Santa Fe Oasis105 Installation & Operation Instructions

Santa-Fe-Products.com | 800.533.7533

 

CAUTION!

DO NOT CONNECT WITH A STATIC PRESSURE GREATER THAN OR EQUAL TO +1.0 WG.  

CONTACT TECHNICAL SUPPORT AT (800) 533-7533 FOR ADDITIONAL DETAILS.

Ducting Considerations:

•  All flexible ducting connected to the Santa Fe Oasis105 should be UL listed.
•  A short piece of flexible ducting on all Santa Fe Oasis105 duct connections is recommended to reduce 

noise and vibration transmitted to rigid ductwork in the structure.

•  Use a minimum 10" diameter round or equivalent rectangular duct for total duct lengths of up to 25'. 
•  Grills or diffusers on the duct ends must not excessively restrict airflow.
•  A length of 8” or more of insulated flex duct or any other vibration isolating material on the outlet of the 

Santa Fe Oasis105 will reduce air noise from the blower.

•  Effective dehumidification may require that ducting be branched to isolated, stagnant air flow areas. 

When ducting to two or three areas, use 8" or larger diameter branch ducting. When ducting to four or 

more areas, use 6" or larger diameter branch ducting. Provisions must be made to provide airflow from 

supply locations to the central return location. Proper air distribution is important to ensure even humid-

ity control and heat distribution throughout the structure.

•  DO NOT locate the return in a bathroom or a kitchen.

Decide Where To Place The Unit.

 

  CAUTION! ALLOW FOR ENOUGH SPACING TO PROPERLY ROUTE THE RETURN AND 

SUPPLY CONNECTION

a.  If You Place On Floor 

Attach leveling feet and use 

vibration pads and/or risers.

b.  If You Hang Dehumidifier 

Use 2 Brackets

*

 Per Unit. 

*

 Brackets sold separately.

Choose Weather To Place On Floor Or Hang Dehumidifier. 

  CAUTION! INTERNAL STOPS LIMIT FEET HEIGHT. DO NOT TIGHTEN FEET BEYOND THE 

RESISTANCE PROVIDED BY STOPS.

Example Of Hanging Option:

Ducting To HVAC Systems

DEHUMIDIFIERS

*

 RECOMMEND 4” OFF GROUND 

*

 NOTE: LEVELING FEET HOLD BRACKET IN PLACE

Return and supply duct collars are optional accessories for the Santa Fe Oasis105 and not included with the unit.

Содержание OASIS105

Страница 1: ...tile and energy efficient dehumidifier the Santa Fe Oasis105 is perfect for a wide range of applications including whole home basements attics and crawl spaces It features onboard digital controls var...

Страница 2: ...rain Installation 5 Operation 6 Controller Instructions 6 Control Functions 6 Modes of Operation 7 Using Onboard Control 7 Using Remote Terminal Control 7 Terminal Block Control Operations 7 Air Filtr...

Страница 3: ...or use as a shelf or table Before leaving the unit unattended ensure children do not have access to the equipment Do not allow children to play with or near the unit or in its air flow The unit is de...

Страница 4: ...Location Considerations Locate the dehumidifier near a suitable drain 8 drain hose included Allow for proper drainage and routing of needed drain pipes Locate the dehumidifier in an area where the co...

Страница 5: ...y Drain Port Secondary Drain Port End View PVC Trap Use care to keep the hose as flat to the floor as possible Be sure the hose is not kinked or otherwise restricted so water can pass through the hose...

Страница 6: ...tor When lit indicates a filter change is needed 7 Filter button Press Filter button after filter is changed to reset 8 Dark Mode indicator When lit indicates unit is in Dark Mode 9 Dark Mode button P...

Страница 7: ...4 but less than 1 0 of static resistance Press and Hold the FAN button for 3 seconds this will enter High Override mode this changes the High setting Press the up arrow to 99 in order to operate the...

Страница 8: ...ulling on the top of the filter frame Step 2 Replacing the Filter Angle the bottom of the MERV 13 filter and gently slide the filter into the filter slot Do not force If resistance is felt check align...

Страница 9: ...Place dehumidifier in a central location that does not restrict the airflow of the air intake and air outlet 3 The dehumidifier must be installed on a level floor to ensure water drains out of the uni...

Страница 10: ...not included with the unit Attaching Duct Collars Return Air Inlet A 10 diameter duct collar and a front panel are attached to the unit Supply Air Outlet Two 10 diameter duct collars attach to the out...

Страница 11: ...assive grill will prevent the unfinished room from being placed under a negative pressure and also allow the dehumidifier to focus on keeping the unfinished area dry as well The onboard dehumidistat c...

Страница 12: ...ted stagnant air flow areas When ducting to two or three areas use 8 or larger diameter branch ducting When ducting to four or more areas use 6 or larger diameter branch ducting Provisions must be mad...

Страница 13: ...th a backdraft damper If the existing system has multiple returns instead of installing a dedicated return to the Santa Fe Oasis105 it is possible to select one to disconnect from the existing HVAC sy...

Страница 14: ...t the supply of the dehumidifier to the air supply of the HVAC system with a backdraft damper Optional Duct the supply of the Oasis105 to a 10 x 10 x 10 tee damper with a gravity draft damper adjusted...

Страница 15: ...static requires HI fan setting Anything greater than 0 7 of static requires HI override 99 Anything greater than 0 9 is not recommended HVAC Supply Oasis105 Supply Backdraft Damper Air Handler Option...

Страница 16: ...n Install a 6 insulated duct from outside teeing into the 8 return duct of the Ultra Series Dehumidifier to provide outdoor air ventilation optional The supply of the Oasis105 Dehumidifier should be d...

Страница 17: ...tes every hour Dehumidifier will not operate until incoming air dew point reads above 40 F No E3 Low refrigerant Evaporator coil temp is too high during extended operation Dehumidifier will go into lo...

Страница 18: ...r will circulate air for 15 minutes every hour Dehumidifier will not operate until incoming air temp reads above 40 F No E8 Communication from power board is not being received 1 There is a cable conn...

Страница 19: ...in an area that may become wet a GFCI protected circuit is recommended The unit should not be used in areas prone to flooding Consult local electrical codes for any further information An optional rem...

Страница 20: ...any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Respon...

Страница 21: ...allation Operation Instructions Register your product using the serial number and part number above at www thermastor com registration WARRANTY WARRANTY REGISTER YOUR PRODUCT PART NUMBER SERIAL NUMBER...

Страница 22: ...Santa Fe Products com 800 533 7533...

Отзывы: