21
6. Air Purging
Air and moisture remaining in the refrigerant system
have undesirable effects as indicated below. Therefore,
they must be purged completely.
G
pressure in the system rises
G
operating current rises
G
cooling (or heating) efficiency drops
G
moisture in the air may freeze and block capillary tubing
G
water may lead to corrosion of parts in the refrigerant
system
I
Air Purging with a Vacuum Pump (for Test Run)
(1) Check that each tube (both narrow and wide tubes)
between the indoor and outdoor units have been
properly connected and all wiring for the test run
has been completed. Note that both narrow and
wide tube service valves on the outdoor unit are
kept closed at this stage.
(2) Using an adjustable wrench or box wrench, remove
the valve caps from the service valve on both nar-
row and wide tubes.
(3) Connect a vacuum pump and a manifold valve (with
pressure gauges) to the service port on the wide
tube service valve. (Fig. 57)
(4) With the “Lo” knob of the manifold valve open, run
the vacuum pump. The operation time for the vacu-
um pump varies with tubing length and the capacity
of the pump. The following table shows the amount
of time for evacuation:
Table 7
Hi
Lo
I
n
door
un
it
O
u
tdoor
un
it
Ma
n
ifold valve
(Excl
us
ively for R410A)
Pre
ssu
re
g
a
ug
e
Vac
uu
m p
u
mp
Char
g
i
ng
ho
s
e
(Excl
us
ively for R410A)
Vac
uu
m p
u
mp adapter
(Excl
us
ively for R410A)
(with rever
s
e flow preve
n
tio
n
)
Fig. 57
CAUTION
Be sure to use a manifold valve
for air purging. If it is not avail-
able, use a stop valve (field sup-
ply) for this purpose. The “Hi”
knob of the manifold valve must
always be kept closed.
The required time in Table 7 is calculated based on the
assumption that the ideal (or target) vacuum condition
is around 10 mmHg abs.
NOTE
Required time for evacuation when
100 liter/h vacuum pump is used
If tubing length is
If tubing length is
less than 33 ft. (10 m)
more than 33 ft. (10 m)
10 min. or more
15 min. or more
CAUTION
The service port on the wide tube
service valve uses a Schrader core
valve to access the refrigerant sys-
tem. The valve core is similar to
those used in automobile tires.
Therefore, be sure to use a vacuum
hose connector which has a push-
pin inside.
To prevent other refrigerants from being mistakenly
charged to units which use R410A, the size of the
charge port on the service valve is different from the
one for other refrigerant types. For servicing such as
recharging, the specified charging hose, manifold and
vacuum pump adapter (with reverse flow prevention)
for R410A must be used.
NOTE
07-105 KS0971-1271 5/10/07 9:17 AM Page 21
Содержание C0971
Страница 17: ...3 DIMENSIONAL DATA Indoor Unit KS0971 KS1271 Unit inch mm 17 ...
Страница 57: ...INSTRUCTION MANUAL KS0971 C0971 CL0971 KS1271 C1271 CL1271 OI 852 6 4180 803 00 2 APPENDIX A A 1 ...
Страница 81: ...INSTALLATION INSTRUCTIONS KS0971 C0971 CL0971 KS1271 C1271 CL1271 II 852 6 4189 991 00 6 APPENDIX B A 2 ...