1. I NTRODUCTION
2
1.3 Product standard
This product complies with the following criterion levels:
EMC:
Safety
I E C 62040-1-1
1.4 Technical specifications
INPUT
Connection: Hardwired, three-phase (3
ϕ
4W + G) or single phase (1
ϕ
2W + G); “N” must
be installed
Voltage range: three-phase (204~520)VAC/single-phase (118~300)VAC
Frequency range: (46~54) for 50Hz or
(56~64) for 60Hz
Bypass voltage range: three-phase (140~457)VAC/single-phase (80~264) VAC
Power factor: > 0.98
OUTPUT
Connection: Hardwired, single phase (1
ϕ
2W + G)
Voltage: 220/230/240 x (1
±
2%) VAC (Default 220VAC) or
2 sets of 110/115/120 x (1
±
2%) VAC ( Option. With down-voltage ISO
Transformer)
Frequency : Synchronized to mains input or 50/60
±
0.2Hz in battery mode
Power factor: 0.7 lag
Overload capacity: 110%~130%(
±
5%) transfer to bypass mode in 30sec
130%(
±
5%) transfer to bypass mode in 2sec
Nominal Battery voltage: 120VDC
Nominal Charge Voltage: 137VDC
Noise: < 62dB
Operating Environment
Operating temperature: 0
℃
~40
℃
Ambient humidity: 20%~90%
Altitude: 0 – 5000m
Storage temperature: -25
~55
℃
℃
EMI
EMS
: 61000-4-2(ESD) GB/T17626.2 Electrostatic discharge immunity
61000-4-3(RS) GB/17626.3 Radiated,radio-frequency,electro
magnetic field
immunity
61000-4-4(EFT) GB /17626.4 Electrical fust transient/burst
immunity
61000-4-5(SURGE) GB/17626.5 Surge
immunity
IEC
IEC62040-2 Class A
GB7260.2 Class A