7
Outdoor Unit
SAP – C122AH
Controller PCB
—
Compressor
Type
Rotary (Hermetic)
Compressor model
C-R112H5X 80616745-S
Nominal output
W
1,100
Compressor oil ... Amount
cc
4GSD-T or SAY-56T ... 550
Coil resistance (Ambient temp. 25°C)
Ω
C–R : 1.962
C–S : 5.38
Safety devices
Type
External(OLR A)
External(OLR T)
Overload relay
MRA98596-9201
CS-7C115
Operating temp.
Open
°C
145±5
115±3
Close
°C
69±11
95±5
Operating amp.(Ambient temp. 25°C)
Trip in 6 to 16 sec. at 21A
—
Run capacitor
µF
25.0
VAC
400
Crank case heater
—
Fan & Fan Motor
Type
Propeller
Q'ty ... Dia.
1 ... ø370
Fan motor model ... Q'ty
UE6S-21AC5P-S ... 1
No. of poles ... rpm (230 V, High)
6 ... 750
Nominal output
W
20
Coil resistance (Ambient temp. 20°C)
Ω
BRN-WHT : 341.2
WHT-YEL : 212.7
YEL-PNK : 190.0
Safety devices
Type
Thermal fuse
Operating temp.
Open
°C
145 ± 2
Close
°C
—
Run capacitor
µF
1.5
VAC
440
Heat Exch. Coil
Coil
Aluminum plate fin / Copper tube
Rows
2
Fin pitch
mm
1.2
Face area
m
2
0.329
External Finish
Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.