User Manual & Datasheet V 2.3
5. To test, dip elixir into the application material until the
switching point is reached.
The STATUS LED will start blinking RED if the switch
point is reached. It will blink for the number of seconds for
which the cover delay is set. 1 blink is equal to 1 second
during switching. A maximum of 25 seconds can be set.
15
Uncover Delay
When the application material uncovers elixir’s fork tines,
the changeover of the output can be delayed by a pre-
determined time. This time is called UNCOVER Delay. For
a different value of Uncover Delay, the number of blinks can
be adjusted as per requirement.
Note:
You can set the value of UNCOVER DELAY between
1-25 secs.
Follow the below procedure for setting Uncover
Delay
1. Ensure that all DIP switches are in OPEN position as
shown in Figure 10. Make sure that STATUS LED is
not blinking for Error.
2. To set the Uncover Delay, set the UNCOVER switch to
CLOSE position as shown in Figure 14.
(CLOSE is the opposite of OPEN for a DIP switch.)
The STATUS RED LED will glow.
OPEN
ENTER
COVER
UNCOVER
CALIBRATE
FAILSAFE
ELIXIR
STATUS
LED
RED
GREEN
Figure 14: Uncover Delay Switch Position
3. Press ENTER and keep it pressed as shown in Figure
15. The STATUS RED LED will start blinking. Count
the number of blinks. After setting the value release
the ENTER key.
OPEN
ENTER
COVER
UNCOVER
CALIBRATE
FAILSAFE
ELIXIR
STATUS
LED
RED
GREEN
Figure 15: Setting Uncover Delay
4. Uncover Delay is entered, but not saved. To save and
test the Uncover Delay, set the UNCOVER switch back
to OPEN position as shown in figure 16. The STATUS
LED will come back to its original position.
OPEN
ENTER
COVER
UNCOVER
CALIBRATE
FAILSAFE
ELIXIR
STATUS
LED
RED
GREEN
Figure 16: Saving Uncover Delay
5. To test, dip elixir into the application material until the
switching point is achieved.
6. The STATUS LED will start blinking GREEN if the
switch point is achieved. It will blink for the number
of seconds for which the Uncover Delay is set.
16
Failsafe Settings
In a condition of device failure, known errors and input
power failure the outputs of the device resemble the ALARM
condition. This is meant to prevent overflow or dry run con-
ditions in case of failures.
Prevent Overflow - High Level Switch
Failsafe High (de-
fault) is set by moving the Failsafe switch to OPEN position.
1. When not in contact with the material, LED turns
GREEN.
2. When in contact with the material, LED turns RED.
OPEN
ENTER
COVER
UNCOVER
CALIBRATE
FAILSAFE
ELIXIR
STATUS
LED
RED
GREEN
Figure 17: Failsafe High
Prevent Dry run - Low Level Switch
Failsafe Low is set
by moving the Failsafe switch to CLOSE position
1. When in contact with the material, LED turns GREEN.
2. When not in contact with the material, LED turns RED.
OPEN
ENTER
COVER
UNCOVER
CALIBRATE
FAILSAFE
ELIXIR
STATUS
LED
RED
GREEN
Figure 18: Failsafe Low
Sapcon Instruments Pvt.Ltd.
R
13