10. Test Run
10-1. Preparing for Test Run
Before starting the air conditioner, check the
following:
(1)
Remove all loose matter from the cabinet espe-
cially metal filings, bits of wire, and clips.
(2)
Connect the control wiring correctly and tighten
all electrical connections.
(3)
Remove the protective spacer for the compressor
used for transportation.
(4)
For “CL” models only:
Connect the power to the unit for at least 5
hours before starting the compressor. The
bottom of the compressor should be warm to the
touch and the crankcase heater around the feet
of the compressor should be hot to the touch.
(5)
Open both the wide and narrow tube service
valves after air purge.
(6)
Remove the transportation cardboard protection
for the indoor fan.
Operation
selector
Air filter
Air intake grille
0984_M_I
TEST OFF ON
Air intake grille
Fig. 10-1
OFF
TEST
ON
OPR
TIMER
REMOTE CONTROL receiver
OPERATION
lamp
TIMER
lamp
Operation
selector
Flap
0985_M_I
Fig. 10-2
10-2. Performing Test Run
Be careful since the fan will
start when performing Test
Run.
(1)
For TS and XS models, the Operation Selector is
located on the electrical component box inside
the indoor unit. To access the Operation Selector,
press the two latches of the air intake grille in the
direction of the arrow to open the grille. Open the
air intake grille downward. (Fig. 10-1)
For KS model, Operation Selector is located on
the right side of the air discharge. (Fig. 10-2)
(2)
Set the Operation Selector to the “Test” position.
The air conditioner will start running.
(3)
Let the unit run for about 30 minutes and check
that the unit operates normally.
(4)
After the Test Run, be sure to reset the Operation
Selector to the “ON” position for normal opera-
tion. The air conditioner continues to run .
(5)
Referring to the Operatiing Instructions, select the
Cooling mode and press the ON / OFF operation
button on the remote control unit, to confirm
remote control unit operation.
Set the Operation Selector at the “ON” position.
Otherwise the unit will stop or will not run correctly.
CAUTION
Important