4
Santa Fe Oasis105 Installation & Operation Instructions
Santa-Fe-Products.com | 800.533.7533
Items Included in Box:
• Santa Fe Oasis105 Dehumidifier
• Santa Fe Oasis105 Dehumidifier Leveling Feet
• 8’ Drain Hose and Drain Adapter
• MERV-13 Filter (Dimensions: 1” x 12” x 14”)
Important Precautions
• Do not install the Santa Fe Oasis105 dehumidifier with the intake or exhaust of the unit within 14” of a wall or other
obstruction. Avoid directing the discharge air at people. The dehumidifier should be used in the upright position
• Do not place the unit where curtains or debris can be drawn into the intake and restrict airflow.
• The device is designed to be installed indoors in a space that is protected from rain and flooding.
• Do not operate in standing water or place the unit near open water. If used near a water source; be certain there is no
chance the unit could fall into the water or get splashed and that it is plugged into a dedicated circuit and Ground Fault Circuit
Interrupter (GFCI) protected outlet.
• Install the unit with enough space to access all sides for maintenance and service. The top panel needs to be removed in
order to do repairs.
• DO NOT use the dehumidifier as a bench or table.
• DO NOT place the dehumidifier directly on structural building members without vibration absorbers or unwanted noise may
result. Place the Santa Fe Oasis105 dehumidifier on supports to raise the base of the unit.
Location Considerations
• Locate the dehumidifier near a suitable drain
(8’ drain hose included). Allow for proper
drainage and routing of needed drain pipes.
• Locate the dehumidifier in an area where the
cord’s length (9’) easily reaches a 115 VAC
electrical outlet with a minimum of a 15 Amp
circuit capacity.
• The unit is designed to operate while level. If
the unit is placed on an unlevel surface, refer
to section below (Installing Leveling Feet).
Failure to level the unit may result in leakage or
improper drainage.
• The unit should be suspended with a hang kit
from the floor joists if there is any possibility
of flooding. A flooded unit is not covered by
warranty. Feet will be installed as a securing
measure after the hang kit is put on the
dehumidifier. DO NOT hang the Santa Fe
Oasis105 dehumidifier from its’ cabinet.
• Allow sufficient clearance to handle the unit’s overall dimensions as well as any optional return and supply ductwork to the unit.
• Allow sufficient clearance for filter removal and to prevent airflow obstruction.
Installing Leveling Feet
• Lay down a protective pad (pillow, blanket, etc.).
• Carefully turn unit onto side.
• Install leveling feet and adjust to the desired position to ensure unit is level for proper drainage.
• Carefully bring unit to upright position.
• Wait a minimum of 10 minutes before operating.
Dehumidifier Set Up
9' POWER CORD
TOP VIEW
MINIMUM
CLEARANCE
FOR PROPER
AIR FLOW OF
RETURN AIR
2"
RETURN AIR
SUPPLY AIR
A
B
PRIMARY
DRAIN
ACCESS
MINIMUM CLEARANCE
FOR PROPER AIR FLOW
OF SUPPLY AIR
B
14"
6"
A
MINIMUM
CLEARANCE
FOR FILTER
REMOVAL
SECONDARY
DRAIN
ACCESS
CONTROL
PANEL
Содержание OASIS105
Страница 22: ...Santa Fe Products com 800 533 7533...