background image

41

A boiler room with solid fuel automatic boiler requires periodic supervision. 

During boiler operation certain daily activities must be performed, to prevent 

emergency situations.

When fuel is loaded into the hopper, it should be ensured that the fuel does 

not contain any large pieces of coal, and in particular stones, which may block 

the feeder!

The controller settings must be adjusted according to current temperatures 

outside and quality of burned fuel. Setting parameters should be selected (moni-
toring fire condition and appearance in the furnace).

In the automated mode the controller measures the temperature of water in 

the boiler, and uses the results to control work of the fuel feeder and the blower 
fan according to previously selected settings optimum for a given fuel type. De-
pending on the weather conditions, burning intensity and the boiler heat output 
should be adjusted according to changing conditions, regulating a temperature 
of water leaving the boiler (or, when the three- or four-way valve is installed, by 
changing settings of the control shutter).

At the same time the controller controls operation of pumps: central heating, 

domestic hot water, floor and circulation (if the heating system is equipped with 
pumps).

Regularly - at least once a day - open the furnace door and check the flame 

condition (furnace appearance). When any deviations are noticed, adjust the bo-

iler operation (see Chapter 11 “Statuses of incorrect boiler work”).

In the central heating system, the heat demand changes with changes in the 

external conditions, i.e., time of the day and changes in the temperature outside. 
The temperature of water leaving the boiler also depends on the building energy 
performance, i.e., on construction materials, particularly insulation, used for its 
construction.

When the fire in the boiler is extinguished, clean the furnace and air the boiler 

ducts during firing, and restart firing. 

During firing smoke can penetrate into the boiler room or retting (sweating) 

of the boiler. When the boiler and the flue pipe are warmed these adverse effects 
should be reversed.

The boiler can stop when there is no fuel in the hopper or the feeder is blocked 

with undesirable hard objects, stones, etc.

8.3. BOILER CLEANING

For economic fuel consumption and to obtain declared boiler output and heat 

effectiveness, it is necessary to maintain required cleanness of the burner furnace 
space and the exchanger convection ducts.

The convection ducts, in which air-born ash is deposited, should be regularly 

cleaned, every 3÷7 days. Relevant tools delivered with the boiler should be used 

Содержание BIO SOLID 14

Страница 1: ......

Страница 2: ...arranty terms and conditions 55 Warranty card 55 LIST OF FIGURES AND TABLES Table 1 SAS BIO SOLID boiler equipment 18 Table 2 Technical and operational parameters for the SAS BIO SOLID 14 f 48 kW boil...

Страница 3: ...with the provisions of Directive 2006 42 EC The Ordinance Of The Minister Of The Economy Official Journal No 199 2008 item 1228 MD Machinery Directive Directive 2004 108 EC Official Journal No 82 200...

Страница 4: ...aximum working temperature declared i e 85 C 5 Flue gases emitted from an obstructed stack are hazardous The stack and the connector should be kept clean they should be cleaned according to the instru...

Страница 5: ...5...

Страница 6: ...6...

Страница 7: ...7...

Страница 8: ...8...

Страница 9: ...ter central heating systems open close system with gravitational or forced water flow secured according to current local or EU regulations PN EN 12828 A1 2014 05 Heating installations in buildings De...

Страница 10: ...programmed for combustion of the solid fuel in automatic mode The fuel is bio mass in the form of wood granules wood pellets with parameters defined by EN 14961 2 or PN EN ISO 17225 2 2014 07p Basic b...

Страница 11: ...ed by a stream of air coming from the air duct After reaching the preset temperature the automatic fuel ignition and fire support system enables the boiler the possibi lity of efficient operation even...

Страница 12: ...t operation of the moving grate mechanism requires a correct setting of the Hall effect sensor A distance between the position sensor and the moving grate drive string should be 3 to 5 mm these compon...

Страница 13: ...temperature sensor The co operation between the controller Fig 6 item 39 of the feeder SAS MULTI FLAME type the master boiler controller Fig 6 item 28 is possible thanks to the wired RS communication...

Страница 14: ...ly control activi ties must be performed to prevent emergency situations BOILER DESIGN With the boiler structure based on three pass layout of a flue gas duct in the exchanger with ceramic panels flue...

Страница 15: ...for closing systems for doors and a fuel tank cover Non flammable insulating materials were installed to reduce heat losses and secure against excessive increase in a temperature of external boiler su...

Страница 16: ...a few seconds When the fuel reservoir cover is closed the operation is resumed Inside the cover there is an information for the user about the presence and operation of the limit switch reservoir cove...

Страница 17: ...ided in this instruction Fig 9 SAS BIO SOLID automatic boiler with control is delivered with a controller blowing fan pellet burner SAS MULTI FLAME fuel reservoir ash box doors furnace doors clean out...

Страница 18: ...made of stainless steel protecting the cleanout door pieces 1 12 The set of refractory ceramic panels rear front sides horizontal partitions pieces 1 13 The set of refractory ceramic panels boiler sid...

Страница 19: ...230V 50Hz 21 Power consumption W up to 220 600 on ignition 22 Noise level by PN EN 15036 1 2006 dB 65 dB A 23 Basic boiler dimensions Amps mm 1230 1270 1270 1290 1410 A1 mm 290 290 290 305 330 B mm 9...

Страница 20: ...side 11 Ceramic panels rear front 12 Ceramic shelves 13 Furnace doors 14 Protective partition 15 Clean out hatch door 16 STB safety temperature limiter 17 Power strip 18 Flue gas turbulator 19 Flue g...

Страница 21: ...s separated by the transfer duct 4 Fuel feeder temperature sensor 5 Moving grate drive motor 6 Feeder supporting foot 7 Hall effect sensor moving grate positioning sensor 8 Thermally insulated air duc...

Страница 22: ...BURNER DESIGN upper view 15 Moving grates number depends on the burner power 16 Sealing cord 17 Burner mounting plate 18 Blower fan 19 Gear motor for the feeder 20 Feeder drive unit 21 Housing of the...

Страница 23: ...terials this may result in damage to the fur nace Contamination of the heat exchanger surface leads to reduced boiler effi ciency and deterioration in the burning process It is forbidden to use flamma...

Страница 24: ...chimney degree exchanger contamination inside and outside temperature of the heated building building insulation NOTICE The fuel tank should be loaded with fuel free of water and exces sive quantitie...

Страница 25: ...n the back part of the room a device controlling air flow should be installed in a supply aperture or duct however it sho uld not reduce the cross section to less than 1 5 no supply ventilation or its...

Страница 26: ...system damping connectors vibration compensator e g EFAR DANFOSS etc can be installed The boiler should be set according to guidelines provi ded in chapter 7 3 Setting a boiler 7 3 SETTING A BOILER T...

Страница 27: ...y connected to the stack with a smoke connection in form of a steel pipe 3 mm thick of a thermal resistance of 400 C and of a diameter allowing its tight connection to the flue outlet and inserting in...

Страница 28: ...emperature of exhaust gas at the nominal thermal power bo iler can cause pollution wet deposition of soot insufficient chimney flow This may result in moisture accumulation and corrosion of masonry ch...

Страница 29: ...ed with the following components a circulatory pump and a domestic hot water temperature sensor connected to a supply terminal strip on the boiler side The system should be constructed by a qualified...

Страница 30: ...ceptable as this may damage the sewage system When the temperature in the sensor environment drops below 95 C the re lief valve is closed automatically and water flow from the overflow vessel is stop...

Страница 31: ...precipita ting deposits may affect temperature indications and prolong the time needed to open a valve protecting against overheating For correct operation of the thermostat valve markings showing a c...

Страница 32: ...tank 7 four way valve 8 circulatory pump of a central heating system 9 central heating system RW expansion pipe RB pressure relief pipe RO venting pipe RP overflow pipe RS signalling pipe Figure 10 Ge...

Страница 33: ...tank 15 circulatory pump of an open vented system 16 plate heat exchanger 17 circulatory pump of a sealed system RW expansion pipe RB pressure relief pipe RO venting pipe RP overflow pipe RS signallin...

Страница 34: ...tube 4 cut off ball valve 5 sump strainer 6 thermal protection device e g SYR type 5067 protecting the system against overheating 7 differential pressure control valve 8 circulatory pump of a domesti...

Страница 35: ...e cold water may flow from the supply pipe cooling down the boiler When lowering the temperature of the boiler to 94o C the discharge valve is closed With thermally controlled filling valve and temper...

Страница 36: ...gs Design for water based heating systems PN EN 303 5 Minister of Infrastructure Regulation concerning technical conditions that should be met by buildings and their setting of 12 April 2002 Jour nal...

Страница 37: ...devices working with it ope rate under voltage of 230 V therefore all connections can only be made by a person having required qualifications Polish Electricians Association licence up to 1kV All work...

Страница 38: ...grees free oxygen content 0 1 mg O2 l Temporary hardness caused by hydrogen carbonates that are thermally unstable and when heated are transformed into water insoluble carbonates deposited as lime sca...

Страница 39: ...erature When a supply ventilation is not installed this may result in generation of large quantities of flammable highly explosive gases a risk of damage to the flue pipe NOTICE Both the fuel reservoi...

Страница 40: ...firing process on the controller ceramic burner In the boiler automatic mode a set temperature boiler water temperature value must be set on a con troller along with the operating time and intervals i...

Страница 41: ...on if the heating system is equipped with pumps Regularly at least once a day open the furnace door and check the flame condition furnace appearance When any deviations are noticed adjust the bo iler...

Страница 42: ...ust slag At the factory the boiler was equipped with a set of ceramic sealant see inspec tion clean our doors holes Regular inspection of the sealant condition is recommen ded and its replacement when...

Страница 43: ...ir chamber see fig 7 item14 possibly shutoff the boiler and clean the furnace the pellet burner When the boiler is equipped with a flue gas temperature sensor its surfa ce must be cleaned regularly to...

Страница 44: ...rflow pipes is very dangerous as it may result in the boiler damage it is forbidden to fire the boiler using flammable materials such as petrol kerosene or solvents as this may result in explosion or...

Страница 45: ...of air nozzles and patency of air outlets 7 Periodically clean dust and residues of fuel or ash from the feeder 8 Regularly clean the motor casing using a dry cloth 9 Do not use any solvents for clea...

Страница 46: ...patency and parameters see a table specifying appropriate chimney hight and cross section for a given boiler output check whether the chimney does not end below the highest roof ridge contamination of...

Страница 47: ...eating system and the boiler e g due to incorrect filling of the system and the boiler with water boiler warming up i e maintaining the temperature above 70 C for longer time until air bubbles are com...

Страница 48: ...g mes sage Temperature does not increase When the encoder is pressed the alarm is switched off The controller returns to the last set operational mode AUTOMATED SENSOR MONITORING When the central heat...

Страница 49: ...90 to 100 C The equipment cannot be restarted automatically even when the temperature is lowered The user must switch them on resetting the sensor with the button after the temperature of the boiler...

Страница 50: ...r is additionally secured against flashback to the fuel tank hop per The boiler is equipped with a feeder pipe sensor measuring temperature near the fuel tank When the temperature increases significan...

Страница 51: ...ed in the sealed system e g SYR type 5067 When the boiler is overheated jacket temperature above 95 C the thermal pro tection valve installed on the boiler is opened the water supplied from the water...

Страница 52: ...to a relevant waste collection entity The waste collection place should be specified by relevant municipal or commune services 15 WARRANTY TERMS AND CONDITIONS 1 The manufacturer grants to the Buyer a...

Страница 53: ...ensures free of charge repairs of the subject matter of the agreement within 14 days of a date of notification 11 A defect covered by a warranty repair should be notified immediately when that defect...

Страница 54: ...ress and product moder nisation These changes may not be included in this operation and mainte nance documentation while the basic described features of the product will be maintained All issues and q...

Страница 55: ...period of 60 months on low temperature boiler SAS BIO SOLID boiler is given in accordance with the technical documentation Boiler no Thermal power Heating surface Year of manufacture Signature and sta...

Страница 56: ......

Отзывы: