7. OPERATION AND MAINTENANCE
22
3) Enter the password (default is “1234”) 4) After pressing
↵
↵
↵
↵
by using
▲
or ▼
5) Select REDUNDAN and press
↵
↵
↵
↵
6) If the number of the redundancy module
to set up the number of the
is set to “0” (as default), that means
UPS-Module for redundancy
warning of preset redundancy level is
not activated.
7)
Turn on the UPS system in the battery mode, please make sure that the battery pack(s)
has/ have been connected correctly before switching the “system startup switch” from
OFF to ON. The LCD display menu is similar to the one in the utility power mode. Perform
the UPS system ON/OFF in battery mode according to the menu display. If you do not
turn on the UPS system within 15 seconds, the UPS system will automatically power off
*
The redundancy setup will be valid after
leaving the redundancy setup menu. If you
want the UPS system to notify you when the
number of redundant UPS-Module is less than
a specified level, enter a redundancy level for
the UPS system. This setting only affects the
warning alarm, the UPS system continues to
operate even if the parameter is left at default
of “0” due to increment of the output load or
removing the UPS-Module.
* Select “
↵
“ or “ESC“ will return to the
setup menu.
USER KEY: *****
SERVICE ONLY: *****
SETUP
SELFTEST TIME
RE-START REDUNDAN
PASSWORD VOLTAGE
PHONE
SETUP REDUNDANCE
TOTAL NUM: 3
REDUND NUM: 1
MAX POWER CURRENT
SETTING: 8kVA/5.6kW
WARNING:
CURRENT SETTING IS
NO REDUNDANCY, OK?
YES
NO