15
English
INDOOR
UNIT
Tubing length (L)
OUTDOOR
UNIT
Elevation
difference (H)
Table 4
*1 Standard tubing length is 5 m.
*2 If total tubing length becomes 5 m to 15 m, charge additional refrigerant (R410A) by 20 g/m.
No additional charge of compressor oil is necessary.
Model
Max. Allowable Tubing
Length at Shipment
(m)*
1
Limit of Tubing
Length (L)
(m)
Limit of Elevation
Different (H)
(m)
Required Amount of
Additional Refrigerant
(g/m)*
2
CRV9AEH
5.0
5
20
15
CRV12AEH
5.0
5
20
15
Table 5
* Packed in the outdoor unit
Parts
Figure
Q’ty
Parts
Figure
Q’ty
Tapping
screw
AAA alkaline
battery
2
Remote
control unit
1
Parts
Figure
Q’ty
Drain elbow
*
1
1
1
4.2 x 25 mm
Insulation
tube
NA
F
RE
PO
NOO
FF
C
FF
O/N
O
FAN
-+
ED
OM
KC
OL
C
TIM
NO
RE
WO
LBP
ME
T
ITME
R
FFO
OB
RUT
PE
EL
ST
HGI
L
5
1
0
Flare nut
Putty
Fig. 37
Drain elbow
Drain hole
Hose
(locally purchased,
inner dia. 16 mm)
Fig. 38
4-4. Tubing Length
Install unit within the maximum elevation different (H)
above or below the outdoor unit and within a total tub-
ing length (L) from the outdoor unit as detailed in
Table 4 and Fig. 37.
4-5. Outdoor Condensation Drainage
The drain hole at the bottom of the outdoor unit was not
plugged at the time of factory shipment. If necessary,
mount the accessory drain elbow before installing the
outdoor unit. (Fig. 38)
4-6. Accessories
Table 5 lists the accessories supplied with the unit.
CAUTION
When installing in a cold area where
drainage water may freeze, do not
attach the provided drain elbow to
the bottom plate of the unit.