Functions
No.
Label
Status display
Lit
Not lit
Blink
Fast blink
①
BACK UP
UPS input power status,
UPS operation status
AC input power error,
Battery back up
AC input power
normal
AC input power error,
UPS output stop
-
②
OUTPUT
UPS output power status
Output power supply OFF
Power supply
bypassing
During ON/OFF delay
operation of output line
control operation *2
③
INVERTER
UPS output power status
UPS power supply
OFF
-
-
④
BYPASS
UPS output power status
Bypass power supply OFF
-
-
⑤
BATT.LOW
Battery status
Battery voltage low,
Battery charge is 25 %
or less
Battery power
normal
Battery exhausted
-
⑥
25
Load level 25%
Load 25% or more
Load under 25%
-
-
⑦
50
Load level 50%
Load 50% or more
Load under 50%
-
-
⑧
75
Load level 75%
Load 75% or more
Load under 75%
-
-
⑨
100
Load level 100%
Load 100% or more
Load under 100%
*1
-
⑩
LOAD (%)
O.L.
Overload display
Load 105% or more
Load under 105%
-
-
⑪
ALARM
Alarm
Failure detected
No failure
-
-
⑫
ON/OFF
Operation status
Output power supply OFF
Power supply
bypassing
During ON/OFF delay
operation of Linked
operation *3
⑬
ON/OFF
UPS ON/OFF switch
⑭
BATT.TEST
Battery test
Result: Normal
-
Testing
↓
Blinking speed changes.
Result: Error
⑮
BATT.TEST
Battery test operation
⑯
CLEAR
Stop buzzer, clear result of battery test
The LEDs on the control panel are
described as “Green ON/OFF” or “Red ALARM”.
The LEDs state are indicated as follows;
: LED lights. : LED blinks.
Indications of LED in this manual
*1. For about 5 seconds after MAIN MCCB is set to “ON”, the LOAD “Green 100” blinks.
*2. Blinks during delay operation when output line control is being performed with an optional outlet box. The blinking is
faster than the blinking which indicates UPS bypass power supply.
*3. Blinks during delay operation when linked operation is being performed with an optional remote switch and optional
linked operation cable(s). The blinking is faster than the blinking which indicates UPS bypass power supply.
Note
⑪
②
③
④
⑯
⑮
⑭
⑩
⑨
⑧
⑦
⑥
①
⑫
⑬
⑤
Содержание A11H
Страница 1: ...Instruction Manual 120V Model 2kVA 3kVA Uninterruptible Power Supply M0008068...
Страница 70: ...Blank page...
Страница 71: ...Blank page...
Страница 72: ......