User Manual & Datasheet V 2.3

11

Installation & Handling Guide-

lines

The elixir can be installed in the vessel in almost any posi-

tion. Previously existing bosses welded in any direction can
be used. Since the fork can be screwed into a mounting
socket suitable for supplied mounting threads and the fork
length is comparatively short, it can be installed directly on
pipes too. For liquids with higher viscosities, top mounting
or side mounting with tines slanting downwards is preferred
as then the viscous liquid can drip off faster when the level
goes below the set point.
While installation of probe, please take care of the following
points:

The instrument shouldn’t block the material filling inlet.

Secure the cover of housing tightly. Tighten the cable
glands.

For side-mounting, provide a baffle to prevent the ma-
terial from falling on the fork. Please refer to Figure 6.

Figure 6: Provision of Baffle

When handling forks, do not lift them using their tines.
Please see Figure 7.

Figure 7: Instrument Handling

The tines should not be bent nor should their dimen-
sions be altered. Deforming the shape of the tines may
interfere with the fork’s operating frequency. Please
see Figure 8.

Make all electrical connections as instructed in the
manual. Don’t power on the device before verifying
connections.

To prevent the ingress of moisture and water seepage
in side mounting position, the cable entries should al-
ways point downwards.

Figure 8: Tines Handling

Weatherproofness of enclosure is guaranteed only if
the cover is in place glands adequately tightened.
Damage due to accidental entry of water can be
avoided if the instrument is installed in a rain shade.

If the ambient temperature is high, the instrument
should not be installed to receive direct sunlight. In
case such a position of shade is not available, a heat
shield should be fitted above the instrument especially
if the operating temperature lies between

60

C and

80

C.

While screwing the elixir instrument, the hexagonal
mounting bush should be turned and not the housing.

12

Electrical Connections

Please refer to the Figures 9a, 9b and 9c for the same.

13

Calibration Settings

Follow the below procedure for calibrating the instrument

at notch point

To start with calibration, set calibration switch to
CLOSE position. (CLOSE is opposite of OPEN on the
DIP switch.)

Make sure that Status LED is not blinking for error.

Dip the fork till the notch point.

Then press ENTER.

The Status LED will blink in RED color.

Blinking indicates that elixir is registering the switch
point position.

Keep ENTER key pressed for 4 to 5 blinks.

Then release the ENTER key.

On Release, the status LED should :
- Turn RED for Maximum Failsafe Selection.
- Turn Green for Minimum Failsafe Selection.
- This indicates that calibration is correct.

Now test the calibration by dipping and removing the
tines from liquid.

During calibration, delays are automatically by-passed.

If calibration is correct, put the calibration switch back
to the OPEN position.

Sapcon Instruments Pvt.Ltd.

R

11

Содержание ELIXIR

Страница 1: ...ELIXIR Compact Vibrating Fork INSTRUCTION MANUAL Version 2 3 ...

Страница 2: ...ifications 7 9 Switching Indication 7 10 Influences on Switching Point 8 11 Installation Handling Guidelines 11 12 Electrical Connections 11 13 Calibration Settings 11 14 Cover Delay 12 15 Uncover Delay 13 16 Failsafe Settings 13 17 Troubleshooting Fault Indication 14 17 1 Output Indications 14 17 2 Error Indications 14 18 Maintenance 14 19 Customer Support 14 20 Product Selection Chart Elixir 15 ...

Страница 3: ... Instrument Handling 11 8 Tines Handling 11 9 Electrical Connections 12 10 Cover Delay Switch Position 12 11 Cover Delay Switch Position 12 12 Setting Cover Delay 12 13 Saving Cover Delay 12 14 Uncover Delay Switch Position 13 15 Setting Uncover Delay 13 16 Saving Uncover Delay 13 17 Failsafe High 13 18 Failsafe Low 13 List of Tables 1 Electrical Specifications 6 2 Application Specifications 6 3 M...

Страница 4: ...this manual may differ from the actual instrument housing in terms of dimensions color and design Please refer to GA drawings for dimensional details Values of performance described in this manual were obtained under ideal testing conditions Hence they may differ under industrial environment and settings General Instructions Instrument shouldn t block the material filling inlet Secure the cover of...

Страница 5: ...n of Parts 3 Features Universal Power Supply 18 55V DC 90 265V AC Low Power Consumption less heat long life High temperature durability H1 up to 200 C Immunity to spurious external vibrations material tur bulence and flow Suitable for liquids with viscosity up to 10 000 cP Fast switching Self diagnosis Independent of material s electrical properties 4 System Description The elixir level detecting ...

Страница 6: ...umption 4W at 24V DC with 90 mA load Fail safe Settings User selectable Field selectable through toggle switch Open Fail safe High Close Fail safe Low Time Delay Settings Cover and Uncover Delay 0 8s 1s to 20s through toggle switches Sensitivity Setting Field Selectable through toggle switches Protection If required additional over current and short circuit protec tions can be provided with the us...

Страница 7: ...your specifications Material MS Plated SS Extension Pipe GI Galvanized Iron SS 304 SS 316 Wetted Parts S4 SS 304 S6 SS 316 S6L SS 316L HA Hastelloy C CHLR Halar Coated PTFE Teflon Coated Process Temperature A Ambient Below 100 C H High temperature 100 C 200 C Resonant Frequency Active Fork length of 100mm Active Fork length of 44mm Value Approx 1 1KHz Approx 1 5KHz Table 3 Mechanical Specification...

Страница 8: ...uences on Switching Point 1 Process Pressure It has no significant effect on the switching point of the device as can be observed from the Figure 3 Figure 3 Influence of Process Pressure on Switching Point Sapcon Instruments Pvt Ltd R 8 ...

Страница 9: ...atasheet V 2 3 2 Process Temperature The influence of temperature on switching point of the device is described in Figure 4 Figure 4 Influence of Process Temperature on Switching Point Sapcon Instruments Pvt Ltd R 9 ...

Страница 10: ...sheet V 2 3 3 Liquid Density The influence of liquid density on switching point of the device can be seen in the graph in Figure 5 Figure 5 Influence of Liquid Density on Switching Point Sapcon Instruments Pvt Ltd R 10 ...

Страница 11: ...d al ways point downwards Figure 8 Tines Handling Weatherproofness of enclosure is guaranteed only if the cover is in place glands adequately tightened Damage due to accidental entry of water can be avoided if the instrument is installed in a rain shade If the ambient temperature is high the instrument should not be installed to receive direct sunlight In case such a position of shade is not avail...

Страница 12: ...over Delay the number of blinks can be adjusted as per requirement Note You can set the value of COVER DELAY between 1 25 secs Follow the below procedure for setting Cover Delay 1 Ensure that all DIP switches are in OPEN position as shown in Figure 10 Make sure that STATUS LED is not blinking for Error OPEN COVER UNCOVER CALIBRATE FAILSAFE Figure 10 Cover Delay Switch Position 2 To set the Cover D...

Страница 13: ...NTER COVER UNCOVER CALIBRATE FAILSAFE ELIXIR STATUS LED RED GREEN Figure 15 Setting Uncover Delay 4 Uncover Delay is entered but not saved To save and test the Uncover Delay set the UNCOVER switch back to OPEN position as shown in figure 16 The STATUS LED will come back to its original position OPEN ENTER COVER UNCOVER CALIBRATE FAILSAFE ELIXIR STATUS LED RED GREEN Figure 16 Saving Uncover Delay 5...

Страница 14: ...ive Oscillator In fail safe High mode instrument will switch to alarm condition if the connectivity between vibrat ing fork and electronics is lost 18 Maintenance The electronics of elixir instrument needs no mainte nance When cleaning and checking the vessel free the tuning fork from deposits If the material has tendency to form a hard sticky deposit the instrument must be checked more often Make...

Страница 15: ...non inductive load NMR Namur type current output at 8 2V ION 2 2 to 2 5 mA and IOFF 0 8 to 1 0 mA Only with VF44 DC6 MA1 8 16 mA 2 wire Loop powered current output at 24V DC Only with VF44 DC Power Supply Depends on Vibrating Fork Output U Universal 18 to 55V DC and 90 to 265V at 50Hz AC DC6 8 2V DC supplied by NAMUR certified isolator Only with VF44 NAMUR DC 24V DC Only with VF44 MA1 Insulation D...

Страница 16: ... Length VF44 Total Length 50 mm Tines 44mm Material SS 316 Only with 0 68H 1 05H 1 25H10H VF110 Total Length 110mm Tines 100mm Material SS 316 Only with 1 3H 1 75H 2H30H Finish HB Standard FB Fully Buffed Extension Material Depends on Probe Length Only with 1 25H10H 2H30H ES4 SS 304 ES6 SS 316 Standoff Material Depends on Operating Temperature Only with 20T STS4 SS 304 STS6 SS 316 Operating Temper...

Отзывы: