4
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
5
Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB
ECO G 3 Way Outdoor Unit Specifications
ECO G 3 Way Heat Recovery VRF System
LPG option
The option of using LPG as a power supply increases flexibility
and avoids the problems of potential site restrictions in the
future. The purer fuel is also excellent for further reductions
in CO
2
emissions - a fact recognised by the government.
Still the only heat recovery (3 way) GHP system in
Europe.
The new M Series ECO G 3 Way offers even more
performance and outstanding features when you need
simultaneous heating and cooling. Now with increased
capacities available from 16HP to 25HP, SANYO offers the
greatest choice and flexibility to solve any power problem or
site requirement.
• Simultaneous heating and cooling for total control
• Reduced gas consumption by Miller-cycle engine
• Reduced electrical power consumption by using DC motors
• New lightweight design by use of aluminium engine block
reduces weight by 110kg
• Part load efficiencies increased
• Connectability increased to up to 36 indoor units
• Now available in 16, 20 and 25HP
• 200m maximum allowable piping length (L1) (equivalent - refer
to technical manual)
• Diversity ratio 50% - 130%
• Extended pipe runs (total 500m)
• Silent mode offers a further 2dB(A) reduction
• 10,000 run hours between engine service intervals (equivalent
to one maintenance every 3.2 years*)
• Full heating capacity down to -20°C
• No defrost cycle
* Assuming 3120 running hrs per year - 12 hrs x 5 days x 52 weeks
ECO G 3 Way is ideal for the following types of
application:
• Office buildings with a diverse range of room temperatures
due to differing load profiles.
• Buildings with computer rooms requiring year round cooling.
Additional parts
By taking its power supply from the nearest indoor unit, the
SANYO solenoid valve (change-over box) does not require any
additional fused spur and at only 150mm high can be easily
installed within a 200mm void space.
Dimensions ECO G 3 Way (16-25HP)
Comparison of the start times for heating operation
Room temperature (˚C )
Gas heat pump
Electric heat pump
Time axis (in case of the same load)
Outside air temperature (˚C)
Electric heat pump
Gas heat pump
Comparison of heating capacity
Heating capacity (% )
Comparison of the start times for heating operation
Room temperature (˚C )
Gas heat pump
Electric heat pump
Time axis (in case of the same load)
Outside air temperature (˚C)
Electric heat pump
Gas heat pump
Comparison of heating capacity
Heating capacity (% )
HP
16
20
25
Model
SGP-EZ150M2G2
SGP-EZ190M2G2
SGP-EZ240M2G2
Capacity
Cooling
kW
45.0
56.0
71.0
Heating
STD
kW
50.0
63.0
80.0
Heating Low temp*
53.0
67.0
75.0
Electricity
Cooling
kW
1.35
Heating
kW
1.01
1.54
Gas
Cooling
kW
31.6
38.3
60.9
Heating
STD
kW
36.1
43.0
58.0
Heating
LOW
47.3
56.4
64.9
COP
Cooling
1.37
1.41
1.14
Heating
1.35
1.43
1.34
AVE
1.36
1.42
1.24
Size
Height
mm
2,248
Width
1,800
Depth
1,000 (+60)
Weight
kg
845
875
Starter amperes
A
30
Piping
connection
Gas
Inches (mm)
1 1/8 (28.58)
Discharge
7/8 (22.22)
Liquid
3/4 (19.05)
Pipe fuel gas
R3/4 (bolt thread)
Pipe exhaust drain
mm
ø 25 rubber hose
Operation sound
dB(A)
57
58
62
Indoor/outdoor capacity ratio
50-180% *1
Number of indoor connections
36
* 1: Low temp condition: Outdoor temperature 2 C˚.
Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details.
Please refer to tube sizing charts for pipe selections and pipe length parameters.
Rear View
Front View
Left Side View
at least 2000
Service Clearances for installation
(Units: mm)
Rear
(refrigerant tubing)
Rear
(refrigerant tubing)
at
le
as
t
60
0
at
le
as
t
60
0
at
le
as
t
10
00
at
le
as
t
10
00
at least
100
at least
100
at least
100
at least
350
at least
350
Front View
Front View
(Single-unit installation)
(Multi-unit series installation)
Suction refrigerant pipe
ø28.58
ø22.22
Size (mm)
Model Type
150
190 240
ø25.4
ø19.05
ø28
ø28
G: R3/4
ø20
4 - ø20
4 - ø24
OD: ø25 Length: 200
1
Discharge refrigerant pipe
2
Liquid refrigerant pipe
3
Exhaust gas drain hose
4
Inter-unit cable port
5
Electrical power supply port
6
Fuel gas port
7
Condensation drain opening
8
Rain and condensation outlet
9
Engine exhaust outlet
10
Suspension holes
11
Anchor holes
12
Segmented display
13
Coolant intake (top)
14
Vent
15
Top View
1800 (external)
22
48
(+
30
)
(1
81
)
400
10
14
(a
nc
ho
r p
itc
h)
1000
(anchor pitch)
10
14
12
13
1030 (suspension holes)
1000 (external)
ø736
1060 (frame width)
9
15
11
27
54
147
22
99
10
8
18
1
57
207
242
279
312
55
5
271
7
6
5
4
3
1
2
8