background image

10

Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB

11

Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB

System configured at site

Main

Hot Water

Boiler

Hot water inlet: Rø3/4
Hot water outlet: Rø3/4

Hot Water 

Storage

Tank

Water piping

GHP

OUT

IN

GU Type Heat Exchanger & CFR Units

SANYO’s  new  heat  recovery  ventilation  system  allows 

total  control  via  a  system  network  whilst  modulating  the 

temperature and humidity of incoming air supply.

•  Integration of heat recovery ventilation and DX coil technology 

for optimum air temperature control

•  Connects to all ECO & GHP outdoor units with a filter option

• 3 Way: Solenoid valve kit is required for each unit

• 2 Way: RAP kit is required for each unit

Indoor unit specifications

Model Name

SPW-GU055XH

SPW-GU075XH

SPW-GU105XH

Air circulation (H)  m³/h

500

750

1,000

Power source

220/230/240V, 1 phase - 50 Hz

Fresh air load 

treatment capacity

UK Cooling 

kW

5.3 (1.7)*¹

8.2 (2.6)*¹

10.7 (3.4)*¹

UK Heating 

kW

6.5 (2.3)*¹

9.8 (3.5)*¹

12.6 (4.6)*¹

Enthalpy exchange 

efficiency

UK Cooling 

%

59

UK Heating 

%

67

Temp exchange efficiency

75

Equivalent cooling capacity

kW

3.6

5.6

7.3

BTU/h

12,000

19,000

25,000

Power input

Cooling 

kW

0.532

0.737

0.798

Heating 

kW

0.532

0.737

0.798

Running current

Cooling 

Amps

2.4

3.2

3.5

Heating 

Amps

2.4

3.2

3.5

Fan motor

Type

Sirocco fan

External static pressure-return air  

Pa

183 (170)

221 (188)

135 (88)

External static pressure-supply air  

Pa

205 (182)

264 (218)

176 (137)

Output 

kW

0.28 (4P)x2

0.35 (4P)x2

Sound pressure level (C/H)  

db(A)

46 (Cooling), 47 (Heating)

47 (Cooling), 48 (Heating)

48 (Cooling), 49 (Heating)

Dimensions

Height 

mm

425

450

Width 

mm

1785

1903

Depth 

mm

1000

1120

1220

Piping connections

Liquid (flare)  

mm (inches)

6.35 (1/4)

Gas (flare)  

mm (inches)

12.7 (1/2)

Drain piping

VP-25

Connection duct diameter  

mm

250

300

Net weight  

kg

134

153

168

The values in ( ) for the external static pressure and operating sound are for use of booster cable. *1: Heat recovery capacity by heat exchanger. Data subject to change without notice.

The CFR- PHE uses a unique purifying Bioxigen system to 

produce negative ions this can reduce pollutants by up to 

85% whilst improving, significantly air quality within most 

environments. 

• High efficiency heat exchanger & Easy to clean filters

The CFR-PHE unit structure is constructed from Aluzink frame 
work and galvanised steel with 20 mm thick fire resistant 
acoustic insulation, reducing both weight and sound levels to 
a minimum. The system is supplied with ducted spigots which 
can be positioned either at the front or side of the unit to ease 
installation.    

Indoor unit specifications

Model CFR/ CFR-PHE

33

55

110

175

220

Nominal air flow *

m3/hr

300

620

920

1580

1850

External Static Pressure 

pa

45

55

65

70

77

Sound Pressure **

dB(A)

43

51

50

53

52

Fans
Power in 

Watts

184

340

294

700

700

Absorbed power

A

0.75

1.8

2.2

4.4

4.8

Fan speeds 

no

1

3

Insulation Class

F

Electrical supply 

v/ph/htz

230/1/50

Bioxigen Elements (PHE only)
Number of elements 

2 X C

2 X F

Electrical supply 

v/ph/htz

230/1/50

Power in 

Watts

8

8

8

8

8

Filter 

EU3

Paper Heat Exchanger 

CFR-PHE

Temperature Efficiency heating ***

76%

74%

72%

68%

73%

Temperature Efficiency cooling ****

62%

60%

58%

54%

59%

* Nominal air flow  ** Sound pressure 1.5 mts from the unit in free field   *** Data referred to -5

0

C 80% RH OAT room condition 20

0

C 50%  RH **** Data referred to 32

0

C 50% RH OAT room condition 26

0

C 50% RH

The high efficiency low pressure loss total heat exchanger 
is made of specially treated paper to enable the unit to be 
as efficient as 76% during normal operation. This allows 
system to recover both latent and sensible heat.  

Additional GHP Functions

GHP Chiller available with outdoor unit capacities from 71kW

Water Heat Exchanger

Air Handling Unit

Water Piping

Duct

Outdoor unit

Operating condition

Cooling

Heating 

(standard)

Heating 

(low temperature)

Water temperature of water heat exchanger unit Outlet 7°C

Outlet 45°C

Outlet 45°C

Outdoor side intake air temperature

35°C DB

7°C DB, 6°C WB

2°C DB, 1°C WB

Note:  The gas consumption can be 110% of the specification value depending on the 

operating conditions.

The  SANYO  ECO  G  Water  Heat  Exchanger  can  provide 

water  at  a  wide  range  of  temperatures  suitable  for  a  

variety of commercial applications ranging from comfort 

air conditioning to food processing or the replacement of 

boilers and other systems.

• New 25 kW and 50 kW capacity models

•  In cooling (chiller) mode provides water from -15°C  to 15°C

•  In heating mode can provide hot water up to 55°C, for example 

for under floor heating applications

• Includes water flow protection to prevent freezing

• Temperature sensor included

• S-Link communication is connectable with any controllers

•  Split system means reduced installation cost and the use of a 

less powerful circulation pump

  One touch changeover between cooling and heating operation

•  The system can accommodate up to 120m (actual length) of 

piping between the outdoor unit and the water heat exchanger, 
allowing flexibility of installation location

•  The system uses antifreeze coolant, so it can produce cold water 

even at -15°C, thereby complying with “brine specifications”

Model No.

SGP-WE80M1

SGP-WE170M1

SGP-EW120M2G2W

Cooling capacity

kW

25

30

Heating capacity

kW

30

35.5

SGP-EW150M2G2W

Cooling capacity

kW

25

37.5

Heating capacity

kW

30

45

SGP-EW190M2G2W and

SGP-EGW190M2G2W

Cooling capacity

kW

25

50

Heating capacity

kW

30

60

SGP-EW240M2G2W

Cooling capacity

kW

25

56

Heating capacity

kW

30

67

Electrical rating

Cooling power input kW

0.01

Heating power input kW

0.01

Power supply

220/230/240V Single Phase 50Hz

Size

Height

mm

1,000

Width

mm

550

Depth

mm

965

Weight

kg

125

160

Standard cold/hot water flow rate

m

3

/h

4.3

8.6

Hydrostatic loss

kPa

8.5

11.3

Holding water quantity inside the unit

m

3

0.01

0.02

Minimum holding water quantity outside the unit m

3

0.28

0.50

Piping  refrigerant

Gas pipe

mm

ø22.22

ø28.58

Liquid pipe

mm

ø9.52

ø15.88

Heat exchanger

hot/cold heat exchanger

Water circuit limit pressure

MPa

0.686

Anti-freezing protection system

Protective thermostat

Specifications subject to change without notice.

Hot water supply function (during cooling or heating operation)

SGP-EW120M2G2W 

SGP-EW150M2G2W 

SGP-EW190M2G2W 

SGP-EW240M2G2W 

SGP-EGW190M2G2W

The  engine  waste  heat,  which  is  normally  exhausted  into 
the  atmosphere,  is  recovered  via  the  heat  exchanger  and 
effectively  used  as  hot  water,  so  the  GHP  system  acts  as  a 
subsystem that alleviates the load on the client’s main hot 
water system and therefore offers “free” hot water.

Water heating capacity up to 65 kW (of 75°C hot water)
Hot water piping allowable pressure 0.7 MPa
Hot water circulation rate 2 - 3.9m

3

/h

Hot water pipe size 3/4 inch

Содержание ECO G SGP-EGW190M2G2W

Страница 1: ...SANYO Air Conditioners The natural choice Gas Driven VRF M Series GAS DRIVEN VRF ELECTRIC VRF COMMERCIAL SPLIT SYSTEMS ROOM AIR CONDITIONERS HEATING SOLUTIONS ...

Страница 2: ... supply problems If you are short of electrical power gas heat pump could be the perfect solution Runs on gas and just needs single phase supply Enables the building s electrical power supply to be used for other critical electrical demands Reduces capital cost to upgrade power substations to run heating and cooling systems Reduces power loadings within a building especially during peak periods El...

Страница 3: ...re C Gas heat pump Electric heat pump Time axis in case of the same load Outside air temperature C Electric heat pump Gas heat pump Comparison of heating capacity Heating capacity Comparison of the start times for heating operation Room temperature C Gas heat pump Electric heat pump Time axis in case of the same load Outside air temperature C Electric heat pump Gas heat pump Comparison of heating ...

Страница 4: ...onsumption Cooling kW 24 50 31 60 38 30 60 90 49 00 56 10 63 20 62 80 69 90 76 60 99 20 121 80 Heating STD kW 28 10 36 10 43 00 58 00 56 20 64 20 72 20 71 10 79 10 86 00 101 00 116 00 Heating LOW 36 80 47 30 56 40 64 90 73 60 84 10 94 60 93 20 103 70 112 80 121 30 129 80 COP Cooling 1 40 1 37 1 41 1 14 1 40 1 38 1 37 1 41 1 39 1 41 1 25 1 14 Heating 1 37 1 35 1 43 1 34 1 37 1 36 1 35 1 41 1 39 1 4...

Страница 5: ... STD kW 48 7 43 0 76 80 84 80 97 40 101 00 Heating LOW 62 1 56 4 98 90 109 40 124 20 121 30 COP Air conditioning only Cooling 1 33 1 41 1 29 1 23 1 18 Heating 1 34 1 43 1 31 1 30 1 27 1 38 AVE 1 34 1 42 1 30 1 25 1 28 Max COP Inc generater hot water Cooling 1 78 1 81 1 80 1 78 1 69 Height Height mm 2 248 Width 1 800 1 800 100 Min distance 1 800 Depth 1 000 60 Weight kg 875 1 660 1 685 1 740 1 720 ...

Страница 6: ... 59 Nominal air flow Sound pressure 1 5 mts from the unit in free field Data referred to 50 C 80 RH OAT room condition 200 C 50 RH Data referred to 320 C 50 RH OAT room condition 260 C 50 RH The high efficiency low pressure loss total heat exchanger is made of specially treated paper to enable the unit to be as efficient as 76 during normal operation This allows system to recover both latent and s...

Страница 7: ...R74GXH56B SPW U095XH SPW UR94GXH56B SPW U125XH SPW UR124GXH56B SPW U165XH SPW UR164GXH56B SPW U185XH SPW UR184GXH56B SPW U255XH SPW UR254GXH56B SPW U365XH SPW UR364GXH56B SPW U485XH SPW UR484GXH56B SPW U605XH SPW UR604GXH56B DR Type Concealed Duct SPW DR254GXH56B SPW DR364GX H56B SPW DR484GX H56B SPW DR764GX H56B SPW DR964GX H56B K Type Wall Mounted Unit SPW K075XH SPW K095XH SPW K125XH KR Type Wa...

Страница 8: ...ON OFF Mode setting Fan speed setting Temperature setting Air flow direction Permit Prohibit switching Weekly programme 1 Setting is not possible when a remote control unit is present Use the remote control for setting Centralised control systems Operation with various function from central station Only ON OFF operation from central station Simplified charge ratio for each tenant Touch screen pane...

Страница 9: ... to present only general particulars and shall not form any part of the contract For full installation details please contact your SANYO distributor Rating Conditions The cooling and heating capacities are based on the following conditions Cooling Indoor temperature 27 C DB 19 C WB Outdoor temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB Outdoor Temperature 7 C DB 6 C WB Printed usin...

Отзывы: