15. Commissioning

Once the hydraulic and electrical connections have been made, check that the connections are tight by allowing water to flow through each 
entry point used. Ensure that the pump is working properly.

16. Use

Sanicom is designed for disposing of wastewater originating from a commercial sink, washing machine, dishwasher, shower or bath and basin.

Sanicom can pump out hot water upto 85°C for short periods only (eg. glass washer cycle etc.)

CAUTION:

1.

  Do not dispose of chemical products (acids, solvents, oils, etc.) into the items connected to the Sanicom.

2.

   In the event of power failure, stop all water flow to the appliances connected to the Sanicom.

17. Troubleshooting

ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY A PROFESSIONAL ELECTRICIAN

SYMPTOMS

PROBABLE CAUSES

REMEDIES

•   Motor does not start

•   The appliance is not switched on
•    The cable is defective

•   Check the electrical installation

•   The alarm sounds

•   Pump is blocked
•   Pump Jammed
•   To much water flowing through

•   Call a service engineer
•   Call a service engineer
•   Reduce water inflow

ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY A PROFESSIONAL ELECTRICIAN

Before carrying out any service work always disconnect power supply.

SYMPTOMS

PROBABLE CAUSES

REMEDIES

•   Motor does not start

•   Pressure reader tube kinked or out of position
•    Electronic card defective

•   Check the electrical installation
•   Call a service engineer

•   Pumps working constantly

•   Vertical discharge too high
•   Electronic card defective

•   Check Installation
•   Call a service engineer

•   Alarm Sounding

•   Pump blocked
•   Pump jammed
•   Electrical problems with motor
•   Too much water flowing through
•   Electronic card defective

•   Call a service engineer
•   If the pump revolves but does not 

pump, call a service engineer

•   Intermittent start-up of pumps

•   The non-return valve broken or leaking

•   Clean or change the valve or call a 

service engineer

FIRST LEVEL TROUBLESHOOTING

SECONDARY LEVEL TROUBLESHOOTING

18. Warranty

Sanicom SFA is guaranteed for 2 years for labour and parts, subject to correct installation and use of the apparatus.

Содержание Sanicom FF03-P95

Страница 1: ...e safety of persons Indication that a risk of electrical origin exists Electrical installation must be carried out by a professional electrician Attention Failure to comply with this instruction could endanger the safe functioning of the apparatus 2 List of Accessories included 25 x 40 A B C D E F G H I x2 x1 x2 x2 x1 x1 x2 x2 x1 Hose clip Hose clip Inlet Cover Hose clip Screw Plug Elbow Hose clip...

Страница 2: ...aste enters the unit As soon as the waste enters the tank the pump starts 5 Performance Curve Height and Length of the discharge pipe Flow Rate litre min Vertical Height Metres 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 12 11 10 9 8 7 6 5 4 3 2 1 0 max 10m 3 7 4m 3m 2m 1m 5m 6m 7m 1 Max 8m max 20m max 30m max 40m max 50m max 60m max 70m max 80m 420mm 330mm 490mm ø 60 230mm ...

Страница 3: ... Maximum current consumption 3 3 A Electrical class I Protection index IP44 Max temp with intermittent functioning 80 Net weight 10 kg In the case of bath or shower tray make sure the waste traps are raised 15cm above floor level CAUTION 1 All applications other than those described in this notice are prohibited 2 Do not exceed an incoming flow rate greater than 80 of the flow rate stated on the d...

Страница 4: ...a vertical rise is required this must be installed at the start of the run before the horizontal section The horizontal section should then have a minimum 1 fall to the final drain point Take care that the discharge valve flap faces the direction of flow If the end of the discharge pipework is much lower than the unit install a riser pipe about 80mm long from the highest point of the discharge run...

Страница 5: ...ronic circuit board On this card use the point marked E V and the unused neutral connection point marked N Use a round 2 x 0 75mm 2 wire which must pass across the lid of the upper casing through the cable gland before being connected to the chosen alarm system The electrical installation should be carried out by a qualified person All wiring must conform to BS7671 1992 requirements for electrical...

Страница 6: ...s Pump is blocked Pump Jammed To much water flowing through Call a service engineer Call a service engineer Reduce water inflow ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY A PROFESSIONAL ELECTRICIAN Before carrying out any service work always disconnect power supply SYMPTOMS PROBABLE CAUSES REMEDIES Motor does not start Pressure reader tube kinked or out of position Electronic card defective Ch...

Страница 7: ...19 Parts ...

Отзывы: