SM830043
– 62 –
4
4. Service procedures
b)
Check compressor motor thermal protector (49C)
0628_X_S
• Check voltage between
terminals No.2 and No.4 at
terminal plate.
• Check P.C.B. Ass’y.
No voltage appears.
P.C.B. Ass’y is defective.
D.
Check indoor unit P.C.B.
0626_X_S
Is temperature of compressor
abnormally high ?
Refrigerant gas shortage.
YES
NO
Compressor is defective.
Charge refrigerant gas.
• Check compressor motor
thermal protector. (49C)
0627_X_S
• Check compressor motor
magnetic contactor.
(52C)
(Only outdoor fan does not run.)
Содержание SPW-T483GS56 ? SPW-C483G8 (/M)
Страница 6: ... 6 SM830043 ...
Страница 28: ... 28 SM830043 1 Specifications 1 ...
Страница 32: ... 32 SM830043 2 2 Processes and functions ...
Страница 54: ...SM830043 54 3 3 Electrical data ...