background image

6

Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB

7

Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB

ECO G 2 Way Heat Pump VRF System

ECO G W-Multi for Heat Pump 

Applications

The  new  and  improved  M  Series  heat  pump  

(2  Way)  not  only  offers  improved  performance 

but  also  increased  flexibility.  Now  available  as 

multi-systems,  many  combinations  are  possible, 

from  13HP  to  50HP,  allowing  for  more  power 

and  enabling  accurate  matching  of  a  system  building 

load.  Additional  new  features  include  part  load  engine 

management and compressor run hour equalisation. 

• Reduced gas consumption by Miller-cycle engine

•  Reduced electrical power consumption by using DC motors

•  New  lightweight  design  by  use  of  aluminium  engine  block 

reduces weight by 110kg

• Part load efficiencies increased

• Connectability increased - now up to 48 indoor units 

• Multi-systems with combinations from 13HP up to 50HP

• 200m maximum allowable piping length (L1) (equivalent - refer 

to technical manual)

• Diversity ratio 50-180%

• Extended pipe runs (total 500m)

• Industry leading sound levels

• Silent mode offers a further 2dB(A) reduction

• Chiller option

- 13HP (25kW cooling - 30kW heating) 
- 25HP (56kW cooling - 67kW heating)

•  10,000 run hours between engine service intervals (equivalent 

to one maintenance every 3.2 years*)

• Full heating capacity down to -20°C

• No defrost cycle

* Assuming 3120 running hrs per year - 12 hrs x 5 days x 52 weeks

ECO G 2 Way Outdoor Unit Specifications

Dimensions ECO G W-Multi 2 Way

HP

13

16

20

25

26

29

32

33*

36*

40*

45*

50

Model name

SGP-EW120M2G2W

SGP-EW150M2G2W

SGP-EW190M2G2W

SGP-EW240M2G2W

SGP-EW120M2G2W

SGP-EW120M2G2W

SGP-EW150M2G2W

SGP-EW120M2G2W

SGP-EW150M2G2W

SGP-EW190M2G2W

SGP-EW190M2G2W

SGP-EW240M2G2W

SGP-EW120M2G2W

SGP-EW150M2G2W

SGP-EW150M2G2W

SGP-EW190M2G2W

SGP-EW190M2G2W

SGP-EW190M2G2W

SGP-EW240M2G2W

SGP-EW240M2G2W

Capacity

Cooling

kW

35.50

45.00

56.00

71.00

80.50

90.00

91.50

101.00

112..0

127.00

142.00

Heating 

STD

kW

40.00

50.00

63.00

80.00

90.00

100.00

103.00

113.00

126.00

143.00

160.00

Heating  Low temp*1

42.50

53.00

67.00

75.00

85.00

95.50

106.00

109.50

120.00

134.00

142.00

150.00

Hot water

12.00

16.00

20.00

25.00

24.00

28.00

32.00

32.00

36.00

40.00

45.00

50.00

Electricity

Cooling

kW

0.85

1.35

1.70

2.20

2.70

2.20

2.70

Heating

1.01

1.54

2.02

2.55

3.08

Gas consumption

Cooling

kW

24.50

31.60

38.30

60.90

49.00

56.10

63.20

62.80

69.90

76.60

99.20

121.80

Heating 

STD

kW

28.10

36.10

43.00

58.00

56.20

64.20

72.20

71.10

79.10

86.00

101.00

116.00

Heating 

LOW

36.80

47.30

56.40

64.90

73.60

84.10

94.60

93.20

103.70

112.80

121.30

129.80

COP

Cooling

1.40

1.37

1.41

1.14

1.40

1.38

1.37

1.41

1.39

1.41

1.25

1.14

Heating

1.37

1.35

1.43

1.34

1.37

1.36

1.35

1.41

1.39

1.43

1.38

1.34

AVE

1.39

1.36

1.42

1.24

1.39

1.37

1.36

1.41

1.39

1.42

1.31

1.24

Max COP (inc hot water) Cooling

1.87

1.85

1.92

1.54

1.87

1.86

1.85

1.90

1.89

1.92

1.69

1.54

Size

Height

mm

2,248

Width

1,800

1,800 + 100 (min distance) + 1,800 (in a straight installation)

Depth

1,000 (+60)

Weight

kg

790

820

850

1,580

1,610

1,640

1,670

1,700

Starter amperes

(A)

30

Piping connection

Gas

Inches (mm)

1 1/8 (28.58)

1 3/8 (34.92)

1 5/8 (41.27)

Liquid

1/2 (12.7)

5/8 (15.88)

3/4 (19.05)

Balance

3/8 (9.52)

Pipe fuel gas

R3/4 (bolt thread)

Pipe exhaust drain

ø25 rubber hose

Operation sound

dB(A)

57

58

62

60

61

63

65

Indoor/outdoor capacity ratio

50-180 %

50-130 %

Number of indoor connections

32

36

48

* In case of these combinations EGW190M2G2W is able to connect as W-multi instead of EW190M2G2w. 

* 1: Low temp condition: Outdoor temperature 2 C˚.

 

Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details. 

Please refer to tube sizing charts for pipe selections and pipe length parameters. 

Capacity Hot Water is available when outside ambient air temperature is above 7C˚.

Rear View

Front View

Left Side View

at least 2000

Service Clearances for installation

(Units: mm)

Rear

(refrigerant tubing)

Rear

(refrigerant tubing)

at

 le

as

60

0

at

 le

as

60

0

at

 le

as

10

00

at

 le

as

10

00

at least 

100

at least 

100

at least 

100

at least 

350

at least 

350

Front View

Front View

(Single-unit installation)

(Multi-unit series installation)

Gas refrigerant pipe (Gas tube)

ø25.4

ø28.58

ø12.7

Size (mm)

120

Model Type

150

190 and 240

ø15.88

ø9.52

ø28

ø28

ø28

G: R3/4

ø20

4 - ø20

4 - ø24

Rp3/4

Rp3/4

OD: ø25 Length: 200

1

Liquid refrigerant pipe (Liquid tube)

2

Refrigerant balance pipe (Balance tube)

3

Exhaust gas drain hose

4

Electrical power supply port

5

Inter-unit cable port

6

Fuel gas port

7

Condensation drain opening

8

Rain and condensation outlet

9

Engine exhaust outlet

10

Suspension holes

11

Anchor holes

12

Segmented display

13

Coolant intake (top)

14

Vent

15

Hot water intake

16

Hot water outlet

17

Cable inlet for interlock and the like

18

Top View

1800

22

48

400

10

14

(a

nc

ho

r p

itc

h)

1000

(anchor pitch)

10

14

12

12

1040

1000

ø736

1060

9

15

11

27

11

8

50

55

54

147

207

242

275

312

461

55

83

99

95

22

55

5

16

3

271

3

17

16

7

2

1

4

8

18

6

5

Содержание ECO G SGP-EGW190M2G2W

Страница 1: ...SANYO Air Conditioners The natural choice Gas Driven VRF M Series GAS DRIVEN VRF ELECTRIC VRF COMMERCIAL SPLIT SYSTEMS ROOM AIR CONDITIONERS HEATING SOLUTIONS ...

Страница 2: ... supply problems If you are short of electrical power gas heat pump could be the perfect solution Runs on gas and just needs single phase supply Enables the building s electrical power supply to be used for other critical electrical demands Reduces capital cost to upgrade power substations to run heating and cooling systems Reduces power loadings within a building especially during peak periods El...

Страница 3: ...re C Gas heat pump Electric heat pump Time axis in case of the same load Outside air temperature C Electric heat pump Gas heat pump Comparison of heating capacity Heating capacity Comparison of the start times for heating operation Room temperature C Gas heat pump Electric heat pump Time axis in case of the same load Outside air temperature C Electric heat pump Gas heat pump Comparison of heating ...

Страница 4: ...onsumption Cooling kW 24 50 31 60 38 30 60 90 49 00 56 10 63 20 62 80 69 90 76 60 99 20 121 80 Heating STD kW 28 10 36 10 43 00 58 00 56 20 64 20 72 20 71 10 79 10 86 00 101 00 116 00 Heating LOW 36 80 47 30 56 40 64 90 73 60 84 10 94 60 93 20 103 70 112 80 121 30 129 80 COP Cooling 1 40 1 37 1 41 1 14 1 40 1 38 1 37 1 41 1 39 1 41 1 25 1 14 Heating 1 37 1 35 1 43 1 34 1 37 1 36 1 35 1 41 1 39 1 4...

Страница 5: ... STD kW 48 7 43 0 76 80 84 80 97 40 101 00 Heating LOW 62 1 56 4 98 90 109 40 124 20 121 30 COP Air conditioning only Cooling 1 33 1 41 1 29 1 23 1 18 Heating 1 34 1 43 1 31 1 30 1 27 1 38 AVE 1 34 1 42 1 30 1 25 1 28 Max COP Inc generater hot water Cooling 1 78 1 81 1 80 1 78 1 69 Height Height mm 2 248 Width 1 800 1 800 100 Min distance 1 800 Depth 1 000 60 Weight kg 875 1 660 1 685 1 740 1 720 ...

Страница 6: ... 59 Nominal air flow Sound pressure 1 5 mts from the unit in free field Data referred to 50 C 80 RH OAT room condition 200 C 50 RH Data referred to 320 C 50 RH OAT room condition 260 C 50 RH The high efficiency low pressure loss total heat exchanger is made of specially treated paper to enable the unit to be as efficient as 76 during normal operation This allows system to recover both latent and s...

Страница 7: ...R74GXH56B SPW U095XH SPW UR94GXH56B SPW U125XH SPW UR124GXH56B SPW U165XH SPW UR164GXH56B SPW U185XH SPW UR184GXH56B SPW U255XH SPW UR254GXH56B SPW U365XH SPW UR364GXH56B SPW U485XH SPW UR484GXH56B SPW U605XH SPW UR604GXH56B DR Type Concealed Duct SPW DR254GXH56B SPW DR364GX H56B SPW DR484GX H56B SPW DR764GX H56B SPW DR964GX H56B K Type Wall Mounted Unit SPW K075XH SPW K095XH SPW K125XH KR Type Wa...

Страница 8: ...ON OFF Mode setting Fan speed setting Temperature setting Air flow direction Permit Prohibit switching Weekly programme 1 Setting is not possible when a remote control unit is present Use the remote control for setting Centralised control systems Operation with various function from central station Only ON OFF operation from central station Simplified charge ratio for each tenant Touch screen pane...

Страница 9: ... to present only general particulars and shall not form any part of the contract For full installation details please contact your SANYO distributor Rating Conditions The cooling and heating capacities are based on the following conditions Cooling Indoor temperature 27 C DB 19 C WB Outdoor temperature 35 C DB 24 C WB Heating Indoor temperature 20 C DB Outdoor Temperature 7 C DB 6 C WB Printed usin...

Отзывы: