4. Troubleshooting summary table 

 

Problem 

Possible causes 

Try …

 

On/Off button 

internal LED is 

not lit 

-

 

There is no power to the 

electrical outlet 

-

 

The On/Off button is not 
pressed ON 

-

 

Power cord is damaged 

-

 

Circuit board is damaged or 

defective 

-

 

Test the outlet to make sure there is 

power by plugging in another 

electrical appliance 

-

 

Press the switch to the ON position 

-

 

Check the power cord for damage 
and replace if damaged (contact 

Sanuvox) 

-

 

Visually inspect the circuit board and 

look for damage/burn marks 

-

 

Contact Sanuvox to replace circuit 

board and thermistor together 

Status LED is 

Orange 

-

 

The lamp has reached its 3 year 

lifespan 

-

 

Get a genuine replacement lamp and 

reset the counter to 3 years (refer to 
reset procedure) 

Status LED is Red 
with 2 flashes 

-

 

Connection issues between the 
lamp and the ballast 

-

 

Connection issues between the 
ballast and circuit board (power 

supply) 

-

 

Defective lamp 

-

 

Defective ballast 

-

 

Verify that the connections between 
lamp and ballast (also ballast and 

circuit board) are secured 

-

 

Test lamp continuity (refer to lamp 

test procedure) 

-

 

Contact Sanuvox to replace UV lamp 

-

 

Contact Sanuvox to replace ballast  

 

Status LED is Red 
with 3 flashes 

-

 

Thermistor is not connected 

-

 

Thermistor is damaged or 

defective 

-

 

Check thermistor connections 

-

 

Contact Sanuvox to replace 

thermistor 

Status LED is Red 

with 4 flashes 

-

 

Thermistor is shorted 

-

 

Contact Sanuvox to replace 

thermistor 

Status LED is Blue 

with heartbeat 

-

 

Airflow detection activated, 

waiting for airflow 

-

 

Change the fan setting for higher 

speed 

-

 

Reposition the SRMax in the 

ductwork where the airflow is 
unobstructed 

-

 

By-pass the thermistor (refer to 
thermistor by-pass procedure) 

Status LED is 
blank 

-

 

Start-up not completed 

-

 

Defective LED 

-

 

Wait 5-10 seconds for start-up to 
complete 

-

 

Contact Sanuvox to replace LED 

Lamp burned 

before the 3 years 
elapsed 

-

 

Over cycling of the UV lamp due 

to excessive start/stop of the 
variable speed fan 

-

 

Contact Sanuvox to replace lamp and 

by-pass thermistor (refer to 
thermistor by-pass procedure) 

 

 

Содержание SRMax

Страница 1: ...ontreal Canada www sanuvox com July 2018 Contents 1 Tools required for troubleshooting 1 2 Identifying internal components inside SRMax 1 3 List of parts for replacement 2 4 Troubleshooting summary table 3 5 Step by step instructions 4 5 1 Open the SRMax ballast box 4 5 2 Test UV lamp continuity 4 5 3 By pass circuit board test ballast and UV lamp together 5 5 4 By pass thermistor 6 5 5 Resetting ...

Страница 2: ...5 16 nutdriver 2 Identifying internal components inside SRMax To access internal components of the SRMax remove cover by following the Step by step instructions Circuit board Reset button Circuit board to ballast connection Ballast to lamp connection Ballast Thermistor ...

Страница 3: ...2 3 List of parts for replacement Sanuvox PN Description BST120 240GL Ballast MSCELC20 1 Circuit board MSCTER2 Thermistor LMPRGXJ65 6 5in regular intensity UV lamp ...

Страница 4: ...efective ballast Verify that the connections between lamp and ballast also ballast and circuit board are secured Test lamp continuity refer to lamp test procedure Contact Sanuvox to replace UV lamp Contact Sanuvox to replace ballast Status LED is Red with 3 flashes Thermistor is not connected Thermistor is damaged or defective Check thermistor connections Contact Sanuvox to replace thermistor Stat...

Страница 5: ...e SRMax out from the ductwork by removing the 4 screws located on the cover 4 corners that hold it to the frame 2 Place the SRMax down on a flat surface remove the 4 screws that attach the cover to the ballast box and pull the cover off 5 2 Test UV lamp continuity Step 1 Take the SRMax out from the ductwork by removing the 4 screws located on the cover 4 corners that hold it to the frame ...

Страница 6: ...oard test ballast and UV lamp together Step 1 Open the SRMax ballast box Refer to instructions above 2 Unplug from the circuit board the line black from the power cord See picture to the left Insert black wire from the power cord into connector identified Bypass See picture to the right 3 Place the unit on the ground and make sure that you don t have direct line of sight with the lamp Plug the pow...

Страница 7: ...he unit ON click the Reset button once By doing so you ll see the status LED turn Blue meaning the airflow detection is activated By clicking again within 5 seconds LED will turn White meaning that airflow detection is deactivated 5 5 Resetting lamp timer Step 1 Open the SRMax ballast box Refer to instructions above 2 Plug in the SRMax to a power source press the switch to the ON position and wait...