28
28
ENGLISH
Constant Flow Installation Diagram
+
-
SONDA DE
PRESION TDP
VENTILADOR
VARIADOR
DE
FRECUENCIA
COMPUERTAS
MOTORIZADAS
4.3.3 Inverter reconfiguration
For this use, some of the parameters configured in the frequency inverter must be re-programmed. Access the
programming mode (steps 1 and 2 in section 2.2) and then perform the following configuration changes:
-
Press
ENTER
and rotat
e the wheel until “
FUn-
” appears on the screen.
-
Press
ENTER
and rotate the wheel until “
PI-
” appears on the screen.
-
Press
ENTER
and rotate the wheel until “
rPI
” appears on the screen.
-
Press
ENTER
and rotate the wheel until the necessary value appears fo
r the “Pressure to be maintained”
parameter.
Percentage out of selected range in pressure sensor”
.
Required pressure at
measurement point “P”
(Pa)
Value entered
“rPI”
Pressure sensor
pressure range (Pa)
10
10
0
–
100
20
20
0
–
100
30
30
0
–
100
40
40
0
–
100
60
60
0
–
100
80
80
0
–
100
100
33
0
–
300
120
40
0
–
300
180
60
0
–
300
200
66
0
–
300
300
60
0
–
500
350
70
0
–
500
400
80
0
–
500
MOTORISED
DAMPERS
FAN
TDP PRESSURE
SENSOR
FREQUENCY
INVERTER
Содержание VFTM Series
Страница 1: ...VFTM ...
Страница 2: ......
Страница 47: ...47 Fig 2 1 Fig 2 2 ...
Страница 48: ...48 Fig 2 3 Fig 2 4 ...
Страница 49: ...49 Fig 3 1 Fig 3 2 ...
Страница 50: ...50 Fig 3 3 Fig 3 4 ...
Страница 51: ...51 Fig 4 1 Fig 4 2 ...
Страница 52: ...52 Fig 4 3 Fig 4 4 ...
Страница 53: ...53 Fig 5 1 Fig 5 2 ...
Страница 54: ...54 Fig 5 3 Fig 5 4 ...
Страница 55: ......