7. ELECTRICAL DATA
●
Electrical Characteristics
CMH1822 / KMH0922 (
×
1)
Remarks:
Rating conditions are:
Cooling: Outside air temperature 95°F DB/ 75°F WB
Indoor unit entering air temperature 80°F DB/67°F WB
Heating: Outside air temperature 47°F DB/ 43°F WB
Indoor unit entering air temperature 70°F WB
Performance at
Indoor Unit
Outdoor Unit
Complete Unit
230/208V – 1ø – 60Hz
Fan Motor
Max. Heat
Fan Motor
Compressor
Heat-pump
Max. Heat
Cooling
Rating
A
0.15 / 0.14
—
0.52 / 0.52
3.43 / 3.64
4.1 / 4.3
—
Conditions
W
34 / 29
—
116 / 104
750 / 737
900 / 870
—
Heating
Rating
A
0.15 / 0.14
4.35 / 3.93
0.52 / 0.52
3.43 / 3.64
4.1 / 4.3
8.45 / 8.23
Conditions
W
34 / 29
1,000 / 818
116 / 104
750 / 737
900 / 870
Locked-Rotor Amperes
A
0.19 / 0.18
—
0.71 / 0.64
27
—
—
Remarks:
Rating conditions are:
Cooling: Outside air temperature 95°F DB/ 75°F WB
Indoor unit entering air temperature 80°F DB/67°F WB
Heating: Outside air temperature 47°F DB/ 43°F WB
Indoor unit entering air temperature 70°F WB
Performance at
Indoor Unit
Outdoor Unit
Complete Unit
230/208V – 1ø – 60Hz
Fan Motor
Max. Heat
Fan Motor
Compressor
Heat-pump
Max. Heat
Cooling
Rating
A
0.30 / 0.28
—
0.52 / 0.52
7.38 / 7.90
8.2 / 8.7
—
Conditions
W
68 / 58
—
116 / 104
1,636 / 1,618
1,820 / 1,780
—
Heating
Rating
A
0.30 / 0.28
8.70 / 7.86
0.52 / 0.52
6.68 / 7.10
7.5 / 7.9
16.2 / 15.76
Conditions
W
68 / 58
2,000 / 1,636
116 / 104
1,456 / 1,428
1,640 / 1,590
3,640 / 3,226
Locked-Rotor Amperes
A 0.19
×
2 / 0.18
×
2
—
0.71 / 0.64
27
×
2
—
—
CMH1822 / KMH0922 (
×
2)
92-144 S/M (Basic) 00.12.13 10:32 AM ページ 10
Содержание CMH1822
Страница 2: ......
Страница 3: ...ii WM 700700 SERVICE MANUAL CMH1822 KMH0922 2 Basic Information ...