nitiated again g Fire up function If this function is active the damping process is initiated when the pre set room temperatures of the controlled devices have been reached The controlled devices may...

Страница 33: ...he water tank is not sufficiently heated When the pre set temperature of water tank is 55O C whereas the actual CH boiler temperature reaches 62O C so called priority temperature the controller disabl...

Страница 34: ...motors CH pump DHW pump fan feeder and circulating pump No Specification Unit 1 Supply voltage V 230V 50Hz 10 2 Maximum power consumption W 11 3 Ambient temperature O C 5 50 4 Maximum output load of...

Страница 35: ...7 Directive 2014 30 EU of the European Parliament and of the Council of February 26 2014 on the harmonisation of the laws of Member States relating to electromagnetic compatibility EU Journal of Laws...

Страница 36: ...User s manual 36...

Отзывы: