Special Functions
F19xx
~
F20xx
-45-
Special Functions
F19xx
~
F20xx
Code
Function Name
Data Content
Setting
resolution
Factory
preset
1901
Energy-saving mode
selection
0
:
No function
1
:
Simple energy-saving mode
(
V/f mode
)
2
:
Auto energy-saving mode
1
0
1902
Simple energy-saving rate
0
~
50%
1%
0
1903
Simple energy-saving time
0
~
65000
sec,
1sec.
10
2001
V·f separation function
selection
1
:
V·f proportional separation
2
:
Complete separation
1
1
2002
V·f
separation command
voltage
0
:
No function (command given by VRF)
0.01
~
10.23V
0.01V
0
2003
Arbitrary V/f
patten
Intermediate voltage
1
0
~
460V
1V
0
2004
Arbitrary V/f
patten
Intermediate voltage 2
0
~
460V
1V
0
2005
Arbitrary V/f
patten
Intermediate frequency
1
0.05
~
600Hz
0.01Hz
20
2006
Arbitrary V/f
patten
Intermediate frequency
2
0.05
~
600Hz
0.01Hz
40
2007
Automatic torque boost
selection
0
:
No automatic torque boost
1
:
Voltage compensation function
2
:
Slip frequency compensation
1
0
2008
Slip compensation response
time constant
0
~
1000
(
set value
1=10ms
)
1
10
2009
Slip compensation multiple
0.01
~
2
0.01
1