background image

Blower does not run with fan switch in either position. 
Compressor runs briefly but cycles ON & OFF.

1.  Loose connection in blower circuit (see Fig. 2).
2.  Obstruction prevents impeller rotation.
3.  Defective blower.
4.  Blower switch defective.

Evaporator coil frosted continuously, low dehumidifying 
capacity.

1.  Defrost thermostat loose or defective (Sec. 5.8).
2.  Low refrigerant charge.
3.  Dirty air filter or air flow restricted.

5.4 Refrigerant Charging

If the refrigerant charge is lost due to service or a leak, a new 
charge must be accurately weighed in. If any of the old charge is 
left in the system, it must be removed before weighing in the new 
charge. Refer to the unit nameplate for the correct charge weight 
and refrigerant type.

5.5 Blower Replacement

The centrifugal blower has a PSC motor and internal thermal 
overload protection. If defective, the complete assembly must be 
replaced.
1.  Unplug the power cord.
2.  If an outlet duct is connected to the unit, remove it.
3.  Remove the cabinet side.
4.   Remove the 4 screws holding the electrical box located next to 

the blower.

5.   Disconnect the blower leads. Black from the blower switch, 

and white from the run capacitor.

6.   Unbolt the blower capacitor from the blower motor (required 

for removal clearance).

7.   Remove the nuts & bolts holding the blower outlet flange to 

the cabinet end and remove the blower.

8.   Reassembling with the new blower is the above procedure 

reversed.

5.6 Compressor/Capacitor Replacement

This compressor is equipped with a two terminal external overload 
run capacitor, but no start capacitor or relay (see Fig. 2).

 

CAUTION!

 

ELECTRIC SHOCK HAZARD: Electrical power must be present 
to perform some tests; these tests should be performed by a 
qualified service person.

5.6A Checking Compressor Motor Circuits

Perform the following tests if the blower runs but the 
compressor does not with the blower switch OFF and the 
humidity control ON.

1.   Unplug the unit, remove the cabinet side (with two screws 

in center) and the electrical connection cover on the 
compressor top.

2.   Plug in the unit and turn the humidity control to ON. Check 

for 110 volts from compressor terminal R to overload 

terminal 3 using an AC voltmeter. If voltage is present, go 
to step 3. If no voltage, the high pressure control or relay 
are open or there is a loose connection in the compressor 
circuit. Test each component for continuity; see the 
appropriate section if a defect is suspected.

3.   Unplug the unit, then disconnect the red and yellow wires 

from compressor terminals R & S. Using an ohmmeter, 
check continuity between the points listed below.

4.   Compressor terminals C and S: No continuity indicates an 

open start winding. The compressor must be replaced. 
Normal start winding resistance 3 to 7 ohms.

5.   Compressor terminals C and R: No continuity indicates 

an open run winding. The compressor must be replaced. 
Normal run winding resistance is .5 to 2 ohms.

6.   Compressor terminal C and overload terminal 1: No 

continuity indicates a defective overload lead.

7.   Overload terminals 1 and 3: If there is no continuity, the 

overload may be tripped. Wait 10 minutes and try again. 
If there is still no continuity, it is defective and must be 
replaced.

8.   Compressor terminal C and compressor case: Continuity 

indicates a grounded motor. The compressor must be 
replaced.

9.   Disconnect the yellow wires from the capacitor. Set the 

ohmmeter to the Rx1 scale. The capacitor is shorted and 
must be replaced if continuity exists across its terminals. 
If there is no needle movement with the meter set on 
the Rx100000 scale, the capacitor is open and must be 
replaced.

10.  Reconnect the wires to the compressor and capacitor. Plug 

in and turn on the unit. If the compressor fails to start, 
replace the run capacitor.

11.  If the unit doesn’t start, adding a hard-start kit (relay 

& capacitor) will provide greater starting torque. If this 
doesn’t work, the compressor has an internal mechanical 
defect and must be replaced.

5.6B Replacing a Burned Out Compressor

The refrigerant and oil mixture in a compressor is chemically 
very stable under normal operating conditions. However, 
when an electrical short occurs in the compressor motor, 
the resulting high temperature arc causes a portion of the 
refrigerant oil mixture to break down into carbonaceous sludge, 
a very corrosive acid and water. These contaminants must be 
carefully removed otherwise even small residues will attack 
replacement compressor motors and cause failures.

The following procedure is effective only if the system is 
monitored after replacing the compressor to insure that the 
clean up was complete.

1.   This procedure assumes that the previously listed 

compressor motor circuit tests revealed a shorted or open 

SANTA FE CLASSIC INSTALLER'S AND OWNER'S MANUAL

5

Santa Fe Classic Installer’s & Owner’s Manual

Содержание Clasic 4029700

Страница 1: ...llation operating and safety instructions warranty information and all ancillary products n Read and save these instructions For small usage 420l Lien Rd Madison WI 53704 TOLL FREE 1 800 533 7533 www...

Страница 2: ...5 CFM 0 0 WG Power 700 watts 80 F and 60 RH Supply Voltage 115 volt 1 phase 60 Hz Current Draw 6 4 amps Operating Temp 56 F Min 95 F Max Sized for 2 500 Sq Ft Typical Minimum Performance at 80 F and 6...

Страница 3: ...o the Santa Fe Classic room Third a slight negative pressure is created in the room with the Santa Fe Classic which could back draft open combustion devices located there If such devices are present c...

Страница 4: ...ted If a warranty repair is required call the factory first at 1 800 533 7533 Ext 8459 for warranty claim authorization and technical assistance 5 2 Technical Description The Santa Fe Classic uses a r...

Страница 5: ...connection in the compressor circuit Test each component for continuity see the appropriate section if a defect is suspected 3 Unplug the unit then disconnect the red and yellow wires from compressor...

Страница 6: ...ternate method of removing moisture and non condensibles from the system requires evacuation to 29 Hg vacuum Then break the vacuum with 35 to 50 PSIG refrigerant vapor charge Leave the vapor charge in...

Страница 7: ...6 Wiring Diagram SANTA FE CLASSIC WIRING DIAGRAM 7 Santa Fe Classic Installer s Owner s Manual Figure 2 Electrical Schematic of the Santa Fe Classic Dehumidifier...

Страница 8: ...1 1 Defrost Thermostat 4021648 1 Defrost Control Mounting Clip 12 4033925 02 1 Evaporator Coil E Coated 13 4029510 1 Filter Drier 14 4021626 1 Hose Drain 56 ID x 8 15 4021469 1 Humidity Controller 16...

Страница 9: ...o be used to connect to the remote dehumidistat through the connector 6 Disconnect the dehumidistat leads and reconnect with the new wires 7 Replace the wiring box and screws Replace the front cover a...

Страница 10: ...are located near the bottom and on the same side of the unit as the drain hose STEP 5 Example of hose cut at a 45 angle The angle prevents the hose from sealing tight against the bottom of the pump re...

Страница 11: ...des 4 Replace the filters in the unit Exhaust Collar Mounting Instructions 5 The six inch opening may be used as a fresh air inlet from outside 6 Remove the exhaust collar from the box and bend the ta...

Страница 12: ...ed on the Santa Fe Classic Loosen these 2 screws enough to slide the silencer under the screw heads Insert 1 screw from the enclosed parts and tighten Santa Fe Classic Muffler Kit Installed On the San...

Страница 13: ...er s Owner s Manual Instructions To prevent damaging the foam filter place it grid side up on top of the pleated filter and slide them both into the filter slot Foam filter with plastic grid up Pleate...

Страница 14: ...ent that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warr...

Страница 15: ...1 800 533 7533 www Santa Fe Products com...

Страница 16: ...1 800 533 7533 www Santa Fe Products com...

Отзывы: