4.5 - exhibit LF (cont.)
4.5.2 - Field wiring
Fig. 23 - typical electric field connection diagram
For ALArM bUZZEr
For PUrGE INDICAtIoN
For DILUtIoN INDICAtIoN
FEEDbACK SIGNAL
rUN/StoP SIGNAL For CooLING
toWEr FAN
rUN/StoP SIGNAL For CooLING
WAtEr PUMP
rUN/StoP SIGNAL For CHILLED
WAtEr PUMP
For ALArM INDICAtIoN
For StoP INDICAtIoN
For oPErAtIoN INDICAtIoN
rEMotE CHECK SIGNAL
PrE-ALArM SIGNAL
CooLING WAtEr PUMP INtErLoCK
CHILLED WAtEr PUMP INtErLoCK
tE
r
MINAL S
tr
IPS
o
N
tHE C
o
N
tro
L P
ANEL
to
P
o
WE
r
S
o
U
r
CE
ter
MINAL
str
IP
s
o
N
t
H
e
C
o
N
tro
L P
AN
e
L
(1)
continuous
(2)
pulse
(3)
pulse
(4)
continuous
(5)
pulse
FIELD WI
r
ING C
o
NNEC
tIo
N
(1)
Pr
ovide power supply wiring and earthing
Connect wir
e between chiller contr
ol panel and earth on site.
the chiller has a cir
cuit br
eaker
. Please connect power supply cable to the terminal block pr
ovided.
Earthing r
esistance: Should be determined fr
om local r
egulations
Earthing cable: annealed copper wir
e (please use a cable of the same cr
oss section as the power
supply cable).
re
M
ote
s
IGNAL
Chiller can be operated by the following five signal types.
(1)
Volt-fr
ee normally open contact (a) for start & stop (24 V d.c. 10 mA):
Wir
e terminal 324 and 323, connect 170 and 326.
(2)
Volt-fr
ee normally open contact (a) for start (24 V d.c. 10 mA):
Wir
e terminal 324 and 325, connect 170 and 326.
Volt-fr
ee normally open contact (a) for stop (24 V d.c. 10 mA):
Wiring the terminal 325 and 323.
(3)
Volt-fr
ee normally open contact (a) for start (24 V d.c. 10 mA):
Wir
e terminal 324 and 325, connect 170 and 326.
Volt-fr
ee normally closed contact (b) for stop (24 V d.c. 10 mA):
Wir
e terminal 325 and 323.
(4)
Continuous signal of 24 V a.c./d.c. for start & stop (initial setting):
Wir
e terminal 324 and 326 (these terminals ar
e non-polarized)
(5)
Pulse signal of 24 V a.c./d.c. for start:
Wir
e terminal 324 and 326 (these terminals ar
e non-polarized)
Pulse signal of 24 V a.c./d.c. for stop:
Wir
e terminal 325 and 326 (these terminals ar
e non-polarized)
24 V a.c./d.c.
24 V a.c./d.c.
For Hot WAtEr SHUtoFF VALVE
rUN/StoP SIGNAL For Hot
WAtEr PUMP
24
V
d
.c
. 1
0 m
A
For steam contr
ol
valve positioner
(field-supplied)
DC 4 - 20 mA
CVP
o
pen
Closed CMS (24 V a.c.)
Pot: 135
o
hm
For steam contr
ol valve motor
(field-supplied)
UL: 208
V/460
V
-3 ph-60 Hz
CE: 400
V
-3 ph-50 Hz
FIELD-SUPPLIED P
ANEL
o
pen
Closed