How to Test Run the Air Conditioner
After turning on power to the air conditioner, use the remote
controller and follow the steps below to conduct the test run.
(1) Set the remote controller in Test Run mode.
(Fig. 59a)
a) Press and hold the ION button.
b) Then press and hold the 1HR TIMER button.
c) At the same time, press the ACL (reset) button once.
Use a pointed object such as the tip of a pen to press
the ACL button.
• After a few seconds, “
” appears and “oP-1” blinks in
the remote controller display area.
(Fig. 59b)
d) Release the 1HR TIMER button.
e) Release the ION button.
(2) Start Cooling mode test run by pressing the ON/OFF
operation button of the remote controller. (Fig. 59a)
• This starts the fan producing uncooled forced air with
the 4 indicator lamps (OPERATION lamp, TIMER
lamp, QUIET lamp, and ION lamp) on the main unit
blinking. (Fig. 59c)
• After 3 minutes, the system shifts into cooling opera-
tion, and cool air will start to be felt. Cool mode test
run is unaffected by the room temperature.
(3) Press the ON/OFF operation button of the remote con-
troller again to stop the test run. (Fig. 59a)
(4) Finally press the ACL (reset) button of the remote con-
troller to release it from Test Run mode to return to nor-
mal mode. (Fig. 59a)
• “
” and “oP-1” will disappear from the remote con-
troller display area.
Troubleshooting:
In the event that the green “Operation Light” is blinking
upon powering up the system, an error condition exists.
In this case, refer to the self-diagnostics procedure
on the inside of the front cover.
After the test run is completed, be sure to press the
ACL (reset) button to return to normal mode. The
air conditioner will not operate correctly if this is not
done.
IMPORTANT
NOTE
Fig. 59a
Fig. 59b
Fig. 59c
A
1HR.
TIMER
ON/OFF
operatio
n
ACL
(Re
s
et)
ION
b
u
tto
n
b
u
tto
n
b
u
tto
n
b
u
tto
n
OPERATION lam
p
TIMER lam
p
QUIET lam
p
ION lam
p
07-105 KS0971-1271 5/10/07 9:17 AM Page 23
Содержание C0971
Страница 17: ...3 DIMENSIONAL DATA Indoor Unit KS0971 KS1271 Unit inch mm 17 ...
Страница 57: ...INSTRUCTION MANUAL KS0971 C0971 CL0971 KS1271 C1271 CL1271 OI 852 6 4180 803 00 2 APPENDIX A A 1 ...
Страница 81: ...INSTALLATION INSTRUCTIONS KS0971 C0971 CL0971 KS1271 C1271 CL1271 II 852 6 4189 991 00 6 APPENDIX B A 2 ...