10
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
11
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
System configured at site
Main
Hot Water
Boiler
Hot water inlet: Rø3/4
Hot water outlet: Rø3/4
Hot Water
Storage
Tank
Water piping
GHP
OUT
IN
GU Type Heat Exchanger & CFR Units
SANYO’s new heat recovery ventilation system allows
total control via a system network whilst modulating the
temperature and humidity of incoming air supply.
• Integration of heat recovery ventilation and DX coil technology
for optimum air temperature control
• Connects to all ECO & GHP outdoor units with a filter option
• 3 Way: Solenoid valve kit is required for each unit
• 2 Way: RAP kit is required for each unit
Indoor unit specifications
Model Name
SPW-GU055XH
SPW-GU075XH
SPW-GU105XH
Air circulation (H) m³/h
500
750
1,000
Power source
220/230/240V, 1 phase - 50 Hz
Fresh air load
treatment capacity
UK Cooling
kW
5.3 (1.7)*¹
8.2 (2.6)*¹
10.7 (3.4)*¹
UK Heating
kW
6.5 (2.3)*¹
9.8 (3.5)*¹
12.6 (4.6)*¹
Enthalpy exchange
efficiency
UK Cooling
%
59
UK Heating
%
67
Temp exchange efficiency
75
Equivalent cooling capacity
kW
3.6
5.6
7.3
BTU/h
12,000
19,000
25,000
Power input
Cooling
kW
0.532
0.737
0.798
Heating
kW
0.532
0.737
0.798
Running current
Cooling
Amps
2.4
3.2
3.5
Heating
Amps
2.4
3.2
3.5
Fan motor
Type
Sirocco fan
External static pressure-return air
Pa
183 (170)
221 (188)
135 (88)
External static pressure-supply air
Pa
205 (182)
264 (218)
176 (137)
Output
kW
0.28 (4P)x2
0.35 (4P)x2
Sound pressure level (C/H)
db(A)
46 (Cooling), 47 (Heating)
47 (Cooling), 48 (Heating)
48 (Cooling), 49 (Heating)
Dimensions
Height
mm
425
450
Width
mm
1785
1903
Depth
mm
1000
1120
1220
Piping connections
Liquid (flare)
mm (inches)
6.35 (1/4)
Gas (flare)
mm (inches)
12.7 (1/2)
Drain piping
VP-25
Connection duct diameter
mm
250
300
Net weight
kg
134
153
168
The values in ( ) for the external static pressure and operating sound are for use of booster cable. *1: Heat recovery capacity by heat exchanger. Data subject to change without notice.
The CFR- PHE uses a unique purifying Bioxigen system to
produce negative ions this can reduce pollutants by up to
85% whilst improving, significantly air quality within most
environments.
• High efficiency heat exchanger & Easy to clean filters
The CFR-PHE unit structure is constructed from Aluzink frame
work and galvanised steel with 20 mm thick fire resistant
acoustic insulation, reducing both weight and sound levels to
a minimum. The system is supplied with ducted spigots which
can be positioned either at the front or side of the unit to ease
installation.
Indoor unit specifications
Model CFR/ CFR-PHE
33
55
110
175
220
Nominal air flow *
m3/hr
300
620
920
1580
1850
External Static Pressure
pa
45
55
65
70
77
Sound Pressure **
dB(A)
43
51
50
53
52
Fans
Power in
Watts
184
340
294
700
700
Absorbed power
A
0.75
1.8
2.2
4.4
4.8
Fan speeds
no
1
3
Insulation Class
F
Electrical supply
v/ph/htz
230/1/50
Bioxigen Elements (PHE only)
Number of elements
2 X C
2 X F
Electrical supply
v/ph/htz
230/1/50
Power in
Watts
8
8
8
8
8
Filter
EU3
Paper Heat Exchanger
CFR-PHE
Temperature Efficiency heating ***
76%
74%
72%
68%
73%
Temperature Efficiency cooling ****
62%
60%
58%
54%
59%
* Nominal air flow ** Sound pressure 1.5 mts from the unit in free field *** Data referred to -5
0
C 80% RH OAT room condition 20
0
C 50% RH **** Data referred to 32
0
C 50% RH OAT room condition 26
0
C 50% RH
The high efficiency low pressure loss total heat exchanger
is made of specially treated paper to enable the unit to be
as efficient as 76% during normal operation. This allows
system to recover both latent and sensible heat.
Additional GHP Functions
GHP Chiller available with outdoor unit capacities from 71kW
Water Heat Exchanger
Air Handling Unit
Water Piping
Duct
Outdoor unit
Operating condition
Cooling
Heating
(standard)
Heating
(low temperature)
Water temperature of water heat exchanger unit Outlet 7°C
Outlet 45°C
Outlet 45°C
Outdoor side intake air temperature
35°C DB
7°C DB, 6°C WB
2°C DB, 1°C WB
Note: The gas consumption can be 110% of the specification value depending on the
operating conditions.
The SANYO ECO G Water Heat Exchanger can provide
water at a wide range of temperatures suitable for a
variety of commercial applications ranging from comfort
air conditioning to food processing or the replacement of
boilers and other systems.
• New 25 kW and 50 kW capacity models
• In cooling (chiller) mode provides water from -15°C to 15°C
• In heating mode can provide hot water up to 55°C, for example
for under floor heating applications
• Includes water flow protection to prevent freezing
• Temperature sensor included
• S-Link communication is connectable with any controllers
• Split system means reduced installation cost and the use of a
less powerful circulation pump
•
One touch changeover between cooling and heating operation
• The system can accommodate up to 120m (actual length) of
piping between the outdoor unit and the water heat exchanger,
allowing flexibility of installation location
• The system uses antifreeze coolant, so it can produce cold water
even at -15°C, thereby complying with “brine specifications”
Model No.
SGP-WE80M1
SGP-WE170M1
SGP-EW120M2G2W
Cooling capacity
kW
25
30
Heating capacity
kW
30
35.5
SGP-EW150M2G2W
Cooling capacity
kW
25
37.5
Heating capacity
kW
30
45
SGP-EW190M2G2W and
SGP-EGW190M2G2W
Cooling capacity
kW
25
50
Heating capacity
kW
30
60
SGP-EW240M2G2W
Cooling capacity
kW
25
56
Heating capacity
kW
30
67
Electrical rating
Cooling power input kW
0.01
Heating power input kW
0.01
Power supply
220/230/240V Single Phase 50Hz
Size
Height
mm
1,000
Width
mm
550
Depth
mm
965
Weight
kg
125
160
Standard cold/hot water flow rate
m
3
/h
4.3
8.6
Hydrostatic loss
kPa
8.5
11.3
Holding water quantity inside the unit
m
3
0.01
0.02
Minimum holding water quantity outside the unit m
3
0.28
0.50
Piping refrigerant
Gas pipe
mm
ø22.22
ø28.58
Liquid pipe
mm
ø9.52
ø15.88
Heat exchanger
hot/cold heat exchanger
Water circuit limit pressure
MPa
0.686
Anti-freezing protection system
Protective thermostat
Specifications subject to change without notice.
Hot water supply function (during cooling or heating operation)
SGP-EW120M2G2W
SGP-EW150M2G2W
SGP-EW190M2G2W
SGP-EW240M2G2W
SGP-EGW190M2G2W
The engine waste heat, which is normally exhausted into
the atmosphere, is recovered via the heat exchanger and
effectively used as hot water, so the GHP system acts as a
subsystem that alleviates the load on the client’s main hot
water system and therefore offers “free” hot water.
Water heating capacity up to 65 kW (of 75°C hot water)
Hot water piping allowable pressure 0.7 MPa
Hot water circulation rate 2 - 3.9m
3
/h
Hot water pipe size 3/4 inch